3.6 ELECTRICAL WIRING
Main switch
230V ~ 50Hz
Fig. 7
A
3095
ATTENTION:
Do not swap neutral and phase over, follow the diagram shown careful-
ly and carry out a good earth connection.
The section of the conductors must be at least 1mm². (Unless requested oth-
erwise by local standards and legislation).
The electrical wiring carried out by the installer must be in compliance
with the rules in force in the country
TESTING
Check the burner has stopped by opening the thermostats.
Check that the burner is blocked by opening the connector (CN1) inserted in
the probe red wire and located outside the control box.
CONTROL BOX, (see fig. 7)
To remove the control box from the burner it is necessary to:
disconnect all the connectors, the 7-pin plug, the high voltage cables and the
earth wire (TB);
unscrew the bolt (A, fig. 7) and pull the control box in the direction of the ar-
row.
To install the control box it is necessary to:
screw the bolt (A) in at a torque of 1 - 1.2 Nm;
reconnect all the connectors previously disconnected.
NOTES
The burners have been type-approved for intermittent operation. This means they
must stop at least once every 24 hours in order to allow the electrical control box
to check its efficiency on start-up. The boiler limit thermostat (TL) normally en-
sures the burner halts. If this does not happen a time switch halting the burner at
least once every 24 hours must be applied in series to limit thermostat (TL).
E9250
KEY TO LAY-OUT
C
– Capacitor
CN1 – Ionisation probe connector
E
– Electrode
h1
– Hour counter
MV – Motor
PA – Min. air pressure switch
PG – Min. gas pressure svitch
RS – Remote reset
SM – Servomotor for air damper
SO – Ionisation probe
Blue
Black
Brown
D4628
7
GB
S3 – Lock-out signal
(230V - 0.5A max.)
T6A – Fuse
TB – Burner-earth
TL – Limit thermostat
TS – Safety thermostat
V10 – Safety valve
V11 – Adjustment valve
X.. – Plug
XP.. – Socket
CARRIED-OUT
IN THE FACTORY
TO BE DONE BY
THE INSTALLER