Carrier Vector 8100 Operator's Manual page 22

Trailer refrigeration unit
Table of Contents

Advertisement

4. If START PRETRIP is selected, Pretrip will begin and the PRETRIP
STATUS screen will be displayed. Immediately following Pretrip OR if
"View Results of Last Pretrip" is selected the PRETRIP SUMMARY
SCREEN will be displayed.
At any time during Pretrip, the UNIT DATA soft key may be
pressed to allow the user to view the unit data screen, refer to
Unit Data
During Pretrip the ALARM light will illuminate to indicate there is no
temperature control.
5. During Pretrip Test 1, verify that the buzzer is energized and the amber
light on the light bar is illuminated (if equipped).
6. The remainder of the Pretrip tests will run automatically and take 7 to 15
minutes. The percent of Pretrip that has been completed is displayed in
the status bar under the test description information.
7. "PRETRIP PASS", "PRETRIP FAIL IN TEST ##" or "PRETRIP FAILED
AND COMPLETE" will be displayed at the end of the testing. The "PASS"
message will display until a key is pressed. The Pretrip test "FAIL" results
message will display until the alarms are cleared.
To end Pretrip at any time, press STOP PRETRIP soft key.
62-11784
PRETRIP STATUS
PRETRIP TYPE: COOL - AMBIENT 75
TEST 2 OF 10 - CURRENT TEST
LIV
CURRENT DRAW - 2 AMPS
UNIT
TEST
DATA
RESULTS
section. To return to Pretrip, press the BACK soft key.
NOTE
NOTE
TIP
16
o
F
23%
STOP
PRETRIP