Page 3
Q01 : How to add HART devices to HRT-710 ? ..............76 Q02 : How to make sure that HRT-710 gets the HART device data correctly ? ....81 Q03 : How to map HART device CMD(3) data directly to SCADA or HMI ? ...... 84 Q04 : How to update the firmware of HRT-710 ? ...............
Page 4
Q10 : How to integrate HART comm. device with RS-232 hardware interface ? ..... 114 Q11 : How to add the HART Device-Specific command to HRT-710 ? ......115 Q12 : How to set HART device address by HRT-710 utility ? .......... 118 Q13 : All kinds of HART network wiring ? ................
Contact us If you encounter any problems while operating this device, feel free to contact us via mail at: service@icpdas.com . We guarantee to respond within 2 working days. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
250 Ohm (1/4W) 250 Ohm (1W) [ Note ] 1. The software settings for HRT-710 and HRT-310 are all the same and HG_Tool can be used for them. The main features and specifications of HRT-7(3)10 are described as below. HRT-710 / HRT-310 User Manual Version 1.31...
Page 9
HRT-310 Power consumption: 3.5 W (Max.) [ Module Spec. ] HRT-710 Dimensions: 72 mm x 121 mm x 35 mm (W x L x H) HRT-310 Dimensions: 25 mm x 116 mm x 120 mm (W x L x H) ...
2.5 DIP Switch 1. HRT-710 : There is a DIP Switch on the backplane of the HRT-710, as shown in Figure 12. (1) “Normal” : [1] The user’s settings will be adapted in HRT-710. [2] In normal operation, set the DIP Switch to the “Normal” position.
2.6 Jumper 1. HRT-710 : There is a Jumper (JP4) in the HRT-710 module shown as Figure 13. The jumper can provide HART bus with 250Ω (1/4 W) resistor. When the pin 1&2 of JP4 is closed, the resistor will connect to HART bus.
(3) Turn the “dip-switch of Loop Power” in HRT-310 to “ON” position. (It will connect the “H-” of HRT-310 to the internal “LP-” of HRT-310.) (Note: HRT-710 doesn’t support the Loop Power function.) HRT-710 / HRT-310 User Manual Version 1.31 Page:...
(typically 4 mA). The maximum HART device number in HART bus is up to 15. [ Note ] 1. The built-in resistor in HRT-710 is 250 Ohm with 1/4W. Therefore, HRT-710 supports to connect the maximum 7 HART devices simultaneously. If the HART devices in multi-drop mode are more than 7, then users need to disconnect the built-in resistor in HRT-710 (prevent to burn down) and use the external 250 Ohm resistor with 1W.
Page 34
Ex: If the value is 0x0100 for the MB address 1000, then the 1000L is 0x00 and the 1000H is 0x01. It means the error status of “Default CMD(0)” is 0x00 and the error status of “Default CMD(3)” is 0x01 in “Module 0”. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Figure 21: Hardware connection Step 2: Set the module to the default settings. (1)HRT-710: Set the DIP switch in the backplane of HRT-710 to the “default” position. (2)HRT-310: Set the “Default” dip switch to be “ON” position. Please reboot the module and the default settings are as below.
About the data of these items is shown as Table 6. [ Table 6: The data of the node ] Node Behavior Data Module name: HRT-710 / HRT-310 HRT-710 click Firmware version: V01.5 Module name: System...
Page 53
In the function, only supports HART command 0, 1, 2, 3, 6, 11, 12, 13, 14, 15, 16, 17, 18, 19 and the different HART command will show the different user command window (EX: The window of HART command 0 and 6 is shown as below). HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 54
[ Note ] About the “Input data” area of user command, the first 2 bytes are response code1 and code2 of HART command and the left bytes are the HART command data. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 59
[6] Protocol: MB RTU Slave or MB ASCII Slave. [7] Swap mode: None / Byte / Word / W&B (The swap mode of Modbus comm.) EX: 2 words data (0x1234, 0x5678) from HRT-710. Users can set the swap mode for different data format.
Page 60
[1] If the address of HART device is 0, it means in the “Point to Point” mode. [2] If the address of HART device is between 1 and 15, it means in the “Multi-Drop” mode. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
5.4 Establish connection with module The connection between HG_Tool and HRT-7(3)10 is shown as Figure 51. Figure 51: The connection of Utility and HRT-710 Please follow the below steps to establish connection with HRT-7(3)10. Step 1: Wire COM Port of PC to RS-232 port of HRT-7(3)10 Step 2: Run “HG_Tool”...
