• When charging is interrupted or finished, reinspect the unit but do not let the compressor run into operation.
• Do not use mixture of refrigerant vapor and air or oxygen for pressurizing for fear of explosion.

16. Refrigerant Collecting

When relocating or disposing of the indoor/outdoor unit, pump down the system following the procedure below
so that no refrigerant is released into the atmosphere.
(1) Turn off the power supply (circuit breaker).
(2) Connect the low-pressure valve on the gauge manifold to the charge plug (lowpressure side) on the outdoor
unit.
(3) Close the liquid stop valve completely.
(4) Supply power (circuit breaker).
Start-up of the indoor-outdoor communication takes about 3 minutes after the power (circuit breaker) is turned
on. Start the pump-down operation 3 to 4 minutes after the power (circuit breaker) is turned on.
(5) Perform the refrigerant collecting operation.
At the commissioning parameter setting page, by touching "Refri. recovery", it will access to the refrigerant
recovery page.
(6) Fully close the ball valve on the gas pipe side of the outdoor unit when the pressure gauge on the gauge
manifold shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner.
When "Refri. recovery" is set to "On", the control panel will go back to the home page. At this time, any
touch operation except ON/OFF will get no response, with a prompt dialog box popping up, saying "The
refrigerant recovery is running!" By touching ON/OFF, refrigerant recovery will quit.
(7) Turn off the power supply (circuit breaker), remove the gauge manifold, and then disconnect the refrigerant
pipes.
• When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the
pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, personal
injury, etc.