Wire Specification - ETC Echo Dual Tech Installation Manual

Wall-mount occupancy sensor
Hide thumbs Also See for Echo Dual Tech:

Advertisement

ETC Installation Guide
Dual Tech Wall-mount Occupancy Sensor

Wire Specification

The Dual Tech Wall-mount Occupancy Sensor connects to the
EchoConnect communication bus. EchoConnect is a bi-directional
protocol that uses one pair of wires (data+ and data–) for both data and
power. ETC recommends using Belden 8471 Class 2 wire (or approved
equal – see the ETC cable cross database
Cross-Database
EchoConnect wire run using Belden 8471 may not exceed 500 m
(1,640 ft), with a maximum distance of 400 m (1,312 ft) between any two
devices.
Note:
qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4 cm (10 in) of wiring in the
back box for connection and to allow slack for future service
needs.
Note:
ESD protection. Pull an additional 2.5 mm
grounding when control wires are not installed in grounded metal
conduit.
Note:
EchoConnect communication bus, please note the following:
• Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kits and must be installed using a bus topology.
Refer to the instructions provided with the Cat5 Termination
Kit (7186A1207) for information to terminate Cat5 wiring.
• Not all topologies are supported using Cat5; careful
planning is required to ensure the proper termination kits
are available and the wire is pulled appropriately.
Supplies
The following supplies are provided with the sensor:
• mounting bracket with pre-routed EchoConnect and ground wires
• 2 each mounting screws, 6-32x3/4 in and 6-32x1 3/4 in
• WAGO connectors, 3-position
• decorator style wall plate
Dual Tech Wall-mount Occupancy Sensor
for equal alternatives). The total combined length of an
All control wiring should be installed and terminated by a
ETC requires that all stations and devices be grounded for
When using Category 5 (or equivalent) cable on the
etcconnect.com/Support/Cable-
2
(14 AWG) wire for