6. Troubleshooting The troubleshooting list can help users to resolve the problems when using the HRT-7(3)10. If the problem still can't be solved, please E-mail to ICP DAS : service@icpdas.com. [ Table 7: Errors and Solutions ] Trouble state Solution...
[ Step 1 ] Connect to HRT-710 with “HG_Tool” utility. (1) Set the com port parameters. (2) Click the “Connect” button to connect to HRT-710 module like Figure 1-1. Figure 1-1 Connect to HRT-710 [ Step 2 ] Delete the default HART device setting in HRT-710 HRT-710 / HRT-310 User Manual Version 1.31...
Page 77
=> Figure 1-2 Delete the default setting of HRT-710. [ Step 3 ] Add the new HART device setting (1) Method 1 => Choose “Auto Configure” option to be Enable like Figure 1-3. Figure 1-3 Add new HART device setting (Auto Config : Enable) (2) Method 2 =>...
Page 78
Figure 1-4 Add new HART device setting (Auto Config : Disable) [ Step 4 ] Save the HART device setting to HRT-710 (1) Click the “Save to Device” button to save the new HART device setting to HRT-710 like Figure 1-5.
Page 79
0 is not allowed in HART multi-drop network. [ Step 1 ] Connect to HRT-710 with “HG_Tool” utility. [ Step 2 ] Delete the default HART device setting in HRT-710 => These above two steps are the same with those of the “Only One” HART device.
Page 80
Figure 1-6 Add new HART device setting [ Step 4 ] Save the HART device setting to HRT-710 (1) Click the “Save to Device” button to save the new HART device setting to HRT-710 like Figure 1-7. Figure 1-7 “Save to Device” function HRT-710 / HRT-310 User Manual Version 1.31...
Q02 : How to make sure that HRT-710 gets the HART device data correctly ? A02: After adding HART device setting to HRT-710 module (refer to the steps of Q01), please follow the steps. (1) Make sure connecting to HRT-710 with HG_Tool successfully and then click “Device Information”...
Page 82
[ Check I/O Data of the Default CMD(3) ] (5) Right click the button of mouse on the “Default CMD(3)” item and choose the “Basic operation” option to open the “I/O Data” screen of the “Default CMD(3)” like Figure 2-5. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 83
Figure 2-7 The I/O Data screen of the “Default CMD(3)” => NG => If the I/O data of the “Default CMD(0)” and “Default CMD(3)” is ok, it means that the communication between HRT-710 and HART devices is ok. HRT-710 / HRT-310 User Manual Version 1.31...
Q03 : How to map HART device CMD(3) data directly to SCADA or HMI ? A03: (1) Make sure that the communication between HRT-710 and HART device is ok. (Refer to the steps of Q02) (2) Set “Swap Mode” of system setting in HRT-710 to be “W&B”.
Page 85
Figure 3-2 Set “Swap mode” to be “W&B” [3] Click the “Save to Device” button to save the new system setting to HRT-710 like Figure 3-3. Figure 3-3 “Save to Device” function (3) Check the firmware version of HRT-710 like Figure 3-4.
Page 86
[1] In firmware v1.5 or newer, HRT-710 provides the MB Address 1300 ~ 1459 (Default CMD(3)(S) Data for Module 0 ~ 15 in HRT-710 => The detailed information refers to the sector 4.3 of users’ manual) and users can map the CMD(3) data of HART device to SCADA directly with these Modbus address 1300 ~ 1459.
Page 90
Figure 3-11 Polling address from “Communication Traffic” <8> Set the “Com Port” parameters and click “OK” button to connect to HRT-710 like Figure 3-12. Figure 3-12 Com Port Parameters of “Modbus Poll” tool <9> The CMD(3) data of HART device is shown like Figure 3-13.
Page 91
Figure 3-13 The CMD(3) data of HART device [ 4.2 - The firmware version of HRT-710 is older than v1.5 ] [1] Add “User CMD(3)” with “Simple” format and then click “Save to Device” to save the new HART device setting to HRT-710 like Figure 3-14. The mapped Modbus start address and length of User CMD(3) data can be found in “Cmd In address”...
Page 92
[2] The below MB/RTU client will use the “Modbus Poll” tool to show the CMD(3) data of HART device by polling Modbus address 0 ~ 9. <1> Confirm the connection between HG_Tool and HRT-710 is disconnected. <2> Set the “Modbus” parameters like Figure 3-15.
