Unpacking; Location And Mounting; Electrical Grommet(S); Installation Wiring For Ats Utility Socket - Champion 102006 Installation Manual

Service entry whole house automatic transfer switch (ats)
Table of Contents

Advertisement

WHOLE HOUSE AUTOMATIC TRANSFER SWITCH - ALL aXis CONTROLLER

UNpACkING

1. Use care when unpacking to avoid damaging transfer switch
components.
2. Allow the ATS to acclimate to room temperature for
a minimum of 24 hours before unpacking to prevent
condensation on the electrical apparatus.
3. Use a wet/dry vacuum cleaner or a dry cloth to remove dirt
and packing material that may have accumulated in the
transfer switch or any of its components during storage.
4. Do not use compressed air to clean the switch, cleaning with
compressed air can cause debris to lodge in the components
and damage the switch per the ATS manufacturers
specifications.
5. Retain the ATS manual with or near the ATS for future
reference.
TOOLS REQUIRED
5/16 in. Hex Wrench
1/4 in. Flat Screwdriver

Location and Mounting

Install the ATS as close as possible to utility meter socket. Wires
will run between the ATS and main distribution panel, proper
installation and conduit are required by code. Mount the ATS
vertically to a rigid supporting structure. To prevent the ATS or
enclosure box from distortion, level all mounting points; use
washers behind the mounting holes (outside the enclosure,
between enclosure and supporting structure), see following image.
The recommended fasteners are 1/4" lag screws. Always follow
local code.
NOT INCLUDED
Mounting Hardware
Line Voltage Wire
Conduit
Fittings
16 in.
16 in.
406.4 mm
(406.4 mm)
MODELS
®

Electrical Grommet(s)

Grommets can be used in any enclosure knockout for NEMA 1
installations. Grommets can only be used in the bottom enclosure
knockouts for NEMA 3R installations, when installed outside.

Installation Wiring for ATS Utility Socket

The manufacturer recommends that a licensed electrician or
an individual with complete knowledge of electricity perform
these procedures.
Always be certain that the power from the main panel is
turned "OFF" and all backup sources are locked out prior to
removal of the cover or removal of any wiring of the utility
main electrical distribution panel.
Be aware, automatic start generators will start upon loss of
utility main power unless locked in the "OFF" position.
Failure to do so could result in serious injury or death.
Consult with your Local municipal, State and National
electrical codes for proper mandatory wiring methods.
Conductor sizes must be adequate to handle the maximum current
to which they will be subjected. The installation must comply fully
with all applicable codes, standards and regulations. Conductors
must be properly supported, of approved insulation materials,
protected by approved conduit and with the correct wire gauge
size in accordance with all applicable codes. Before connecting
wire cables to terminals, remove any surface oxides from the
cable ends with a wire brush. All power cables must enter the
enclosure through the enclosure knockouts.
1. Determine where the flexible, liquid tight conduit will pass
through the building from the inside to outside. When you
are certain that there is adequate clearance on each side of
the wall, drill a small pilot hole through the wall to mark the
location. Drill an appropriate sized hole through the sheathing
and siding.
2. In compliance with all local electrical codes, route the conduit
along ceiling/floor joists and wall studs to the location where
the conduit will pass through the wall to the exterior of the
house. Once the conduit is pulled through the wall and in
proper position to attach to the HSB generator, place silicone
caulk around the conduit on both side of the hole, inside and
outside.
3. Mount the ATS near the Utility meter socket.
8
UNpACkING
WARNING
CAUTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

102007102008102009102010

Table of Contents