4. If you want to abort a data entry operation, simply refrain from pushing any buttons for 10
seconds; the data entry operation will time out and the original value of the selected item will be
preserved.
Pressure Units [
1UNITS]
Enter LRV
[ 2ENTLRV]
Enter URV
[ 3ENTURV]
ST 800 Pressure Transmitter User's Manual
41
Table 15 – The Standard Display Menus
atm
bar
ftH2O68F
gf/cm2
inH2O39F
inH2O60F
inH2O68F
inHg0C
kgf/cm2
kPa
mbar
mmH2O4C
mmH2O68F
mmHg0C
MPa
Pa
psi
Torr
mH2O4C
cmH2O4C
###. ##
###. ##
Choose appropriate engineering
units from list for calibration and
writing LRV/URV
This selection determines the units
of the values shown on the following
menu items:
Enter LRV
Enter URV
Set LRV
Set URV
Zero Correct
LRV Correct
URV Correct
Cal Low Point
Cal High Point
Cal Low Correct
Cal High Correct
Barometric Correct
For calibration, this parameter
allows the user to match the value
displayed on the menus to
the units supported by the user's
calibration equipment.
The limits are:
2X the Lower Range Limit (LRL) of
the Meter body and 2X the Upper
Range Limit (URL) of the Meter
body.
The LRV/URV value will be
available in Pressure Units (Simple
Display pressure unit)
Press  to
enter menu
selection
Menu to
select from
list
 to enter
Press  to
enter menu
selection
 Menu to
select
number.
 to enter and
shift to the
next digit to
the right
Revision 15