B-Refrigerant Charge and Check - Fin/Tube Coil - TXV
LCH092H, 102H, 120H, 150S, 150H
WARNING-Do not exceed nameplate charge under any
condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant, re­
claim the charge, evacuate the system, and add required
nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1 Attach gauge manifolds and operate unit in cooling
mode with economizer disabled until system stabilizes
(approximately five minutes). Make sure outdoor air
dampers are closed.
2 Check each system separately with all stages operat­
ing.
3 Use a thermometer to accurately measure the outdoor
ambient temperature.
4 Apply the outdoor temperature to tables 8 through 17
to determine normal operating pressures. Pressures
are listed for sea level applications at 80
5
and 67
F wet bulb return air.
5 Compare the normal operating pressures to the pres­
sures obtained from the gauges. Minor variations in
these pressures may be expected due to differences in
installations. Significant differences could mean that
the system is not properly charged or that a problem
exists with some component in the system. Correct
any system problems before proceeding.
6 If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add refrigerant
to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time refrigerant
is added or removed.
7 Use the following approach method along with the nor­
mal operating pressures to confirm readings.
TABLE 8
LCH092H Fin/Tube Coil - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
o
65
F
235
o
75
F
272
o
85
F
312
o
95
F
357
o
105
F
407
o
115
F
460
5
F dry bulb
CIRCUIT 2
Dis­
Suction
Suction
charge
+5 psig
+10 psig
+5 psig
137
262
139
298
142
338
146
380
149
428
154
477
LCH092H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Coil
Entering
Air Temp
o
65
F
o
75
F
o
85
F
o
95
F
o
105
F
o
115
F
Outdoor
Coil
Entering
Air Temp
o
65
F
o
75
F
o
85
F
o
95
F
o
105
F
o
115
F
LCH102H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Coil
Entering
Air Temp
o
65
F
o
75
F
o
85
F
o
95
F
o
105
F
o
115
F
Outdoor
Coil
Entering
Air Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
LCH120H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Coil
Entering
Air Temp
655 F
137
755 F
141
855 F
144
955 F
146
1055 F
149
153
1155 F
Page 53
TABLE 9
CIRCUIT 1
Dis­
Suction
charge
charge
+5 psig
+10 psig
+10 psig
242
134
279
137
319
140
364
143
414
146
467
151
TABLE 10
LCH102H Fin/Tube Coil - TXV
CIRCUIT 1
Dis­
charge
Suction
charge
+10 psig
+5 psig
+10 psig
241
139
277
141
318
143
362
145
411
148
464
150
TABLE 11
CIRCUIT 1
Dis­
Suction
charge
charge
+5 psig
+10 psig
+10 psig
249
137
285
139
327
141
370
143
420
146
473
148
TABLE 12
LCH120H Fin/Tube Coil - TXV
CIRCUIT 1
Dis­
charge
Suction
charge
+10 psig
+5 psig
+10 psig
259
137
297
140
338
143
382
146
431
149
486
151
TABLE 13
CIRCUIT 1
Dis­
Suction
charge
charge
+5 psig
+10 psig
+10 psig
266
134
303
137
344
140
391
143
443
146
499
149
CIRCUIT 2
Dis­
Suction
+5 psig
262
139
297
143
338
146
379
148
427
151
476
155
CIRCUIT 2
Dis­
Suction
+5 psig
273
141
307
144
348
147
389
149
437
151
486
152
CIRCUIT 2
Dis­
Suction
+5 psig
272
142
306
145
347
148
389
150
436
152
485
154
CIRCUIT 2
Dis­
Suction
+5 psig
283
139
321
142
360
144
406
146
453
148
505
151
CIRCUIT 2
Dis­
Suction
+5 psig
281
139
310
141
358
143
403
145
450
146
497
148

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents