400A Installation - Champion 102006 Installation Manual

Service entry whole house automatic transfer switch (ats)
Table of Contents

Advertisement

WHOLE HOUSE AUTOMATIC TRANSFER SWITCH - ALL aXis CONTROLLER

400A Installation

The following instructions are for installing two (2) 200A ATSs,
allowing 400A service.
Primary ATS installed and connected to primary distribution
panel as shown in the Installation Manual for the aXis Controller
Automatic Transfer Switch (ATS), in "Wiring the ATS."
Secondary ATS installed and connected to secondary distribution
panel as shown below.
Models affected
– 100515- 14-kW aXis Home Standby Generator
– 102006 - 200A ATS
– 102007 - 200A ATS
HSB output (L1, L2, N, G) must be brought to a junction box
(customer supplied) and split to supply both primary ATS and
secondary ATS.
Have only qualified personnel who are familiar with applicable
codes, standards and regulations install and service the
generator. ALWAYS comply with local, state, province, or
territory and national electrical and building codes when
installing the generator. NEVER alter the recommended
installation in a way that would render the unit noncompliant
with these codes. ALWAYS comply with regulations that
Occupational Safety and Health Administration (OSHA) has
established. ENSURE the generator is installed following the
manufacturer's instructions.
Gaseous fuels such as NG and LPG are highly explosive.
Even the slightest spark can ignite such fuels and cause an
explosion, which could cause burns, fire or explosion resulting
in serious injury, property damage or even death. NO leakage
is permitted.
WARNING
DANGER
MODELS
®
ALWAYS prevent the generator from starting while the covers
are open. The generator may crank and start at any time
without notice. Follow these steps in order:
®
1. Pull fuse from aXis Controller
to the panel.
2. Disconnect the NEGATIVE, NEG or (-) battery cable first,
and then remove the POSITIVE, POS or (+) battery cable.
To return the generator to service, follow these steps in order:
1. Connect the POSITIVE, POS or (+) battery cable first, and
then connect the NEGATIVE, NEG or (-) battery cable.
2. Remove taped fuse from the panel and reinstall into the
aXis Controller
12
INSTALLATION
WARNING
panel and secure with tape
®
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

102007102008102009102010

Table of Contents