Samson 42-36 Mounting And Operating Instructions page 30

Flow regulator
Table of Contents

Advertisement

Installation
Standard mounting position,
suspended
Balanced by a bellows or
diaphragm
All versions
− Air and gases up to 80 °C
− Liquids up to 150 °C
Balanced by a bellows
− All media above 80 °C
− Steam applications
Alternative mounting position,
actuator on top
Balanced by a diaphragm ·
DN 65 and 80
− Air and gases up to 80 °C
− Liquids up to 120 °C
Balanced by a bellows ·
DN 15 to 80
All versions plus:
− Air and gases up to 80 °C
− Liquids up to 120 °C
Alternative mounting
position in riser pipes ·
Balanced by a bellows
Version with fixed plug guide
plus:
− Air and gases up to 80 °C
− Liquids up to 120 °C
Fig. 5-1: Mounting position
Support or suspension
Note
The plant engineering company is responsi-
ble for selecting and implementing a suitable
support or suspension of the installed regula-
tor and the pipeline.
5-2
Depending on the regulator version and
mounting position, the valve, actuator and
pipeline must be supported or suspended.
NOTICE
!
Risk of regulator damage due to incorrect
support.
Î Do not attach supports to the valve, to
moving parts on the actuator or to the
control lines.
Î Contact SAMSON if the mounting posi-
tion differs from the standard mounting
position.
Control line kit
After the actuator has been mounted, attach
the supplied high-pressure control line to the
regulator (see the 'Design and principle of
operation' section).
A control line kit for tapping pressure at the
valve body is available as an accessory part
from SAMSON (u T 3095).
Tip
Needle valves, compensation chambers and
compression-type screw fittings can be sup-
plied as required. These accessories are list-
ed in
T 3095.
u
Compensation chamber
A compensation chamber (18) is required
for liquids above 150 °C as well as for
steam. Install the compensation chamber at
the highest point of the pipeline. The mount-
ing position of the compensation chamber is
indicated by an adhesive label on the cham-
EB 3015 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

42-36 dot42-3742-39

Table of Contents