Eaton E Series Quick Start Manual page 63

Hide thumbs Also See for E Series:
Table of Contents

Advertisement

Name
Name
Fig. 3:
An assignment to an Adaptive Set parameter adds alternative values to Setting Group
parameters.
By this Adaptive Set assignment, most Setting Group Parameters receive an additional,
alternative value. At first this new value is identical to the DefaultSet value, but it can be
edited the same way. (Double-click it and modify it according to your needs.)
The idea is simple: The protection parameters use the alternative »AdaptSet 1« value as
soon as the assigned signal "V[1] . Pickup" becomes true.
Since there are four normal setting groups, and each of these can have up to four Adaptive
Sets plus the DefaultSet, this means that parameters supporting Adaptive Sets can have up
to 20 different setting values.
Application Examples for Adaptive Parameter Sets
• AR: auto-reclosing with 2 shots
◦ 1
◦ 2
• CLPU: cold load pickup
◦ Motor start, de-sensibilize current protection
• SOTF: switch on to fault
E-Series Family Quick Start Guide
Protection Para/Global Prot Para/I-Prot/50P[1]
Value
ExBlo1
- . -
ExBlo2
- . -
ExBlo TripCmd
- . -
Rvs Blo
- . -
AdaptSet 1
V[1] - 27, 59 . Pickup
AdaptSet 2
- . -
AdaptSet 3
- . -
AdaptSet 4
- . -
Protection Para/Set 1/I-Prot - 50, 51/50P[1] - 50, 51
DefaultSet
Function
Active
ExBlo Fc
Inactive
Rvs Blo Fc
Inactive
Blo TripCmd
Inactive
ExBlo TripCmd Fc
Inactive
Criterion
Fundamental
Pickup
1
Curve Shape
DEFT
t
1
st
shot DEFT characteristic, normal tripping stage
nd
shot INV characteristic, sensitive tripping stage
...
1
2
V[1] - 27, 59 . Pickup
1
DEFT
1
www.eaton.com
4 Good to Know for Commissioning
Unit
In
s
63