ICPDAS ET-2200 Series User Manual page 61

Ethernet i/o modules
Hide thumbs Also See for ET-2200 Series:
Table of Contents

Advertisement

ET-2200 Series Ethernet I/O Modules
Item
In "PULL" mode, the module will update its I/O data based on the
specified scan time.
In "PUSH" mode, If the local DI/AI changes, the module will
immediately update the remote DO/AO. Furthermore, even if the
Scan Time
local DI/AI remains unchanged throughout the scan time, the
module will still update the remote DO/AO.
The valid range is 1000 to 42949672965 (ms)
AI Count
Used to specify how many AI/AO channels are mapped.
AIO
AI Address
Used to specify the start address of the analog input.
AO Address
Used to specify the start address of the analog output.
IO Count
Used to specify how many DI/DO channels are mapped.
Used to select the DI or DO type for the Local site and to enter
the starting address.
Shared memory is only available for DIO series modules:
Local IO
DIO
Address
DI, DO, AI, and AO data share a common memory block. If
different types of I/O data are written to the same address, all
data will overwrite each other. For more information, refer to
Section 5.5
Used to select the DI or DO type for the Remote site and to
Remote IO
Address
enter the starting address.
Used to set the type of Modbus protocol to be used and can be
Network Protocol
(TCP/UDP)
TCPv4/TCPv6 or UDPv4/ UDPv6
Submit
Click this button to save the changes.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
Description
The DIO (Bit) address ranges from 3000 to 7094
The AIO (Register) address ranges from 3000 to 3254
Shared
Memory.
Defaults
1000 ms
0
0
0
0
0
0
TCPv4
-61 -