Swegon ESENSA PX TOP 05 Installation Instructions Manual page 13

Hide thumbs Also See for ESENSA PX TOP 05:
Table of Contents

Advertisement

AO1 = outpout 0-10V for external hydraulic postheater
(option)
DO1 = KWout = output PWM for KWout power regulation
(option)
DO2 = KWin- PX: output PWM for KWin power regulation
(option)
| RX SPEED PWM - RX
AO2 = RX SPEED 0-10V - RX (option)
AO3 = 0-10 V output to control cooling capacity
AO4 = outpout 0-10V for internal hydraulic postheater (op-
tion)
DO3 = BYPASS OPEN- PX (with rotary actuator) (prewired)
DO4 = BYPASS CLOSE - PX (with rotary actuator) (prewired)
DO5 = DAMPER 1 (with or without spring return, Imax = 0.5A
DC) (option)
DO6 = DAMPER 2 (with or without spring return, Imax = 0.5A
DC) (option)
DO7 = HEAT OUTPUT (open collector; Vmax=24 VDC;
Imax=0,1 A)
DO8 = COOL OUTPUT (open collector; Vmax=24 VDC;
Imax=0,1 A)
DO9 = ALARM OUTPUT (open collector; Vmax=24 VDC;
Imax=0,1 A)
DO10 = AL dPA OUTPUT (open collector; Vmax=24 VDC;
Imax=0,1 A)
DO11 = FAN ON OUTPUT (open collector; Vmax=24 VDC;
Imax=0,1 A)
ADI1 = BYPASS POS - PX | RX SPEED FEEDBACK - RX
(prewired)
ADI2 = SUPPLY FILTER dPa
ADI3 = EXTRACT FILTER dPa
F1 = FAN 1 (SUPPLY)
F3 = FAN 3 (EXHAUST)
SAT COM = SAT MODBUS or SAT KNX or SAT WIFI-ETHERNET-
(option)
GREEN LED ON = POWERED ON
RED LED ON = ALARM
We reserve the right to alter specifications.
T1 = from outdoors T° sensor (prewired)
T2 = from indoors T° sensor (prewired)
T3 = to outdoors T° sensor (prewired)
T5 = supply T° sensor for IBA/KWout coil (option)
T7 = IBA/EBA anti freeze protection T° sensor (option)
T8 = Cooling coil frost protection sensor
IN1= FIRE ALARM - must be connected to a +12V or +24V
power terminal.
IN2= BOOST - must be connected to a +12V or +24V power
terminal.
IN3= BYPASS ACTIVATION OVERRIDE - must be connected to
a +12V or +24V power terminal.
IN4= Drain pan full contact (only for LP Unit - prewired)-
must be connected to a +12V or +24V power terminal.
K1: Airflow MODE
Demand/Pressure
control
Torque MODE
K2: Airflow control
Demand/Pressure
control
Torque control
K3: Airflow control
Demand/Pressure
control
Torque control
RJ1 = RJ12 connector for TACtouch (option)
RJ2 = RJ12 connector for Modbus Pressure CP mode (option)
RJ3 = RJ12 connector for Modbus Pressure CA mode on sup-
ply flow (option - prewired)
RJ4 = RJ12 connector for Modbus Pressure CA mode on ex-
haust flow and defrost detecting (option - prewired)
GB.ESENSA.MI. 230612
= m³/h K1
= START/STOP
= %torque K1
= m³/h K2
= 0-10V INPUT
= %torque K2
= m³/h K3
= % ON K3 or 0-10 V INPUT
= %torque K3
www.swegon.com
13