Daikin VRV 5 RXYA8A7Y1B Installer And User Manual page 71

Hide thumbs Also See for VRV 5 RXYA8A7Y1B:
Table of Contents

Advertisement

RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
SV unit
Room area
2
A=15 m²<40 m²
A
[m
]
2
min
110
100
90
80
No safety measure
70
60
50
40
30
20
10
0
5
15
10
20
m Total refrigerant charge in the system [kg]
A
Minimum room area [m²]
min
(a) Lowest underground floor (=Lowest underground floor)
(b) All other floors (=All other floors)
(c) No safety measure (=No safety measure)
(d) Alarm OR Natural ventilation (=Alarm OR Natural ventilation)
(e) NOT allowed (=NOT allowed)
(f) Alarm + shut-off valve [SV unit] OR Alarm + natural ventilation (=Alarm + shut-off
valve [SV unit] OR Alarm + natural ventilation)
16
Special requirements for R32 units
|
Required safety measure
Alarm + natural ventilation OR
Alarm + shut-off valve (SV unit)
(c)
Alarm + shut-off valve [SV unit]
OR
Alarm + natural ventilation
(f)
25
35
45
m [kg]
30
40
50
Installer and user reference guide
71