Advanced Configuration
SETTINGS
Settings have 4 categories (Range Adjust, HART, Level Variables and Signal Properties).
Write to Unit is used to save any changes to the sensor. Any changes made are not saved into EchoBeam
until Write to Unit is pressed.
MN310255 Rev 10
RANGE ADJUST
Reverse mA
o This setting is used to reverse the 4-20mA span.
o Default is NO (4mA at bottom of tank and 20mA at top of tank).
o Set to Yes will place 20mA at bottom of tank and 4mA at top of tank.
Distance Adjust
o This setting is used to make an adjustment of a measured value to
match the output of the sensor.
Note: This function should only be performed by a trained technician. Never
change this setting unless instructed by a Flowline representative.
Note: Record this setting if a Factory reset is performed.
Section Eight
®
53
|