Preset point of the protective devices
Parts name
Temperature sensor
(for protection over-
loading in heating)
Temperature sensor
(for frost prevention)
Temperature sensor
(for protection high
pressure in cooling)
Temperature sensor
(for detecting dis-
charge pipe temperature)
High pressure switch
(for protection)
Low pressure sensor
(for protection)
Equipped
Mark
unit
Th i -R
Indoor unit
Th i -R
Outdoor unit
Tho-R
Outdoor unit
Tho-D
63H1
Outdoor unit
LPT
Outdoor unit
160, 200 model
ON 63˚C
OFF 56˚C
ON 1.0˚C
OFF 10˚C
ON 65˚C
OFF 51˚C
ON 135˚C
OFF 90˚C
ON 4.15MPa
OFF 3.15MPa
ON 0.227MPa
OFF 0.079MPa