3. Infrared Sensor Shutdown Delay
This is the delay between the infrared sensor detecting ice and the start of the shutdown
sequence. The infrared sensor shutdown delay is factory-adjusted to 100 seconds and no
adjustment is required for most dispenser unit/ice storage bin applications.
See below for details.
a) Standard Ice Storage Bin:
When installed on a standard ice storage bin, any shutdown delay setting is acceptable.
b) Dispenser Unit:
For typical dispenser unit applications, a 100-second shutdown delay is recommended.
However, on some dispenser unit applications, the ice level at shutoff may need to be
adjusted depending on the dispenser agitation or dispense method. Should a different
shutdown delay be desired, adjust S2 dip switch 1, 2, and 3 to obtain the shutdown delay
needed. See the table below. For further details, contact Hoshizaki Technical Support at
1-800-233-1940.
Note: When the shutdown sequence begins, the compressor de-energizes immediately
and then 5 minutes later the gear motor and fan motor de-energize.
Increasing the shutdown delay allows a higher level of ice in the dispensing
unit/storage bin before shutdown. This could lead to icemaker movement or ice
overflow.
S2 Dip Switch
NO. 1
NO. 2
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
Shutdown Delay
NO. 3
0 seconds
OFF
100 seconds (1.6 minutes)
OFF
1100 seconds (18.3 minutes)
OFF
1650 seconds (27.5 minutes
ON
2200 seconds (36.7 minutes)
OFF
ON
0 seconds
0 Seconds
ON