Huawei SmartLogger3000 Configuration Manual page 23

Hide thumbs Also See for SmartLogger3000:
Table of Contents

Advertisement

SmartLogger3000
Export Limitation Configuration Guide
Parameter
Switch-off with
0% power limit
Switch-off control
port
Switch-on control
port
Switch-off state
feedback port
Switch-on state
feedback port
Issue 04 (2022-10-24)
Value Range
Enable/Disable
No/DO1/DO2/D
O3
No/DO1/DO2/D
O3
No/DI1/DI2/DI3/
DI4
No/DI1/DI2/DI3/
DI4
Empirical Parameters
Meter
Power
Model
Lowering
Adjustment
Period
UMG
0.5s
COUNTIS
0.5s
E43
Copyright © Huawei Technologies Co., Ltd.
3 Configuting Export Limitation Feature
Default Value
Disable
No
No
No
No
Maximum
Description
Protection Time
3s
3s
Description
Enables or
disables DO
switch-off. The
default value is
Disable. When
enabled and the
power is limited
to 0%, the DO
performs the
corresponding
action (the hold
time is 5 seconds)
if the current
reverse flow does
not disappear
after 5 seconds.
Set the Switch-off
control port based
on actual cable
connection.
Set the Switch-on
control port based
on actual cable
connection.
Set the Switch-off
state feedback
port based on
actual cable
connection.
Set the Switch-on
state feedback
port based on
actual cable
connection.
18

Advertisement

Table of Contents
loading

Table of Contents