5 AC LINE INPUT VOLTAGE

HIGH VOLTAGE CAUTION: This operation must be performed by a
certified electrician.
Wire according to the following points:
Primary wiring: Overcurrent protection should be provided by a 16 A building installation
circuit breaker. PWR-480W input components are rated for an Icp of 10 kA max.
Wiring methods from the branch circuit breaker to the PWR-480W power supply shall comply
with the National Electric Code ANSI\NFPA. The Datalogic DWS-SWITCH is an AC Power
Disconnector and Distributor cabinet which provides this protection.
For primary wiring use a 3-conductor cable (between 2.5 mm
for every conductor. Choose the overall cable diameter and UL Listed conduits accordingly.
The AC input cable must be inserted through the AC Input Cable Compression Connector.
The individual conductors must be inserted into the dedicated terminal blocks on the DIN rail
(see figure below) which are marked Line (L), Neutral (N) and Protection Earth (PE).
Replace the protection cover over the spring clamp connector after correctly installing the
wires.
Figure 13 – PWR-480W AC Line Terminal Block with Protection Covers
The terminal block marked with the ground symbol is a special block which allows direct
connection of the Protection Earth with the enclosure of the PWR-480W.
12
protection covers
PWR-480W INSTALLATION MANUAL