4. Line Set Size and Refrigerant Charge

The icemaker, line set, and remote condenser unit must contain the same type
of refrigerant. Mixing of refrigerants will result in improper operation and possible
damage to the refrigeration system.
Hoshizaki
Icemaker
F-1501MRJZ(-C)(-SC)
F-2001MRJZ/3(-C(-SC) URC-22FZ
NOTICE
Line Set Size and Refrigerant Charge
Up to 66' (20 m)
Hoshizaki
Remote
Condenser
Liquid
Discharge
Unit
Line
URC-14FZ
3/8"
1/2" OD
OD
3/8"
5/8" OD
OD
Line Set
Charge
Line
Adjustment
Not
Applicable
Not
Applicable
25
Line Set
Greater than 66' (20 m)
Maximum 100' (30.5 m)
Liquid
Discharge
Adjustment
Line
Line
3/8"
1/2" OD
Add 0.4 oz.
OD
for each foot
over 66' (40 g
3/8"
5/8" OD
for each meter
OD
over 20 m).
Write new
total charge
on icemaker's
rating label.
Charge
(R-404A)