WHOLE HOUSE AUTOMATIC TRANSFER SWITCH - ALL aXis CONTROLLER

primary ATS LEDs

1 ~ 8, 10 & 11 DIP switches in "ON" position.
9 and 12 DIP switches in the "OFF" position.
The LEDs will illuminate after utility power is supplied.
Primary
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

Secondary ATS LEDs

1 ~ 8 DIP switches in the "ON" position.
9, 10 and 12 DIP switches in the "OFF" position.
The LEDs will illuminate after utility power is supplied.
Secondary
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
14
MODELS
®
The LEDs shown pertain only to aXis Controller
Management Modules (LMM).
Both LMM 1 through 4 (LMM1-4) and Gen stop/start (GSTOP/
GSTART) are not illuminated. This is normal and will occur when
DIP #10 is in the OFF (Secondary ATS) position.
1 2 3 4 5 6 7 8 9 10 11 12
For support, see Settings on the aXis Controller
LMM modules can be attached to either primary or secondary
distribution panel circuits but will be controlled only by primary
ATS. LMM priority is determined by primary ATS and loads will be
controlled as required per the settings input to primary ATS.
Primary ATS kW setting must match HSB rating. Primary ATS will
communicate with secondary ATS to determine total load usage
and determine need to activate LMM modules (if applicable).
When performing LEARN function for loads on LMMs; both
primary and secondary ATS need to be active, but only the primary
ATS is required to LEARN.
HSB is fully controlled by primary ATS. Starting and stopping along
with exercise requirement commands are sent by primary ATS.
Wi-Fi connection should be made at install time to both primary
and secondary ATS units to set day, date, time variables.
Secondary ATS does not need exercise day, date, time set
although it will not affect any operation if set.
HSB battery charge connection (120VAC) can come from either
primary or secondary ATS or primary or secondary distribution
panel. The connection should be fused with no greater than 15A
regardless of source.
Low voltage AC connections can be made from either primary or
secondary ATS.
Secondary ATS low voltage NOT active with DIP switch in the
"OFF" position.