Dual Tech Wall-mount Occupancy Sensor
Program Mode
Program Mode allows for local configuration of a
sensor that is set for Basic configuration mode (DIP
switch 2 set to Off). All basic configuration is set
locally on the sensor using the other available DIP
switches, the [MODE] button and associated amber
Mode LED, and the Auxiliary [A] button and
associated blue Auxiliary LED.
The mode and auxiliary buttons and LEDs are
located on the sensor electronics, accessible with
the cover removed. See
local Echo Program Mode configuration instructions.
Preset
While in Basic configuration mode (DIP switch 2 set to Off), use the
[MODE] and Auxiliary [A] buttons to program the preset that is activated
with an occupancy detected state change. By default, this is Preset 1.
When vacancy is detected, the default action event is Off.
Follow these steps to configure the preset for your sensor:
1. Access the sensor electronics and press and hold the [MODE]
button for three seconds to enter "Program Mode." The Mode LED
lights in amber to indicate the sensor is in Program Mode and the
Auxiliary LED flashes to indicate the preset number controlled by
the occupancy action. By default, this is Preset 1, therefore the LED
will flash one time, pause two seconds and flash again.
2. Press and release the Auxiliary [A] button the number of times that
corresponds to the preset that you want to use. For example, press
the [A] button eight times to set Preset 8. The LED flashes the
number of the preset used.
3. Press and release the [MODE] button to save the current setting.
Vacancy Timeout
Vacancy timeout is the amount of time the sensor waits to take action
after no movement is detected. By default, vacancy timeout is set to 15
minutes (indicated by DIP switch 3 set to Off and 4 set to On; see
Switches on page 7
begins.
When the sensor detects vacancy, the vacancy timeout period begins. If
the sensor does not detect occupancy again during the vacancy timeout
period, the lights turn off and a 30 second grace period begins.
Dual Tech Wall-mount Occupancy Sensor
Preset below
). When the vacancy timeout ends, the grace period
Page 9 of 12
Vacancy Timeout below
and
MODE
AUX
for
DIP
ETC