Mitsubishi Heavy Industries FDUA160AVSAVH Service Manual page 116

Duct connected-high static pressure type
Table of Contents

Advertisement

Wirings
Wirings
a) Connecting of indoor unit and relay parts
a) Connecting of indoor unit and relay parts
• Connect the accessory wiring to CNJ on the indoor control board.
• Connect the accessory wiring to CNJ on the indoor control board.
• Connect the relays to the accessory wiring as shown below.
• Connect the relays to the accessory wiring as shown below.
b) Connecting of relays and damper motors
b) Connecting of relays and damper motors
• Connect the damper motor cable to the relays as shown below.
• Connect the damper motor cable to the relays as shown below.
• Connect the power source of the damper motors to the terminal block (1, 2) in the indoor
• Connect the power source of the damper motors to the terminal block (1, 2) in the indoor
control box as shown below.
control box as shown below.
• When connecting damper motors, ensure to connect them sequentially starting from zone 1.
• When connecting damper motors, ensure to connect them sequentially starting from zone 1.
Attention
Attention
• Connect in such a way that the wiring color can not be mistaken.
• Connect in such a way that the wiring color can not be mistaken.
It may cause damage or malfunction.
It may cause damage or malfunction.
(CONTROL)
(CONTROL)
CNJ
CNJ
(WHITE)
(WHITE)
Accessory
Accessory
wiring
wiring
Wiring specification
Wiring specification
Accessory Wiring color
Accessory Wiring color
White,Black
White,Black
White,Red
White,Red
Damper moter1 output (for Zone1)
Damper moter1 output (for Zone1)
Blue
Blue
Damper moter2 output (for Zone2)
Damper moter2 output (for Zone2)
Yellow
Yellow
Damper moter3 output (for Zone3)
Damper moter3 output (for Zone3)
Brown
Brown
Damper moter4 output (for Zone4)
Damper moter4 output (for Zone4)
Locally supplied parts
Locally supplied parts
Item
Item
Voltate
Voltate
Damper motor
Damper motor
Frequency
Frequency
Relay
Relay
Cable (from Indoor unit to relays)
Cable (from Indoor unit to relays)
Damper motor cable
Damper motor cable
Input voltage
Input voltage
Transformer *1
Transformer *1
Output voltage
Output voltage
Fuse
Fuse
*1: In case of AC24V, it is necessary.
*1: In case of AC24V, it is necessary.
The size or power source method shall be selected properly depending on the type of the
The size or power source method shall be selected properly depending on the type of the
damper motor and the damper motor cable to be used.
damper motor and the damper motor cable to be used.
(POWER)
(POWER)
Relay for damper
Relay for damper
motors power source
motors power source
LY2F or equivalent
LY2F or equivalent
Damper
Damper
motor
motor
Relay LY2F or equivalent
Relay LY2F or equivalent
Usefulness
Usefulness
Damper motor power source
Damper motor power source
Specification
Specification
240VAC or 24VAC
240VAC or 24VAC
50Hz/60Hz
50Hz/60Hz
LY2F equivalent
LY2F equivalent
0.75mm
0.75mm
2
2
or more
or more
30m or less
30m or less
0.75mm
0.75mm
2
2
or more
or more
30m or less
30m or less
240VAC
240VAC
24VAC
24VAC
FSL or FJL 1.25(EM) Time lag type
FSL or FJL 1.25(EM) Time lag type
(NIPPON SEISEN CABLE, LTD.)
(NIPPON SEISEN CABLE, LTD.)
or equivalent
or equivalent
⑤ 
Method to set the large air
(FDUA160 only)
With the factory default, the air flow volume is set with emphasis on quietness.
When the static pressure setting is 120Pa or more, the air volume can be increased.
(FDUA160 only)
Attention
• If this setting is implemented, the noise will increase, so c
noise is acceptable.
Turn SW8-1 ON before turning on the power source, to select the large air flow volume setting.
SW8-1
SW8-1:OFF
(Standard setting)
SW8-1:ON
(Large air flow volume setting)
115
-
3
-
-
-
'21 • PAC-SM-398
'19 • PAC-SM-316