Lennox LCH092H Unit Information page 35

Table of Contents

Advertisement

9-Compressor Overload Relays S176, S177
(M-volt CE units)
Relays are wired in series with the appropriate compres­
sor contactor and monitor the current flow to the compres­
sor motor. When the relay senses an overload condition,
N.C. contacts open to de-energize the compressor. Re­
lays are manufactured by Siemens; see figure 7.
10-Variable Frequency Drive A96 (optional)
Units may be equipped with a VFD which alters the supply
power frequency and voltage to the blower motor. Blower
speed is staged depending on the compressor stages,
heating demand, ventilation demand, or smoke alarm.
The amount of airflow for each stage is preset from the fac­
tory. Airflow can be adjusted as shown in Belt Drive Supply
Air Inverter section. The VFD is located below the Unit
Controller.
11-VFD Power To Motor Contactor K202
(optional)
Contactor is used in VFD units equipped with a VFD bypass
option. The three‐pole contactor with a 24VAC coil is ener­
gized by the A55 Unit Controller. K202 allows power from the
VFD to the B3 blower motor in response to blower demand.
12-Inverter Start Forward Rotation Relay K203
(optional)
Relay is used in optional VFD units and is a three-pole dou­
ble-throw relay with a 24VAC coil. K203 is energized by the
A55 Unit Controller and provides input to the A96 VFD to
start blower forward rotation. K203 also de-energizes K3
allowing A96 to control B3 blower.
13-VFD Controller (GP board) A133 (VFD
units)
M2 and earlier versions of Unit Controller only. The GP
board A133 controls and monitors the status of the VFD
A96. The board sends the signal to start the VFD forward
rotation and also sends a 0-10VDC signal to the VFD to
control the speed of the blower rotation. A133 also reports
VFD malfunctions to the A55.
COMPRESSOR OVERLOAD RELAYS
SET RELAYS
TO MAXIMUM
OVERLOAD
SETTING
14-Blower Motor Overload Relay S42
Two hp high efficiency blower motors and M-volt unit blower
motors are equipped with an overload relay. High efficiency
blower motors and M-volt unit blower motors manufactured
before Dec. 19, 2010, are equipped with the relay.
The relay (S42) is connected in line with the blower motor to
monitor the current flow to the motor. When the relay sens­
es an overload condition, a set of normally closed contacts
open to de-energize the blower. Units will be equipped with
a relay manufactured by Telemecanique figure 8 or
Siemens figure 9.
Page 35