LCS100 with Terminal block
Adjustment SITRANS SCSC/TCSC
The SITRANS SCSC/TCSC with connection of LCS100 is adjusted as follows:
* While switching on, the sensors deliver a defined switching sequence in which the switching conditions empty/full/failure
are run through. This switching sequence is checked and evaluated when switch-on pulse monitoring is activated. If this
does not correspond to the definition or is completely missing, the SITRANS SCSC displays a fault. A function test is only
triggered by pressing the test key. This function test is not carried out automatically when switching on the SITRANS SCSC.
** These settings are not defined for the interaction with LCS100 and can be set by the user under consideration of the
WHG requirements.
SITRANS LCS100 2-wire mA and Relay Version
Operating Instructions, 05/2023, A5E52142831-AA
8/16 mA loop (2-wire operation)
SITRANS TCSC
DIL-switch:
1 Mode (min./max. adjustment)
2 Switch-on pulse monitoring* On/Off
3 to 7
1 Mode (min./max. adjustment), channel 1
2 Switch-on pulse monitoring* On/Off
3 to 6
7 Two-point control On/Off
8 Mode (min./max. adjustment), channel 2
LCS100 with M12 plug
Setting:
Max.
On
**
Max.
On
**
Off
Max.
Operating
6.7 WHG Proof Test