Figure 5.8.1 - RX-7000HY/5000HY 240V electrical connection with EPS
Note:
The battery inverter does not have an internal RCD as it is isolated. If an external RCD breaker
is mandatory in the country of installation, it must be a type A RCD with the rating r esidual current
not more than 30mA.
1. If you need to use both the grid and backup power functions, refer to Figure 5.8.1 for connection details.
2. The grid terminal and EPS terminal cannot be directly connected together, otherwise the system will
be damaged.
3. The inverter can work in off-grid without grid input, in this situation only use the EPS Load port. PV
or other DC input will be required.
Rev 20230601
RX - 7000HY/5000HY
Page 27 of 41