8 Technical data

8.1 Medium
Working medium:
Dust content:
Pressure dew point:
Oil content:
8.2 Temperature
Ambient temperature:
Storage temperature:
8.3 Product compliance
EMC Directive:
RoHS Directive:
8.4 Pressure
Operating pressure:
Flow rate:
Air consumption:
8.5 Mechanical data
Installation position:
Protection class:
Weight:
www.gemu-group.com
Compressed air and inert gases
Class 3, max. particle size 5 μm, max. particle density 5 mg/m³
Class 4, max. pressure dew point +3 °C
Class 3, max. oil concentration 1 mg/m³
Quality classes to DIN ISO 8573-1
Note: Filter strainers are installed in the pneumatic connectors of the positioner to protect against
rough dirt particles. They can be ordered as spare parts with order number 1435 SFI. Each kit con-
tains 3 filter strainers. These filter strainers are meant as an additional protection and do not re-
place the requirement to filter all site compressed air.
0 — 60 °C (standard, Option code 0, 1, 2, 3)
-20 — 60 °C (with heating element, Option code 4, 5, 6, 7)
≤ 5 °C (heating active)
≥ 15 °C (heating inactive)
0 — 60 °C
2014/30/EU
2011/65/EU
0 — 6 bar
The applied pressure must not exceed the maximum control pressure of the process valve.
50 Nl/min (Flow rate code 01)
90 Nl/min (Flow rate code 02)
0 Nl/min (when idle)
Optional
IP 65 acc. to EN 60529
1.7 kg
11 / 71