PRODUCT CHECKING AND PARTS IDENTIFICATION
General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power OFF, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
Environment
Before installation, check that the environment meets the following specifications.
Surrounding air
-10°C to +50°C (non-freezing)
temperature
Ambient humidity
90% RH or less (non-condensing)
-20°C to +65°C 
Storage temperature
Ambience
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 1000m for standard operation. 
Altitude, vibration
5.9m/s

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1000m up to 2500m, consider a 3% reduction in the rated current per 500m increase in altitude.
Note
 Install the inverter on a strong surface securely and vertically with bolts.
 Leave enough clearances and take cooling measures.
 Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
 Install the inverter on a nonflammable wall surface.
2
2
or less at 10 to 55Hz (directions of X, Y, Z axes)
Measurement
position
Inverter
5cm
5cm
5cm
Measurement
position