SAFETY REGULATIONS ELECTRICAL SAFETY This product conforms to the applicable requirements contained in the following European Standards: EN 61439-1 • EN 60204-1 • EN 60950-1 +A11 +A1 +A12 +A2 • IMPORTANT: This symbol is used to bring the user’s attention to details that are considered IMPORTANT.
Page 5
Certifications link where you can search your specific product certification. UKCA DECLARATION OF CONFORMITY Hereby, Datalogic S.r.l. declares that the full text of the UKCA Declaration of Conformity is available at: www.datalogic.com. Select the Support & Service > Downloads > Product Certifications link where you can search your specific product certification.
Filtered Air Intake Low voltage thermal-magnetic circuit breakers Filtered Cooling Fan Out 24 Vdc Terminal Block AC Line Input Compression Connector Cable Entry Plate Serial Host Cable AC Line Input Terminal Block Cooling Fan Figure 2 – PWR-480W General View...
1 OPERATING FEATURES 1.1 DESCRIPTION The PWR-480W is an electrical cabinet housing a 24 Vdc power supply which is used to power up a varying number of reading devices (depending on the product), along with their relative accessory devices. See chapter 4 for details.
PWR-480W INSTALLATION MANUAL 1.2.2 Overload Protection In the event of sustained output current overloading, overload protection is provided where overload power is supplied as explained in the examples below: Example 1: Up to 120% power overload The overload is supplied for approximately 12 seconds and then is reduced (Voltage and Current) to about 104% power continuously.
Page 9
OPERATING FEATURES Example 2: 125% power overload The overload is supplied for approximately 10 seconds and then is reduced (Voltage and Current) to about 95% power for another 10 seconds. In this case the output voltage falls below 20 Vdc and therefore the power supply shuts down for a recovery time of 17 seconds. This procedure is repeated until the excessive current overload is resolved.
PWR powers up correctly. The green DC-OK light should be on steady and the overload light (red) should be off. Close and lock the PWR enclosure and check that it does not open (lock functions correctly). The PWR-480W installation is now complete.
IMPORTANT: The cabinet must be installed vertically in such a way that the upper key lock is no higher than 1.90 m from the ground (see Figure 8). Figure 8 – PWR-480W cabinet max. height Please note that the cabinet door can be unlocked and opened by using the key provided...
PWR-480W INSTALLATION MANUAL 3.2 CABLE INSERTION The PWR-480W is provided with a cable entry plate and a cable compression connector. Follow the instructions below to insert the cables correctly. 3.2.1 Cable Entry Plate The Cable Entry Plate mounted onto the cabinet has 10 cable entry points with various hole size grommets that can be inserted into the plate.
MECHANICAL INSTALLATION 3.2.2 Cable Compression Connector The cable compression connector (see Figure 2, item 4) is used for AC connection. Pass the cable through the compression connector and make sure there is enough length to easily reach the AC Terminal Block (see Figure 2, item 6). Make sure to tighten the compression connector nut.
The F10 section is used to power the DC3000 unit. The F10+ and T10- cables are pre- installed on one end in the PWR-480W terminal block as shown in Figure 10. The other end of the F10+ cable must be inserted in the left contact hole of the connector (available in the DC3000 package), while the other end of the T10- cable must be inserted in the central contact hole (refer to the pictures below).
ELECTRICAL CONNECTIONS 4.2 DM3610 TWO-HEAD DIMENSIONING SYSTEM WIRING A single PWR-480W supports the necessary and optional devices used to make up a Two- Head Dimensioning System. For direct wiring, power distribution is performed simultaneously for the Controller and Dimensioners. However, the Dimensioner motors start up slowly so that there is no significant peak current draw.
Page 17
HDMI + USB ports) USB cables Serial Host to DC3000 (D-sub 9-pin) Standard Serial cable *One end of the two-conductor cable is pre-installed in the PWR-480W terminal block. The other end must be connected as described in Paragraph 4.1, Figure 11.
Primary wiring: Overcurrent protection should be provided by a 16 A building installation circuit breaker. PWR-480W input components are rated for an Icp of 10 kA max. Wiring methods from the branch circuit breaker to the PWR-480W power supply shall comply with the National Electric Code ANSI\NFPA.
MAINTENANCE 6 MAINTENANCE 6.1 AIR FILTER CLEANING Air filters should be cleaned on a regular maintenance schedule between once every month and once every three months depending on the environment in which the power supply is installed. To clean the air filters: 1.
PWR-480W INSTALLATION MANUAL 7 TECHNICAL FEATURES PWR-480W ELECTRICAL FEATURES Input Voltage AC from 100 to 240 V from 50 to 60 Hz Input Current Consumption Max 6 A Icp 10kA - output at full load Output Voltage 24 Vdc Nominal Output Current...
Page 21
ELECTRICAL DIAGRAMS ELECTRICAL DIAGRAMS PWR-480W ELECTRICAL DIAGRAM The PWR-480W components are electrically connected as displayed in the following diagram: Figure 14 - PWR-480W Electrical Diagram...