Export Limitation Configuration Guide
The preceding parameters are tested in a lab environment and can be
preferentially used for configuration and commissioning onsite. They may need to
be adjusted based on the actual situation.
Issue 04 (2022-10-24)
Meter
Power
Model
Lowering
Adjustment
Period
UMP209
0.5s
CHNT
0.5s
DTSU666-H
Copyright © Huawei Technologies Co., Ltd.
3 Configuting Export Limitation Feature
Maximum
Description
Protection Time
3s
3s
Under the Spanish
RD1699 grid standard,
please set Power
Lowering Adjustment
Period 0.8s, Maximum
Protection Time 2s