16.2 Parameter table

Display
1:SETPOINT
Type of set value
2:INIT ALL
Starting automatic initialization
3:DEFAULT STATE
Return to default setting
11:X-DIRECTION
Direction of X display and actual
value output
12:ALARM FUNCT
Defines the function of the alarm
outputs (ALARM1 and ALARM 2)
13:LEVEL ALARM1
Switch point of alarm 1
14:LEVEL ALARM2
Switch point of alarm 2
15:ERROR FUNCTN
Defines the function of the error
message output (ERROR)
16:ERROR TIME
Valve travel time monitoring
(Error message output)
17:ERROR LEVEL
Maximum system deviation
(Error message output)
18:RANGE FUNCTN
Range monitoring of set value in-
put
21:MIN POSITION
Limits the CLOSED position of the
valve min. position
22:MAX POSITION
Limits the OPEN position of the
valve max. position
23:CLOSETIGHT
Defines the function of the close
tight function
24:SETP DIRECTN
1)
Direction of set value
25:SETP RAMP
Ramp function - set value
26:SPLIT START
Split range (set value range) start 0.0 ... 90
27:SPLIT END
Split range (set value range) end
28:SETP FUNCTN
Defines the function of the control
characteristic
www.gemu-group.com
Function
0..10 V
0..20 mA
4..20 mA
NO INIT
Init OK
NO DEFAULT
DEFAULT
RISE
FALL
OFF
min/max
min/min
max/max
0.0...100.0
0.0...100.0
ERROR
ERROR+ INACTIVE
RANGE
ERROR+RANGE
ERR+RANGE+INAC
auto
0...100
auto
0.0...100.0
< 4 mA
> 20 mA
< 4 mA or > 20 mA
0.0...100
0.0...100
no
min
max
min & max
NORMAL
INVERSE
auto
0...400
10 ... 100
Linear
1:25
1:50
free
33 / 71
Value range
V
mA
mA
-
-
s
%
mA
%
%
s
%
%
16 System mode CLASSIC
Unit
Default setting
4..20 mA
NO INIT
DEFAULT
RISE
OFF
10.0
90.0
ERROR+RANGE
auto
auto
< 4 mA or > 20 mA
0.0
100.0
no
NORMAL
0
0.0
100
Linear
GEMÜ 1435 ePos