(2) Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive and affix the CE marking on the inverters.
 Low Voltage Directive: 2014/35/EU
 Standard: EN61800-5-1:2007
Outline of instructions
 Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.
Connect the equipment to the earth securely.
 Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)
 Use the cable sizes on page 7 under the following conditions.
Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN60204.
 Use a tinned (plating should not include zinc) crimp terminal to connect the earth cable. When tightening the screw, be
careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable on page 7.
 Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
 When using an earth leakage circuit breaker, use a residual current operated protective device (RCD) of type B (breaker
which can detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other
equipment, or put a transformer between the main power supply and inverter.
 Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the
power supply) specified in IEC60664.
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
To use the inverter outside of an enclosure in the environment of pollution degree 2, fix the fan cover with fan cover
fixing screws enclosed.
FR-D740-080(SC) or lower
FR-D720S-070(SC) and 100(SC)
Example for FR-D740-036(SC)
Note, the protection structure of the Inverter units is considered to be an IP00.
 On the input and output of the inverter, use cables of the type and size set forth in EN60204.
 The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (Relay outputs are
basically isolated from the inverter internal circuit.)
 Control circuit terminals on page 4 are safely isolated from the main circuit.
 Environment
Surrounding air temperature
Humidity
Maximum Altitude

For the installation at an altitude above 1000m up to 2500m, consider a 3% reduction in the rated current per 500m increase in altitude.
FR-D740-120(SC) or higher
Fan cover
fixing screw
Fan cover
Fan connector
Fan
Running
-10°C to +50°C
90% RH or less
(non-condensing)
1000m
Fan cover
fixing screws
Fan cover
Fan
Fan connector
Example for FR-D740-160(SC)
In Storage
-20°C to +65°C
90% RH or less
(non-condensing)
1000m
During Transportation
-20°C to +65°C
90% RH or less
(non-condensing)
10000m
21