Connecting the control cables
This procedure applies to the standard drive module with integrated control unit. With external
control unit (option +P906), the external control cables are connected to the control unit in
the same way. In addition, connect the control unit to the drive module as instructed in
chapter
External control unit (option +P906) (page
1. Remove the middle front cover of the drive module.
2. Attach the option modules if not attached already. See section
drive module with IP20 shrouds (option +B051) (page
3. Lead the control cables inside the drive cabinet.
4. Ground the outer control cable shields 360 degrees at the cabinet lead-through plate
(recommendation).
5. Route the control cables along the control cable duct from bottom or top to the control
unit.
187).
1
2 × Combi screw
M4×8 Torx T20
(1.5 lbf · ft)
2 N·m
101).
Electrical installation 95
3
11
5
Installation example of