Page 93
<3> Set the “Display” mode to be “Float” format like Figure 3-16. Figure 3-16 “Float” format of “Modbus Poll” tool <4> Set the “Com Port” parameters and click “OK” button to connect to HRT-710 like Figure 3-17. HRT-710 / HRT-310 User Manual Version 1.31...
Page 94
Figure 3-18 The CMD(3) data of HART device [3] The below MB/RTU client will use the “ModScan” tool to show the CMD(3) data of HART device by polling Modbus address 1300 ~1309. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
(1) Download the newest firmware of HRT-710. (Download from ftp://ftp.icpdas.com/pub/cd/fieldbus_cd/hart/gateway/hrt-710/firmware/) (2) Turn off the power and open the shell of HRT-710. Then connect the pin 2 & 3 of JP5 together like Figure 4-1. Figure 4-1 Connect pin 2 & 3 of JP5 together (3) Connect RS-232 cable between PC and HRT-710 and turn on the power of HRT-710 (LED 1,2,3 will flash every second =>...
Page 97
(4) Run “FW_Update_Tool” like Figure 4-3 (Download from : ftp://ftp.icpdas.com/pub/cd/fieldbus_cd/hart/gateway/utilities/fw_tool/ [1] Choose “COM” option and select “Com Port number”. [2] Click “Browser” button to choose the firmware of HRT-710. [3] Click “Firmware Update” button to start firmware update process. [4] Wait for "Firmware Update Success" message.
Page 98
(5) Turn off the power and connect the pin 1 & 2 of JP5 together like Figure 4-4. Figure 4-4 Connect pin 1 & 2 of JP5 together (6) Close the shell and turn on the power of HRT-710. Then users can check the firmware version of HRT-710 by using “HG_Tool” like Figure 4-5.
(1) By using “HG_Tool” to add “User CMD(1)” of HART device and save settings to HRT-710. The Modbus start address and length of the “User CMD(1)” will show in the “Cmd In address” and “Cmd In size” field like Figure 5-1. In the example they are 0 and 7 (byte count=7 =>...
Page 100
(3) Run “MB/RTU” tool. Set the com port settings the same with HART-710 (Baud Rate / Data Bits / Stop Bits / Parity) and then click “Open” button to connect to HRT-710 like Figure 5-2. (4) Input “1 4 0 0 0 4” in “Command” field and click “Send Command” button to send the modbus command.
Page 101
According to the data count is 7, so the actual data will be 00 00 0C 3E C5 20 A4 About the format of HART Command 1, it is shown as below. Command 1: Read Primary Variable HRT-710 / HRT-310 User Manual Version 1.31 Page:...
(3) Run “MB/RTU” tool. Set the com port settings the same with HART-710 (Baud Rate / Data Bits / Stop Bits / Parity) and then click “Open” button to connect to HRT-710 like Figure 6-2. (4) Input “01 04 02 6A 00 0D” in “Command” field and click “Send Command” button to send the Modbus command.
Page 104
So we need to change the byte order. So the data will be as below. 00 00 41 A1 01 22 0C 3E C5 C5 B0 20 41 B6 78 C0 39 42 C9 91 C5 00 00 00 00 00 HRT-710 / HRT-310 User Manual Version 1.31 Page:...
[ Ex1 => The Default CMD(3) of “HART Device 0 & 1” in HRT-710 is Polling Mode ] < 1. The setting of SWAP Mode is “None” (without Byte and WORD swap) >...
Page 107
[1] High Byte : “The comm. status of Default CMD(0) in device 1. [2] Low Byte : “The comm. status of Default CMD(3) in device 1. Figure 7-1.2 The status of Default CMD(0&3) in Device 0 and Device 1 HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 108
In the Figure 7-1, the status of the Default CMD(3) in device 0 is 0x02 and it means that the HART device for the Default CMD(3) is disconnected from HRT-710. (In the Figure 7-1, the status of the Default CMD(0) is 0x02, too.) [ Ex2 =>...
Page 109
In the Figure 7-3, the status of the User CMD Index = 1 is 0x02. It means that the HART device for the User CMD Index = 1 is disconnected from HRT-710. (In the Figure 7-3, the status of the User CMD Index = 0 is 0x00. It means that the HART device for the User CMD Index = 0 is connected to HRT-710.)
Page 111
1. If there are more than 7 HART devices in the HART network, users need to disable the internal resistor (250 Ohm, 1/4W) of HRT-710 (adjust JP4 to be pin2 and pin3, refer to the section 2.6 for detailed). Then add the external resistor (250 Ohm, 1W) in HART network.
