ETC Installation Guide
Dual Tech Vacancy Sensor
Power Up
All EchoConnect terminations in the system must be made before
applying power to the system and sensor. When the sensor is powered,
the PIR and acoustic detection LEDs illuminate for one minute for
calibration and warm-up, and then return to normal operation according
to the configuration.
Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance
tripping. During this time, configuration is not allowed and no events are
triggered.
Configuration
Basic
When the sensor is in Basic
configuration mode (DIP
switch 2 set to Off), the sensor
will activate a Space Off
command when vacancy is
detected.
Custom
When functionality other than
Space Off is required, place the sensor in Custom configuration mode
(DIP switch 2 set to On, the default setting). Customization of the sensor
and all actions are configured using the EchoAccess App. For more
detailed information about custom configuration options available, see
the EchoAccess App integrated help system.

Operation

Dual Technology
When both PIR and acoustic detection are used, the following logic is
used:
• When the space is vacant, only manual control can switch the state
to occupied.
• When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.
• When the vacancy timeout in the space has only been reset by
acoustic detection for 60 minutes, acoustic detection is disabled
until the next PIR detection event.
PIR (only) Detection
When acoustic detection is disabled (DIP switch 6 set to On), the
following logic is used:
Dual Tech Vacancy Sensor
Page 8 of 12
MODE button
and LED
AUXILIARY
button
and LED
ETC