Export Limitation Configuration Guide
Parameter
Maximum
protection time
Power raising
threshold
Fail-safe power
threshold
Issue 04 (2022-10-24)
Value Range
(3.0,300.0)s
(0.001,
50.000)kW
(0.0, 100.0)%
Copyright © Huawei Technologies Co., Ltd.
3 Configuting Export Limitation Feature
Default Value
3.0s
5.000kW
100.0%
Description
The maximum
duration of the
inverter output
power to the
power grid
exceeding the
preset threshold
detected by the
SmartLogger. If
Switch-off with
0% power limit is
enabled, DO
switch-off is
triggered. This
parameter is used
with Power
lowering
adjustment
period. Refer to
Empirical
Parameters.
Suggestion: Set
this parameter
according to the
maximum
duration allowed
by the local power
company.
Inverter output
power raising
threshold.The
recommended
setting is
1%~2%Pn.
Inverter output
power percentage
controlled by the
SmartLogger
when
communication
between the
SmartLogger and
the power meter
is abnormal.
17