Vertical Through-The-Roof Applications - Majestic DVLB7 Series Manual

Direct vent gas fireplace
Table of Contents

Advertisement

DVBL7 Series Gas Fireplace
. Remove soil to a depth of approximately 16" (406 mm)
below base of snorkel. Install drain pipe. Install window
well (not supplied). Refill hole with 1" (305 mm) of
coarse gravel leaving a clearance of approximately 4"
(10 mm) below snorkel. Figure 21
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4" and 7" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
7. Level the soil so as to maintain a 4" (10 mm) clearance
below snorkel. Figure 21
Firestop
7" Pipe
4" (610 mm)
Minimum*
BG40a
Do not back fill around snorkel.
BG402a
Top Vent
a clearance of at least 4" must be maintained
Below grade installation
between the snorkel and the soil.
1/26/00 djt
If the foundation is re-
cessed,
use
recess
brackets (not supplied)
for securing lower por-
tion of the snorkel. Fas-
ten brackets to wall
Foundation
first, then secure
Recess
to snorkel with
self drilling #8 x
1/ sheet metal
Watertight
screws. It will be
Seal Around
PIpe
necessary to ex-
tend vent pipes
out as far as the
Figure 22 -
protruding
wall
Snorkel Installation,
face. Figure 22
Recessed Foundation
74D3001
All manuals and user guides at all-guides.com
Screws
7TDVSNORK
(Snorkel)
4" (10 mm)
C l e a r a n c e
Min.
Window
Well
Gravel
Drain
Foundation Wall
*A minimum of 4" (610 mm) verti-
cal pipe must be installed when
using the 7TDVSNORK Kit.
Figure 21 -
Below Grade Installation
Snorkel
Wall
Screws
Sheet Metal
Screws
BG401
BG401
Snorkel
2/10/99 djt
VertIcaL throuGh-the-rooF
appLIcatIon
his gas fireplace has been approved for:
Vertical installations up to 40' (1 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 23
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by
18" (450 mm).
example: Maximum horizontal length:
No elbows
= 10' (3 m)
1 x 45° elbow = 8.5' (.6 m)
 x 45° elbows = 7' (.1 m)
A minimum of an 8' (.5 m) vertical rise is required.
Two sets of 45° elbow offsets may be used within the
vertical sections. From 0 to a maximum of 8' (.5 m) of
vent pipe can be used between elbows. Figure 23
7DVCS supports offsets. Figure 27. This application
will require that you first determine the roof pitch and
use the appropriate starter kit. (Refer to Venting Com-
ponents List)
The maximum angular variation allowed in the system
is 70°. Figure 24
For the minimum height of the vent above the highest
point of penetration through the roof refer to Page 1,
Figure 28.
Max. Height 40' (12 m)
Min. Height 8' (2 mm)
12" (305 mm)
Min.
Figure 23 -
Support Straps for Horizontal Runs
Vent InStaLLatIon
Max. 10' (3 m)
Support Straps
Every 3' (914 mm)
FP1183
19