[ Solution ] < Hardware > We suggest the user to use 20 HRT-710 modules to connect to 20 HART devices with point to point wiring. < Software > 1. Set the RS-485 station No. (Net ID) of these twenty HRT-710 modules from 1 to 20.
Page 113
(3) In the “System Edit” screen, please input the RS-485 station No. of HRT-710 in the “Net ID” field. Figure 9-2 Setting for the RS-485 Station No. of HRT-710 (4) After the settings are finished, in the “Device Configuration”, please click the “Save to Device”...
RS-232 hardware interface. [ Solution ] < Hardware > We suggest the user to use HRT-710 and I-7570 to do that and the wiring for this case is like figure 10-1. Figure 10-1 The Hardware Wiring for MCU900 < Software >...
Q11 : How to add the HART Device-Specific command to HRT-710 ? A11: (2013/12/06) [ Case Example ] A user wants to get the HART command No.149 data from Emerson 8800D HART device. [ Solution ] < Software > Users must get the HART Device-Specific command first. The HART command No.149 format of Emerson 8800D is like Figure 11-1.
Page 116
Figure 11-3 Save the parameters to HRT-710 1. Get the Modbus address for the HART command No.149 data. (1) Open the “Address Map” screen and click the “UserCMD(149)” item. [1] In the “Modbus AO” area, the light blue grid means the Modbus address for data sending.
(2) Users can use the Modbus Function Code 4 and address from 0 to 2 to get the HART command No.149 data. (Ex: Request Cmd => 0x01 0x04 0x00 0x00 0x00 0x03) HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Q12 : How to set HART device address by HRT-710 utility ? A12: (2014/03/05) 1. Add the “UserCMD(6)” to HRT-710 : (1) Run “HG_Tool” and connect to HRT-710. (2) Open the “Device Configuration” page. (3) Add “UserCMD(6)” and choose “Manual” option in “Mode” field. (Figure 12-1) (4) Click “Save to Device”...
Page 119
(3) Input the HART device address value and click the “Send” button. (Figure12-4, in the demo, HART device address will be set to be 2. Now the setting value is just saved in HRT-710 not sent out yet.) Fiugre 12-3 The “Basic Operation” of UserCMD(6) Figure 12-4 The “I/O Data”...
2. Load the settings from HRT-710 file to the other HRT-710 module. (1) In the “Device Configuration”, click the “Load From File” button and choose the setting file of HRT-710. Then it will show all the settings in the HG_Tool. HRT-710 / HRT-310 User Manual Version 1.31...
Q15 : How to send HART command for writing ? (Ex: CMD19) A13: (2015/12/23) 1. Add the HART command for writing in HRT-710. (The HART cmd 19 is used in the below example => Final Assembly Number) (1) In the “Device Configuration” page, click the right button of mouse on the “HART Device 0”...
Page 127
(4) After sending the above Modbus command, users can check if these values have been set successfully via HG_Tool. [1] In the “Device Information” page, click the right button of mouse on the “User HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 128
UserCMD in the corresponding byte address in the “Output Data” area. Users can see these values of “11”, “22” and “33” been set successfully. 3. Trig the HRT-710 to send the UserCMD0 (HART command 19). HRT-710 / HRT-310 User Manual Version 1.31...
Page 131
RTU_Center software. Main Info -> Server Info -> Server Port => 10000. (default) (3) Main Info -> RS485 Info => The same serial port comm. settings of HRT-710. (4) Modbus Device =>Add the Modbus address of HART device data. HRT-710 / HRT-310 User Manual Version 1.31...
Page 132
(1) Create a new 3G connection device for the GT-540. [1] Module : choose the “GT-540” option. [2] Station ID : Set to be “1” (The same with Machine ID in GT-540 utility) HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 133
[5] QV : AI8 and AI9 (DWORD: 0x41371C71 -> Float: 11.44444) (3) Click the “GT-540 -> HRT-710_Dev2” item in RTU_Center and it will show the HART device 2 data in the AI0~AI9 fields as below. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
Page 134
[1] Run the OPC Server (M2M DA Server)。 [2] Click the “Search” function, it will add all the data in RTU_Center to OPC server automatically and then click the “Monitor” button to show the real-time info. HRT-710 / HRT-310 User Manual Version 1.31 Page:...
[1]Add FW update via Com Port 1. FW update to v1.3 1.20 Raiden 2012/03/06 [1]Add “Simple Format” function 1. Modify the product name to HRT-710. 2. FW update to v1.5: [1]Add on-line replacement of HART devices. [2]Add Long Frame Address acquisition 1.23 Edward 2012/12/04 automatically.