Lennox LCH092H Unit Information page 55

Table of Contents

Advertisement

go below the target liquid temperature when adjusting
charge. Note that suction pressure can change as
charge is adjusted.
7 Example LCH150 Circuit 1: At 95°F outdoor ambient
and a measured suction pressure of 130psig, the target
65 °F
Suct
(psig)
108
114
Circuit 1
119
125
108
115
Circuit 2
124
131
E-Refrigerant Charge and Check - Fin/Tube Coil & TXV
LCH094U, 122U, 152U
WARNING-Do not exceed nameplate charge under any
condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant, re­
claim the charge, evacuate the system, and add required
nameplate charge.
This unit is equipped with solenoid valves
which do not allow refrigerant flow between the high side and
the low side when the unit is de-energized. When reclaiming/
evacuating the system, make sure refrigerant/vacuum is
pulled from both the suction and discharge lines. When adding
nameplate charge, add 1/3 to the suction line and 2/3 to the
discharge line.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1 Attach gauge manifolds and operate unit in cooling
mode with economizer disabled until system stabilizes
(approximately five minutes). Make sure outdoor air
dampers are closed.
2 Make sure both compressors are operating.
3 Use a thermometer to accurately measure the outdoor
ambient temperature.
4 Apply the outdoor temperature to tables 20 through 22
to determine normal operating pressures. Pressures
are listed for sea level applications at 80
5
and 67
F wet bulb return air.
5 Compare the normal operating pressures to the pres­
sures obtained from the gauges. Minor variations in
LCH150S Normal Operating Pressures - Fin/Tube - RFC
75 °F
Disc
Suct
Disc
(psig)
(psig)
(psig)
253
112
295
255
119
296
257
129
303
264
136
308
273
111
314
277
119
318
284
131
327
289
140
334
5
F dry bulb
liquid temperature is 96°F. For a measured liquid tem­
perature of 106°F, add charge in increments until mea­
sured liquid temperature agrees with the target liquid
temperature.
TABLE 19
Outdoor Coil Entering Air Temperature
85 °F
95 °F
Suct
Disc
Suct
(psig)
(psig)
(psig)
114
338
117
122
342
125
136
348
141
146
358
155
114
356
117
122
362
125
137
372
141
148
382
155
these pressures may be expected due to differences in
installations. Significant differences could mean that
the system is not properly charged or that a problem
exists with some component in the system. Correct
any system problems before proceeding.
6 If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add refrigerant
to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time refrigerant
is added or removed.
7 Use the following approach method along with the nor­
mal operating pressures to confirm readings.
Outdoor Coil
Entering Air
Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
Outdoor Coil
Entering Air
Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
Page 55
105 °F
Disc
Suct
Disc
(psig)
(psig)
(psig)
384
119
438
390
127
444
403
145
460
413
161
470
400
119
451
409
128
460
422
145
474
434
160
486
TABLE 20
LCH094U
Discharge +10
psig
238
273
313
361
396
448
TABLE 21
LCH122U
Discharge +10
psig
250
288
331
378
412
463
115 °F
Suct
Disc
(psig)
(psig)
122
501
129
501
149
522
167
530
121
508
129
512
147
532
163
541
Suction +5 psig
136
141
143
146
149
152
Suction +5 psig
134
138
141
143
144
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents