Mitsubishi Heavy Industries FDT125VNPWVH Data Book

Standard inverter packaged air-conditioners, split system, air to air heat pump type, ceilining cassette-4 way type, duct connected-high static pressure type, duct connected-low/middle static pressure type, ceiling suspended type
Table of Contents

Advertisement

Quick Links

DATA BOOK
STANDARD INVERTER PACKAGED
AIR-CONDITIONERS
(Split system, air to air heat pump type)
CEILINING CASSETTE-4 WAY TYPE
FDT125VNPWVH
DUCT CONNECTED-LOW/MIDDLE
STATIC PRESSURE TYPE
FDUM125VNPWVH
Manual No.'22・PAC-DB-409
updated July 28, 2023
DUCT CONNECTED-HIGH STATIC
PRESSURE TYPE
FDU125VNPWVH
CEILING SUSPENDED TYPE
FDE125VNPWVH

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Heavy Industries FDT125VNPWVH

  • Page 1 Manual No.'22・PAC-DB-409 updated July 28, 2023 DATA BOOK STANDARD INVERTER PACKAGED AIR-CONDITIONERS (Split system, air to air heat pump type) CEILINING CASSETTE-4 WAY TYPE DUCT CONNECTED-HIGH STATIC PRESSURE TYPE FDT125VNPWVH FDU125VNPWVH DUCT CONNECTED-LOW/MIDDLE CEILING SUSPENDED TYPE STATIC PRESSURE TYPE FDE125VNPWVH FDUM125VNPWVH...
  • Page 2: Table Of Contents

    '22 • PAC-DB-409 CONTENTS 1. SPECIFICATIONS ············································································ 3 (1) Ceiling cassette-4 way type (FDT) ··············································· 3 (2) Duct connected-High static pressure type (FDU) ···························· 4 (3) Duct connected-Low / Middle static pressure type (FDUM) ··············· 5 (4) Ceiling suspended type (FDE) ···················································· 6 2.
  • Page 3 '22 • PAC-DB-409 11. OPTION PARTS ··············································································· 82 11.1 Wireless kit ·············································································· 82 (1) FDT series (RCN-T-5BW-E2, RCN-T-5BB-E2) ······························· 82 (2) FDU, FDUM series (RCN-KIT4-E2) ············································· 91 (3) FDE series (RCN-E-E3) ··························································· 101 11.2 Motion sensor kit ···································································· 110 (1) FDT series (LB-T-5BW-E, LB-T-5BB-E) ······································ 110 (2) FDU, FDUM series (LB-KIT2) ···················································...
  • Page 4: Specifications

    '22 • PAC-DB-409 1. SPECIFICATIONS (1) Ceiling cassette-4 way type (FDT) FDT125VNPWVH Model Item Indoor unit FDT125VH Outdoor unit FDC125VNP-W Power source 1 Phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 12.1 [5.0 (Min.) — 12.1 (Max.)] Nominal heating capacity (range) 12.1 [4.0 (Min.) —...
  • Page 5: Duct Connected-High Static Pressure Type (Fdu)

    '22 • PAC-DB-409 (2) Duct connected-High static pressure type (FDU) FDU125VNPWVH Model Item Indoor unit FDU125VH Outdoor unit FDC125VNP-W Power source 1 Phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 12.1 [5.0 (Min.) — 12.1 (Max.)] Nominal heating capacity (range) 12.1 [4.0 (Min.) —...
  • Page 6: Duct Connected-Low / Middle Static Pressure Type (Fdum)

    '22 • PAC-DB-409 (3) Duct connected-Low / Middle static pressure type (FDUM) FDUM125VNPWVH Model Item Indoor unit FDUM125VH Outdoor unit FDC125VNP-W Power source 1 Phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 12.1 [5.0 (Min.) — 12.1 (Max.)] Nominal heating capacity (range) 12.1 [4.0 (Min.) —...
  • Page 7: Ceiling Suspended Type (Fde)

    '22 • PAC-DB-409 (4) Ceiling suspended type (FDE) FDE125VNPWVH Model Item Indoor unit FDE125VH Outdoor unit FDC125VNP-W Power source 1 Phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 12.1 [5.0 (Min.) — 12.1 (Max.)] Nominal heating capacity (range) 12.1 [4.0 (Min.) —...
  • Page 8: Exterior Dimensions

    '22 • PAC-DB-409 2. EXTERIOR DIMENSIONS (1) Indoor units (a) Ceiling cassette-4 way type (FDT) Model FDT125VH PJF000Z734 - 7 -...
  • Page 9 '22 • PAC-DB-409 (b) Duct connected-High static pressure type(FDU) Model FDU125VH Symbol Content Gas piping 1280 φ15.88(5/8")(Flare) (Duct dimension) Liquid piping φ9.52(3/8")(Flare) VP25(O.D.32) Drain piping Drain piping Drain hose piece VP20 (Accessory) (Gravity drainage) Hole for wiring (Installed on site) Suspension bolts Outside air opening (Knock out)...
  • Page 10: Hanger Plate For Suspension Bolt

    '22 • PAC-DB-409 (c) Duct connected-Low / Middle static pressure type (FDUM) Model FDUM125VH Symbol Content Gas piping 15.88(5 8")(Flare) Liquid piping 9.52(3 8")(Flare) Drain piping VP25 O.D.32 1280 Duct dimension Drain piping 4 280=1120 VP20 (Gravity drainage) Hole for wiring (M10) Suspension bolts Drain hose piece...
  • Page 11 '22 • PAC-DB-409 (d) Ceiling suspended type (FDE) Model FDE125VH PFA004Z086 - 10 -...
  • Page 12: Outdoor Unit

    '22 • PAC-DB-409 (2) Outdoor unit Model FDC125VNP-W PCA001Z787 - 11 -...
  • Page 13: Remote Control (Option Parts)

    '22 • PAC-DB-409 (3) Remote control (Option parts) (a) Wired remote control Model RC-EX3A Installation space Dimensions (Viewed from front) 30mm 30mm Wiring 配線 30mm 30mm 30mm 30mm 固定穴 Fixing holes R/C temperature sensor Secure minimum spaces for disassembling the case. Upper left and Upper right sides ……30mm or more Bottom side…120mm or more...
  • Page 14 '22 • PAC-DB-409 Model RC-E5 Wiring outlet Cut off the upper thin part of remote control lower case with a nipper or knife, and grind burrs with a file etc. Exposed mounting In case of pulling out In case of pulling out from upper left from center 0.3mm...
  • Page 15 '22 • PAC-DB-409 (b) Wireless remote control RCN-E2(Option parts) Unit: mm - 14 -...
  • Page 16: Electrical Wiring

    '22 • PAC-DB-409 3. ELECTRICAL WIRING (1) Indoor units (a) Ceiling cassette-4 way type (FDT) Model FDT125VH PJF000Z735 - 15 -...
  • Page 17 '22 • PAC-DB-409 (b) Duct connected-High static pressure type (FDU) Model FDU125VH PJG000Z580 - 16 -...
  • Page 18 '22 • PAC-DB-409 (c) Duct connected-Low / Middle static pressure type (FDUM) Model FDUM125VH PJG000Z490 - 17 -...
  • Page 19 '22 • PAC-DB-409 (d) Ceiling suspended type (FDE) Model FDE125VH PFA004Z087 - 18 -...
  • Page 20: Outdoor Unit

    '22 • PAC-DB-409 (2) Outdoor unit Model FDC125VNP-W PCA002Z011 - 19 -...
  • Page 21: Noise Level

    '22 • PAC-DB-409 4. NOISE LEVEL Notes(1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27℃WB. Outdoor unit 35℃DB. (2) The data in the chart are measured in an anechoic room. ecause of reflection. (3) The noise levels measured in the field are usually higher than the data because of reflection. 1.5m 1.5m Measured based on JIS B 8616...
  • Page 22 1000 2000 4000 8000 1000 2000 4000 8000 Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) 1000 2000 4000 8000 1000 2000 4000 8000 Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) '22 • PAC-DB-409 (b) Duct connected-High static pressure type (FDU) Unit Measured based on JIS B 8616 Return duct...
  • Page 23: Outdoor Unit

    1000 2000 4000 8000 1000 2000 4000 8000 1000 2000 4000 8000 Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) '22 • PAC-DB-409 (d) Ceiling suspended type (FDE) Unit Measured based on JIS B 8616 Mike position as right Mike (in front &...
  • Page 24: Characteristics Of Fan

    '22 • PAC-DB-409 5. CHARACTERISTICS OF FAN (1) Duct connected-High static static pressure type (FDU) ・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (SW8-4 OFF : 150Pa, SW8-4 ON : 200Pa) , rated E.S.P., and minimum E.S.P. (SW8-4 OFF : 80Pa, SW8-4 ON : 10Pa) ・Characteristic FAN (2) shows air flow vs E.S.P.
  • Page 25: Duct Connected-Low / Middle Static Pressure Type (Fdum)

    '22 • PAC-DB-409 (2) Duct connected-Low / Middle static pressure type (FDUM) ・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (100Pa) ,  rated E.S.P., and minimum E.S.P. (10Pa) ・Characteristic FAN (2) shows air flow vs E.S.P. curve when set fan tap is set P-Hi with each setting of E.S.P by remote control. ・External Static Pressure (E.S.P.) can be set by wired remote control.
  • Page 26: Temperature And Velocity Distribution

    '22 • PAC-DB-409 6. TEMPERATURE AND VELOCITY DISTRIBUTION Indoor temperature Cooling 27° CDB / 19° CWB Heating 20° CDB Note: These figures represent the typical main range of temperature and velocity distribution at the center of air outlet within the published conditions. In the actual installation, they may differ from the typical figures under the influence of air temperature conditions, ceiling height, operation conditions and obstacles.
  • Page 27: Ceiling Suspended Type (Fde)

    '22 • PAC-DB-409 (2) Ceiling suspended type (FDE) Model FDE125VH Cooling Air flow P-Hi :  Temperature distribution Louver position (℃) 5° Velocity distribution (m/sec) Heating Air flow P-Hi :  Temperature distribution Louver position (℃) 45° Velocity distribution (m/sec) - 26 -...
  • Page 28: Piping System

    Capillary tube (Thi-R2) Strainer Strainer Reducer (Accessory) '19 • PAC-DB-333 '22 • PAC-DB-409 7. PIPING SYSTEM Indoor unit Outdoor unit Heating cycle Model 125 Cooling cycle Service valve Outdoor air temperature sensor Gas pipe (Flare connecting) (φ15.88) (TH2) Muffler Indoor unit Outdoor unit Heating cycle Cooling cycle...
  • Page 29: Range Of Usage & Limitations

    '19 • PAC-DB-333 '22 • PAC-DB-409 8. RANGE OF USAGE & LIMITATIONS 8. RANGE OF USAGE & LIMITATIONS See next page. See next page. Operating temperature range Operating temperature range When used below -5˚C, install a snow hood (prepared on site). When used below -5˚C, install a snow hood (prepared on site).
  • Page 30 '19 • PAC-DB-311D '19 • PAC-DB-311D '19 • PAC-DB-333 '22 • PAC-DB-409 ■ ■ 46℃DB 46℃DB -15℃DB -15℃DB ℃ ℃ ■ ■ ℃ ℃ PCA001Z871 Cooling operation under low outdoor air temperature conditions Cooling operation under low outdoor air temperature conditions PAC models can be operated in cooling mode at low outdoor air temperature condition within above temperature range.
  • Page 31 '19 • PAC-DB-333 '22 • PAC-DB-409 Limitation on unit and piping installation FDC125VNP-W FDC125VNP-W PCA001Z871 PJF000Z317 PCA001Z871 - 30 - - 38 -...
  • Page 32: Selection Chart

    (1) Ceiling cassette-4 way type (FDT) (1) Ceiling cassette-4 way type (FDT) Model FDT90VNPWVH Indoor unit FDT100VH Outdoor unit FDC90VNP-W Model FDT125VNPWVH Indoor unit FDT125VH Outdoor unit FDC125VNP-W Cooling mode Heating mode : HC (kW) (kW) Cooling mode Indoor air temperature...
  • Page 33 '22 • PAC-DB-409 (3) Duct connected-Low/Middle static pressure type (FDUM) Model FDUM125VNPWVH Indoor unit FDUM125VH Outdoor unit FDC125VNP-W Cooling mode (kW) Heating mode:HC (kW) Indoor air temperature Indoor air temperature Outdoor air Outdoor temperature 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB...
  • Page 34 '19 • PAC-DB-333 '22 • PAC-DB-409 [References data] Capacity variation against outdoor and indoor temperature at the maximum compressor speed capacity compensation coefficient shows the ratio to nominal capacity. [References data]   Capacity variation against outdoor and indoor temperature at the maximum compressor speed capacity compensation (I) Model FDC90VNP-W coefficient shows the ratio to nominal capacity.
  • Page 35: Correction Of Cooling And Heating Capacity In Relation To Air Flow Rate Control (Fan Speed)

    How to obtain the cooling and heating capacity Example : The net cooling capacity of the model FDT125VNPWVH with the air flow “P-Hi”, the piping length of 15m, the outdoor unit located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0℃ and outdoor dry-bulb temperature 35℃ is Net cooling capacity = 12.1...
  • Page 36: Application Data

    '22 • PAC-DB-409 '21 • PAC-DB-367D 10. APPLICATION DATA 10.1 Installation of indoor unit (1) Ceiling cassette-4 way type(FDT) PJF012D051 ①B ●Ins This manual is for the installation of the indoor unit. CAUTION For electrical wiring work (Indoor unit), refer to page 58. For remote control installation, refer to page ●Co 62.
  • Page 37 '21 • PAC-DB-367D '22 • PAC-DB-409 2D051 ①Before installation ③Preparation before installation ●Install correctly according to the installation manual. ●If suspension bolt becomes longer, do reinforcement of earthquake resistant. When moving the indoor unit, hold only ●Confirm the following points:  ○For grid ceiling the hanging hardware (4 places) only,  ○Unit type/Power source specification...
  • Page 38 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑤Refrigerant pipe (continued) ④Installation of indoor unit (continued) ⑥D ● Protection of the indoor unit Caution: Refrigerating machine oil should not be applied to the threads of union or external surface of flare. It ●...
  • Page 39 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑦Wiring-out position and wiring connection (continued) ⑥Drain pipe (continued) As wide as possible Indoor power ●When sharing a drain pipe for more than 1 Wiring between indoor Single Split (PAC) series VRF (KX) series (about100mm) and outdoor units source line...
  • Page 40 '21 • PAC-DB-367D '22 • PAC-DB-409 PJF012D037 • Panel installation Read this manual together with the indoor unit’s installation manual. ⑤ Orientation of the panel installation ⑦ Ele Take note that there is an orientation to install the panel. The wiring WARNING Install the panel with the orientation shown on the right.
  • Page 41 '21 • PAC-DB-367D '22 • PAC-DB-409 2D037 ⑦ Electrical wiring ⑨ Installing the inlet grille To attach the inlet grille, follow the procedure described in in the reverse order. The wiring work varies depending on the panel type. Select the wiring work appropriate for the panel type. ③...
  • Page 42 '22 • PAC-DB-409 (2) Duct connected-High static pressure type (FDU) PJG012D022 (a) Indoor unit ○This mo blow typ •This munual is for instaration of an indoor unit and an outdoor air processing unit (FDU-F). •This manual is for the installation of an indoor unit. ①B CAUTION For electrical wiring work (Indoor), refer to page 58.
  • Page 43 '22 • PAC-DB-409 D022 ○This model is high static ducted type air-conditioning unit. Therefore, do not use this model for direct ③Cautions for the handling and installation place of outdoor air processing unit blow type air-conditioning unit. ① This unit monitors the outdoor air temperature at the position of sensor A in the figure, and controls the start and ①Before installation stop with the thermostat based on the value of sensor A and the setting temperature by the remote control.
  • Page 44 '22 • PAC-DB-409 ⑥Duct Work (continued) ⑤Installation of indoor unit ⑦R ⑥Make sure to insulate ducts, in order to prevent dewing on them. Caut Work procedure ⑦Connect the duct with care not to touch the blower (fan motor) with fingers. Or, when inhaling 1.
  • Page 45 '22 • PAC-DB-409 ⑧Drain pipe ⑦Refrigerant pipe Caution Caution haling ● Install the drain pipe according to the installation manual in order to drain properly. ●Be sure to use new pipes for the refrigerant pipes. Use the flare nut attached to the product. Regarding whether existing pipes can be reused or not, and the washing method, refer to the instruction manual of the Imperfection in draining may cause flood indoors and wetting the household goods, etc.
  • Page 46 '22 • PAC-DB-409 ⑧Drain pipe (continued) ⑨Wiring-out position and wiring connection (continued) Main fuse 4. Insulate the drain pipe. ● Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may cause dew condensation and water leakage. ※...
  • Page 47 '22 • PAC-DB-409 (b) Replacement procedure of the fan unit (c) Replacement procedure of the fan unit (c) Replacement procedure of the fan unit Notes(1) The unit is a heavy item. It must be supported securely and handled with care not to drop when it is necessary to replace. (2) For the maintenance space, refer to page 42.
  • Page 48 '21 • PAC-DB-367D '22 • PAC-DB-409 PJG012D021 (3) Duct connected-Low/Middle static pressure type (FDUM) ○This mo (a) Indoor unit blow typ This manual is for the installation of an indoor unit. CAUTION For electrical wiring work (Indoor), refer to page 58. For remote control installation, ①B refer to page 62.
  • Page 49 '21 • PAC-DB-367D '22 • PAC-DB-409 D021 ○This model is middle static ducted type air-conditioning unit. Therefore, do not use this model for direct ③Preparation before installation blow type air-conditioning unit. ●If suspension bolt becomes longer, do reinforcement of earthquake resistant. ①Before installation  ○For grid ceiling   When the suspension bolt length is over 500mm, or the gap between the ceiling and roof is...
  • Page 50 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑤Duct work (continued) ⑤Duct work ⑥R ① A corrugated board (for preventing sputtering) is attached to the main body of the air-conditioner Connecting the air intake/vent ducts 4. R (on the outlet port). Do not remove it until connecting the duct. ①Fresh Air Intake ●An air filter can be provided on the main body of the air-conditioner (on the inlet port).
  • Page 51 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑥Refrigerant pipe (continued) ⑦Drain pipe (continued) 4. Refrigerant is charged in the outdoor unit. 3. Make sure to make descending slope of greater than 1/100 and do not make up-down bend As for the additional refrigerant charge for the indoor unit and piping, refer to the installation and/or trap in the midway.
  • Page 52 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑧Wiring-out position and wiring connection ⑨External static pressure setting (continued) ● Electrical installation work must be performed according to the installation manual by an ● How to start automatic setting ① , ② Same setting as MANUAL SETTING. electrical installation service provider qualified by a power provider of the country, and be ③...
  • Page 53 '22 • PAC-DB-409 (b) Replacement procedure of the fan unit Notes(1) The unit is a heavy item. It must be supported securely and handled with care not to drop when it is necessary to replace. (2) For the maintenance space, refer to page 48. Model FDUM125VH ( i ) Remove the control box and the side panel, and remove the (iii) Remove the screws marked in the circles (2 places) from the...
  • Page 54 '21 • PAC-DB-367D '22 • PAC-DB-409 '21 • PAC-T-390 (4) Ceiling suspended type (FDE) PFA012D636B ① This manual is for the installation of an indoor unit. Insta For electrical wiring work (Indoor), refer to page 58. For remote control installation, refer to page CAUTION 62.
  • Page 55: Hole

    '21 • PAC-T-390 '21 • PAC-T-390 '21 • PAC-DB-367D '22 • PAC-DB-409 Before installation Before installation Before installation Before installation ① ① Preparation before installation (continued) Preparation before installation (continued) ③ ③ (mm) (mm) ※Pipes can be taken out in 3 directions (rear, right or ※Pipes can be taken out in 3 directions (rear, right or Install correctly according to the installation manual.
  • Page 56 '21 • PAC-T-390 '21 • PAC-T-390 '21 • PAC-DB-367D '22 • PAC-DB-409 Refrigerant pipe Refrigerant pipe Drain pipe Drain pipe ⑤ ⑤ ⑥ ⑥ ⑦ ⑦ ●The drain pipes may pull out either from back, right or left side. ●The drain pipes may pull out either from back, right or left side. Caution Caution ●Be sure to use new pipes for the refrigerant pipes.
  • Page 57 '21 • PAC-T-390 '21 • PAC-DB-367D '22 • PAC-DB-409 ⑦ Wiring-out position and wiring connection (continued) Clip FDE (small) operly. Wiring ,etc. ur, the Clip Clip FDE (medium) Wiring Clip Screw ① Screw ① Clip FDE (large) /or trap Wiring roperly Clip Control box Sliding Method...
  • Page 58 '22 • PAC-DB-409 (5) Effective range of cool/hot wind (Reference) (a) FDT series Guideline for ceiling height Model Fan speed setting FDT125VH 3.6m P-Hi 4.5m Note (1) If the ceiling height is over 3m, please consider to add circulators. This table shows reference values in case of four outlet. If you shut some outlets, they are different.
  • Page 59: Electric Wiring Work Installation

    '22 • PAC-DB-409 10.2 Electric wiring work installation PSC012D049 PSC012D117 201609 ② Re Electrical wiring work must be performed by an electrician qualified by a local power provider according to ● Electrical wiring connection the electrical installation technical standards and interior wiring regulations applicable to the installation site. ①...
  • Page 60 '22 • PAC-DB-409 C012D049 201609 AIR CON NO ② Remote control, wiring and functions Operation and confirmation from remote control ③ ● Operation from the eco touch remote Operation from the standard remote Do not install it on the following places AIR CON NO Item control (RC-EX series)
  • Page 61 '22 • PAC-DB-409 ⑤ Operation and setting from remote control ⑤ O A : Refer to the instruction manual for RC-EX series ○:Nearly same function setting and operations are possible. *1: Remote controls before RC-EX1A don't have this function. B : Refer to the installation manual for RC-EX series △:Similar function setting and opperations are possible.
  • Page 62 '22 • PAC-DB-409 ⑤ Operation and setting from remote control (continued) Setting & display item Description RC-EX3A RC-E5 2 Administrator settings Temp increment setting The temp increment setting can be changed by 0.5˚C or 1.0˚C. Set temp display Ways of displaying setting temperatures can be selected. C-E5 [Administrator password] R/C display setting...
  • Page 63: Installation Of Wired Remote Control (Option Parts)

    '22 • PAC-DB-409 '21 • PAC-DB-367D 10.3 Installation of wired remote control (Option parts) 8.3 Installation of wired remote control (Option parts) PJZ012A171 (1) Model RC-EX3A (1) Model RC-EX3A   1 )Safety precautions ●Please read this manual carefully before starting installation work to install the unit properly. Every one of the followings is important information to be observed strictly.
  • Page 64 '21 • PAC-DB-367D '22 • PAC-DB-409   WARNING Do not install the unit in appropriate environment or where inflammable gas could generate, flow in, accumulate or leak. t f I s i t c a l s n i l i o , t s i v l o , r o...
  • Page 65 '21 • PAC-DB-367D '22 • PAC-DB-409   CAUTION Do not install the remote control at following places. i t a r t n . l o ・Where it is exposed to direct sunlight ・Where the ambient temperature becomes 0 ° C or below, or 40 ° C or above ・...
  • Page 66 '21 • PAC-DB-367D '22 • PAC-DB-409 2 )Accessories & Prepare on site   Following parts are provided. Accessories R/C main unit, wood screw (φ3.5 x 16) 2 pcs., Quick reference Following parts are arranged at site. Prepare them according to the respective installation procedures. When the cable length is longer than 100 m, Item name Q’ty...
  • Page 67 '21 • PAC-DB-367D '22 • PAC-DB-409   4)Installation procedure Perform installation and wiring work for the remote control according to the PCB side (Viewed from rear) following procedure. Dimensions (Viewed from front) 固定穴 Fixing holes センサー 端子 Sensor USB port Terminal block To disassemble the R/C case into the upper and lower pieces after assembling them once...
  • Page 68 ブッ シング パテで シール する こ と '21 • PAC-DB-367D '22 • PAC-DB-409   リ モコ ン配線 ③ Connect wires from X and Y terminals of R/C to X and Y terminals of indoor unit. R/C wires (X, Y) have no polarity. Fix wires such that the wires will run around the terminal screws on the top case of R/C.
  • Page 69 '22 • PAC-DB-409 '21 • PAC-DB-367D   5) Main/Sub setting when more than one remote control are used ○ : operable ×: not operable Up to two units of R/C can be used R/C operations Main Sub R/C operations Main Sub ○...
  • Page 70 '21 • PAC-DB-367D '22 • PAC-DB-409 PJA012D730 (2) Model RC-E5 Installation manual for wired remote controller Connect the remote con terminal block. Connect the terminal of r Read together with indoor unit's installation manual. with the terminal of indoo (X and Y are no polarity) WARNING Wiring route is as shown Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the...
  • Page 71 '21 • PAC-DB-367D '22 • PAC-DB-409 lation manual for wired remote controller Connect the remote controller cord to the Sheath ote controller terminal block. Connect the remote control cord to the Sheath Sheath The range of temperature settin Connect the terminal of remote controller (X,Y) Upper case terminal block.
  • Page 72 '21 • PAC-DB-367D '22 • PAC-DB-409 PJA012D730 P J A 0 1 2 D 7 2 9 A Sheath The range of temperature setting When shipped, the range of set temperature differs depending on the operation mode as below. Upper case Board Heating : 16-30˚C (55-86˚F) emperature differs depending on the operation mode as below.
  • Page 73 '21 • PAC-DB-367D '22 • PAC-DB-409 The functional setting ndoor unit connected, when remote Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defin The initial function setting for typical using is performed automatically by the indoor unit connected, when remote Note 1: The initial setting marked “...
  • Page 74 PJA012D73 '21 • PAC-DB-367D '22 • PAC-DB-409 PJA012D730 ned as following table. PJA012D730 omatically defined as following table. Operation message How to set function Operation message How to set function Function description: Function description: ndoor unit. Function No. Operation message Stop air-conditioner and press (SET) (MODE)
  • Page 75: Installation Of Outdoor Unit

    '22 • PAC-DB-409 PSC012D174C 10.4 Installation of outdoor unit Model FDC125VNP-W Inverter driven split PAC INSTALLATION MANUAL FOR OUTDOOR UNIT FDC125VNP-W Designed for R32 refrigerant ◎This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to page 35. ◎When install the unit, be sure to check whether the selection of installation place, power source specifications, usage limitation (piping length, height differences between indoor and outdoor units, power source voltage and etc.) and installation spaces SAFETY PRECAUTIONS...
  • Page 76 '22 • PAC-DB-409 1. HAULAGE AND INSTALLATION (Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.) When a unit is hoisted with slings for haulage, take into consideration the offset of its CAUTION gravity center position.
  • Page 77: Case

    '22 • PAC-DB-409 5) Air tightness test ① Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness from the Gas side service valve’s check joint equipped on the outdoor unit side. While conducting a test, keep the service valve shut all the time. service valve Outdoor unit Indoor unit...
  • Page 78 '22 • PAC-DB-409 4. ELECTRICAL WIRING WORK For details of electrical cabling, refer to the indoor unit installation manual. Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country. In case of faulty wiring connection, indoor unit dose not Electrical installation work must be executed according to the technical standards and other regulations applicable to electrical installations in the country.
  • Page 79: Safety Precautions In Handling Air-Conditioners With Flammable Refrigerant

    '21 • PAC-DB-367D '22 • PAC-DB-409 9.7 Safety precautions in handling air-conditioners with flammable refrigerant 10.5 Safety precautions in handling air-conditioners with flammable refrigerant R32 REFRIGERANT USED R32 REFRIGERANT USED PSA012B839G PSA012B839G • There is information included in the user’s manual and/or There is information included in the user’s manual and/or is leaked, together with an external ignition source, there is a •...
  • Page 80 '21 • PAC-DB-367D '22 • PAC-DB-409 CAUTION 4.9 Checks to electrical devices .9 Checks to electrical devices 10. Charging procedures • Repair and maintenance to electrical components Repair and maintenance to electrical components • Under no circumstances shall potential sources of •...
  • Page 81 '21 • PAC-DB-367D '22 • PAC-DB-409 CAUTION CAUTION • Hoses shall be complete with leak-free disconnect • Hoses shall be complete with leak-free disconnect 13. Recovery 14. Other safety precautions 13. Recovery 14. Other safety precautions couplings and in good condition. couplings and in good condition.
  • Page 82 '21 • PAC-DB-367D '22 • PAC-DB-409 Selection of installation location for the indoor unit Selection of installation location for the indoor unit Minimum installation area for indoor unit Minimum installation area for indoor unit CAUTION CAUTION The indoor unit shall be installed in a room with minimum installation area or more according to the refrigerant charge amount (factory refrigerant charge +additional The indoor unit shall be installed in a room with minimum installation area or more according to the refrigerant charge amount (factory refrigerant charge +additional refrigerant charge).
  • Page 83: Option Parts

    '22 • PAC-DB-409 '20 • PAC-T-352 11. OPTION PARTS 5. WIRELESS KIT 11.1 Wireless kit FDT series(RCN-T-5BW-E2, RCN-T-5BB-E2) (1) Specification (1) FDT series (RCN-T-5BW-E2, RCN-T-5BB-E2) (a) Specification Installation of wireless kit Installation position of wireless kit Receiver Do not install the wireless kit at the following places in order to avoid malfunction.
  • Page 84 '22 • PAC-DB-409 5.1 WIRELESS KIT (RCN-T-5AW-E2) (b) Installation manual Notes: ● 1.Following function of FDT indoor unit series are not able to be set with this wireless remote control. • Individual flap control system ● PJF012D035C PJF012D035 2.This wireless remote control can operate the prevention function without connecting the wired remote control. PJF012D035C Safety precautions ●...
  • Page 85 '22 • PAC-DB-409 WARNING ● Do not wash the unit with water. ● Use the cables for wiring, and connect them securely with care to protect 2D035 electronic parts from external forces. ● When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress electric noises.
  • Page 86 It could cause electric shocks. '22 • PAC-DB-409 ③ ② Preparation before installation (continued) To change setting Master/Slave setting when using Installat plural remote controls 1. Remove the cover by unscrewing two screws from the back of receiver. 2. Change the setting by the switch on PCB. ①...
  • Page 87 '22 • PAC-DB-409 ③ How to install the receiver(continued) n using Installation of the receiver ① ② Put the wiring of the receiver through the opening. ol can indoor ③ Put the wiring on the notch on the control box so as not to be pinched by the control box and lid as shown below.
  • Page 88 '22 • PAC-DB-409 ④ ④ Wireless remote control 2. Setti Installation tips for the remote control holder Fix the remote control holder using the screws supplied with this product. Button * Precautions for installing the holder FAN SPEE Holder for ●...
  • Page 89 '22 • PAC-DB-409 ④ Wireless remote control (continued) 2. Setting details The following functions can be set. Button Number indicator Function setting Fan speed setting : Standard FAN SPEED Fan speed setting : Setting 1 * control Fan speed setting : Setting 2 * Room heating temperature adjustment : Disable Room heating temperature adjustment : +1°C MODE...
  • Page 90 '22 • PAC-DB-409 ⑤ ⑤ Receiver 2. Corre 1 Control plural indoor units with one remote control Restrictions on the thickness and length of wire and re (Maximun total extension 600m.) Up to 16 indoor units can be connected. The d Standard Within 0.3 mm²...
  • Page 91 '22 • PAC-DB-409 ⑤ Receiver (continued) 2. Correlation between illuminance at the receiver The receivable area of the h of wire and reachable area of the signal in a plain view. signal when the illuminance at the receiver is 300lux The drawing in the right shows the correlation between the reachable area of the signal and illuminance at the receiver when the remote...
  • Page 92: Fdu, Fdum Series (Rcn-Kit4-E2)

    '22 • PAC-DB-409 11. OPTION PARTS (2) FDU, FDUM series (RCN-KIT4-E2) (a) Specification 11.1 Wireless kit (RCN-KIT4-E2) (1) Specification PJZ000Z323 Indoor unit terminal block X Y White Black 0.3mm2・2-core O.D.φ5.0mm (Accessory 3m) REMOTE CONTROL SIGNAL RECEIVING SECTION Receives a signal from the remote control. CHECK MODE INDICATOR When an irregularity occurs, the indicator indicates the status of malfunction by symbol.
  • Page 93 '22 • PAC-DB-409 Installation precautions Do not install it on the following placesin order to avoid malfunction. (1) Places exposed to direct sunlight (2) Places near heat devices (3) High humidity places (4) Hot surface or cold surface enough to generate condensation (5) Places exposed to oil mist or steam directly (6) Uneven surface (7) Places affected by the direct airflow of the AC unit...
  • Page 94 PJZ012D112 '22 • PAC-DB-409 PJZ012D112 (b) Installation manual Safety precautions ●Please read this manual carefully before starting installation work to install the unit properly. Safety precautions Every one of the followings is important information to be observed strictly. WARNING Failure to follow these instructions properly may result in serious consequences ●Please read this manual carefully before starting installation work to install the unit properly.
  • Page 95 '22 • PAC-DB-409 WARNING ● Do not wash the unit with water. It could cause electric shocks, fire, or break-down. ● Use the specified cables for wiring, and connect them securely with care to protect electronic parts from external forces. Improper connections or fixing could cause heat generation, fire, etc.
  • Page 96 It could cause electric shocks. '22 • PAC-DB-409 ② ③ Preparation before installation (continued) To change setting Master/Slave setting when using ⑤ Tak plural remote controls ⑥ Fit 1. Remove one screws located on the under of the receiver and detach the board.
  • Page 97 '22 • PAC-DB-409 ③ How to install the receiver(continued) ⑤ Take out the connector to the backside from the hole of the lower case putting through the wiring at ①. ⑥ Fit the upper case and the lower case, and tighten the screws. (B) Installation with enclosed bracket Use this method when installaing onto a gypsum board (7 to 18mm), etc.
  • Page 98 '22 • PAC-DB-409 ③ ④ How to install the receiver (continued) Chan (C) Exposed installation How t Use the following procedure when installing the case with the wiring exposed. The A Cord clamp pump When Wiring remot Band (enclosed) Fix with band To dis button Hole...
  • Page 99 '22 • PAC-DB-409 ④ Wireless remote control (continued) Changing the wireless remote control setting How to change the Auto Run setting The Auto Run mode is not available on the building air-conditioner and gas heat pump series (excluding the cooling/heating free multi system). When using the wireless remote control to operate those models, set the wireless remote control to disable the Auto Run mode.
  • Page 100 '22 • PAC-DB-409 ⑤ ⑤ Receiver (continued) For the shop series For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the indoor unit PCB from [000] to [127] so as not to duplicate. Terminal block Indoor unit (1) Indoor unit (2) Indoor unit (16)
  • Page 101 [0] to [F] so as not to duplicate. Within 2.0 mm² × 600m '22 • PAC-DB-409 ⑤ Receiver (continued) The receivable area of the signal when the illuminance at the receiver is 300lux. The receivable area of the signal when the illuminance at the receiver is 600lux.
  • Page 102: Fde Series (Rcn-E-E3)

    '21 • SCM-DB-314 '22 • PAC-DB-409 (3) FDE series (RCN-E-E3) (3) FDE series (RCN-E-E3) (a) Specification (a) Specification Receiver Installation position of wireless kit Receiver TIMER CHECK RUN Notes (1) Two LR03 AAA dry cell batteries for remote control are enclosed. 133.4 (2) See spec sheet of "Wireless remote control"...
  • Page 103 PFA012D635 PFA012D635 '22 • PAC-DB-409 PFA012D635 (b) Installation manual Safety precautions Please read this manual carefully before starting installation work to install the unit properly. Every one of the followings is important information to be observed strictly. WARNING Failure to follow these instructions properly may result in serious consequences such as death, severe injury, etc.
  • Page 104 '22 • PAC-DB-409 WARNING Do not wash the unit with water. It could cause electric shocks, fire, or break-down. Use the specified cables for wiring, and connect them securely with care to protect electronic parts from external forces. Improper connections or fixing could cause heat generation, fire, etc. When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress electric noises.
  • Page 105 Do not operate the unit with wet hands. It could cause electric shocks. '22 • PAC-DB-409 ② ④ Preparation before installation (continued) Connect t To change setting Master/Slave and conne setting when 1. Remove four screws located on the back of the receiver and This inst using plural detach the board.
  • Page 106 '22 • PAC-DB-409 ④ How to connect the wiring for control box Connect the attached wiring to the signal terminal block primary side XY (for grill side) in the control box, and connect to the CNL connector (3P white) from the receiver . This installation is unnecessary for indoor unit that have wiring is already connected from the signal terminal block to the receiver.
  • Page 107 '22 • PAC-DB-409 ⑤ Wireless remote control Installation tips for the remote control holder Fix the remote control holder using the screws supplied with this product. * Precautions for installing the holder Holder for Wood screw Adjust the position so that it is upright. remote control Ensure that the screw heads are not protruding.
  • Page 108 '22 • PAC-DB-409 ⑤ Wireless remote control (continued) 2. Setting details The following functions can be set. Button Number indicator Function setting Fan speed setting : Standard FAN SPEED Fan speed setting : Setting 1 * Fan speed setting : Setting 2 * Room heating temperature adjustment : Disable Room heating temperature adjustment : +1°C MODE...
  • Page 109 '22 • PAC-DB-409 ⑥ Receiver 1 Control plural indoor units with one remote control Restrictions on the thickness and length of wire (Maximun total extension 600m.) Up to 16 indoor units can be connected. Standard Within 0.3 mm² × 100m Connect the XY terminal with 2 cores wire.
  • Page 110 '22 • PAC-DB-409 ⑥ Receiver (continued) Wireless remote control's operable area 1. Standard signal receiving range 2. Points for attention in connecting a plural [Condition] number of indoor units Illuminance at the receiver area: 360 lux. [Condition] (When no lighting fixture is located within 1m Illuminance at the receiver area: 360 lux.
  • Page 111: Motion Sensor Kit

    '22 • PAC-DB-409 '20 • PAC-T-352 6. MOTION SENSOR KIT 11.2 Motion sensor kit FDT series(LB-T-5BW-E, LB-T-5BB-E) (1) FDT series(LB-T-5BW-E, LB-T-5BB-E) (1) Specification (a) Specification Motion sensor kit Installation position of motion sensor kit Motion sensor Refrigerant pipe Drain pipe Note (1) Motion sensor must be installed to the position as shown.
  • Page 112 '22 • PAC-DB-409 PJF012D036 (b) Installation manual PJF012D036 WARNING ● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring securely so as not to apply unexpected stress on the PCB. Loose connection or hold will cause abnormal heat generation or fire. ●...
  • Page 113 '22 • PAC-DB-409 Installing the motion sensor It is possible to install the motion sensor by replacing with a corner lid on the panel. Aim of the detectable scope Indoor unit Hight of the ceiling Detectable scope① about 4.5 about 6.4 about 7.6 Detectable scope②...
  • Page 114 '22 • PAC-DB-409 Installation of the motion sensor ① Loosen the bolts which fix the panel, and make a gap between the panel and the indoor unit. ② Pass the wiring of the motion sensor through the opening of the panel. ③...
  • Page 115 '22 • PAC-DB-409 Setting the motion sensor The motion sensor will not function if it is only installed. Set the function of the motion sensor by the wired or wireless remote control. Refer to the manual instruction of each remote control for the setting procedure. Note: It is not possible to set by the following remote control models or older.
  • Page 116: Fdu, Fdum Series (Lb-Kit2)

    '22 • PAC-DB-409 (2) FDU, FDUM series (LB-KIT2) 12.2 Motion sensor kit (LB-KIT2) (a) Specification PJZ000Z341 External dimensions Case of wiring out to the side face, cut thin wall part Case of wiring out to the back φ15 (Ciling hole) Wiring pass hole Switch box Lockscrew of cover...
  • Page 117 '22 • PAC-DB-409 Installation precautions Do not install the motion sensor kit at the following places in order to avoid malfunction. (1) Places exposed to direct sunlight (2) Places near heat devices (3) High humidity places (4) Hot surface or cold surface enough to generate condensation (5) Places exposed to oil mist or steam directly (6) Uneven surface (7) Places affected by the direct air flow of the AC unit...
  • Page 118 '22 • PAC-DB-409 (b) Installation manual PJZ012D134 WARNING ● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring securely so as not to apply unexpected stress on the PCB. ● Make sure the power source is turned off when electric wiring work. Otherwise, electric shock, malfunction and improper running may occur.
  • Page 119 '22 • PAC-DB-409 Installing the motion sensor • The recommended height is lower than 4000mm for motion sensor. When the installation height is higher, motion detection accuracy might be reduced. • Sensor will detect the object with a different temperature from the surrounding. •...
  • Page 120 '22 • PAC-DB-409 Option (A) Ceiling plane strength to install the motion sensor directly with screws. ① Prepare a relay wiring on site and lay out the wiring in advance. ② Remove the screw at the side of the motion sensor Relay wiring φ15 hole (prepare on site)
  • Page 121 '22 • PAC-DB-409 Option (B) screws. ① Remove the screw at the side of the motion sensor and slide the upper case in the direction of the arrow. ② (The same as of Option (A)) ② Pull the wiring of the motion sensor toward the side. Cut off the thinner part of the upper case. Lower case Thinner part Upper case...
  • Page 122 '22 • PAC-DB-409 ② Remove the screw at the side of the motion sensor and slide the upper case in the direction of the arrow. Lower case ② (The same as of Option (A)) ③ Pull the wiring of the motion sensor. ③...
  • Page 123 '22 • PAC-DB-409 <In the case of CnV2 connector on the indoor unit PCB> ① Connect the same color to the relay wiring (prepare on site) and the attached wiring <2>. ② Remove the control box cover from the indoor unit. ③...
  • Page 124: Fde Series (Lb-E)

    '22 • PAC-DB-409 (3) FDE series (LB-E) (a) Specification Motion sensor kit Installation position of motion sensor kit Motion Sensor 133.4 Note  1.The recommended height, is lower than 4m for motion sensor. When the installation height is higher, motion detection accuracy might be reduced. Installation of motion sensor kit DO NOT install the motion sensor kit at the following places in order to avoid malfunction.
  • Page 125: Control Box

    PFA012D633 '22 • PAC-DB-409 201802 PFA012D633 (b) Installation manual Insta WARNING ● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring Motion se securely so as not to apply unexpected stress on the PCB. CAUTION Loose connection or hold will cause abnormal heat generation or fire.
  • Page 126  Wiring from the motion sensor and the attached wiring to the '22 • PAC-DB-409 motion sensor kit have been connected when shipped from the factory. Remove the connector at the position of  mark and connect it to the attached wiring to the indoor unit before use. Installing the motion sensor Installing the motion sensor •...
  • Page 127 '22 • PAC-DB-409 01802 Installing the motion sensor (before installing the unit) Motion sensor can be installed by replacing with a cover of the panel. CAUTION: Install the motion sensor before installing the unit. because of working at high place. ①...
  • Page 128 ④ Install the motion sensor Place the connector under the panel and install it to the panel with careful attention to the direction of the motion sensor. '22 • PAC-DB-409 CAUTION: Connect the connectors before installing the motion sensor. In case of connecting after the motion sensor has been installed, it will be necessary to remove the panel.
  • Page 129: User's Manual

    Thank you very much for your purchase of this packaged air conditioning system and motion sensor (4) User’s manual PJZ012A164 kit by Mitsubishi Heavy Industries. This user's manual describes cautions for safety. Please read it along with the indoor unit and remote control user's manual. SAFETY PRECAUTIONS WARNING ●...
  • Page 130 mode” will be displayed on the message display. In auto-off mode F1: High power F2: Energy-saving F1: High power F2: Energy-saving “Complete stop”... When auto-off is enabled, the unit stops. The unit will not resume operation even when human presence is detected. '22 •...
  • Page 131: Simple Wired Remote Control (Rch-E3)

    '22 • PAC-DB-409 11.3 Simple wired remote control (RCH-E3) Note: Following functions of FDU indoor unit series are not able to be set with this simple wired remote control (RCH-E3).  1. 4-fan speed setting (P-Hi/Hi/Me/Lo) 3-fan speed setting (Hi/Me/Lo) Names and functions of sections Remote c Remote control sensor ON/OFF button...
  • Page 132 '22 • PAC-DB-409 MITSUBISHI HEAVY INDUSTRIES,LTD. AIR-CONDITIONING & REFRIGERATION SYSTEMS HEADQUARTERS Remote control installation dimensions In case of embedding wiring Wall surface Wiring Wiring outlet Electrical box (In case of embedding wiring) (Prepare on site) 12×7 slot hole Installation hole 9×4.5 slot hole (2 places)...
  • Page 133 '22 • PAC-DB-409 In case of exposing cord 3. Maste Simple Remote Control Installation Manual PJZ012D069 ⑴   M ake certain to remove a screw on the bottom surface of the ⑴   U p to t remote control. Read together with indoor unit's installation manual. WARNING ⑴...
  • Page 134 '22 • PAC-DB-409 3. Master/ slave setting when more than one remote control are used ⑴   U p to two remote controls can be connected to one unit (or one group) of indoor unit. Switch Setting Function detail Slave remote control indoor unit SW1-1 Master remote control...
  • Page 135 ⑸ Connect the remote control cord to the terminal block. necessary at the wire   Connect the terminals (X and Y) of the remote control and the terminals (X and Y) of the indoor connecting section. Be careful about contact failure. unit. (No polarity of X and Y) 100 - 200m・・・・・・・・・・・・・・・・・0.5mm ×...
  • Page 136 “88” blinks on the temperature setting indicator. (blinking for approximately 2 to 10 seconds while ores data is read) Then, the return air temperature is displayed. When AIR CON No. is pressed, return cores to the indoor unit selection display (example, “U 000”). ON/OFF button.
  • Page 137: Filter Kit (Fdum Series)

    PJ Z012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 Installation P oints and Operating I I n n s s t t a a l l l l a a t t i i o o n n P P o o i i n n t t s s a a n n d d O O p p e e r r a a t t i i n n g g I I n n s s t t a a l l l l a a t t i i o o n n P P o o i i n n t t s s a a n n d d O O p p e e r r a a t t i i n n g g I I n n s s t t a a l l l l a a t t i i o o n n P P o o i i n n t t s s a a n n d d O O p p e e r r a a t t i i n n g g I I n n s s t t a a l l l l a a t t i i o o n n P P o o i i n n t t s s a a n n d d O O p p e e r r a a t t i i n n g g...
  • Page 138 '22 • PAC-DB-409 3. Installation P oints 3. Installation P oints 3. Installation Points 3. Installation Points (1) Stick the insulation on both inner sides of the duct, leaving no space up and down. (1) Stick the insulation on both inner sides of the duct, leaving no space up and down. (Unit inside) (Unit inside) BOTTOM...
  • Page 139: Superlink E Board (Sc-Adna-E)

    '22 • PAC-DB-409 11.5 Superlink E board (SC-ADNA-E) PJZ012D029K - 138 -...
  • Page 140 '22 • PAC-DB-409 cores cores cores cores cores make cores cores - 139 -...
  • Page 141: Technical Information

    (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners, the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 142 (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 143 Total electric power input 0.030 rated,c elec Sound power level Cooling capacity (latent) 50.0 rated,c (per speed setting,if applicable) Heating capacity rated,h Contact details Mitsubishi heavy industries thermal systems,LTD FDT50VH Model(s) : Item Symbol Value Unit Item Symbol Value Unit Cooling capacity (sensible) Total electric power input 0.040...
  • Page 144: Duct Connected-High Static Pressure Type (Fdu)

    (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 145 (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 146 Total electric power input 0.250 rated,c elec Sound power level Cooling capacity (latent) 65.0 rated,c (per speed setting,if applicable) Heating capacity rated,h Contact details Mitsubishi heavy industries thermal systems,LTD FDU100VH Model(s) : Item Symbol Value Unit Item Symbol Value Unit Cooling capacity (sensible) Total electric power input 0.350...
  • Page 147: Duct Connected-Low/Middle Static Pressure Type (Fdum)

    (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 148 (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 149 Total electric power input Pelec 0.100 Sound power level Cooling capacity (latent) Prated,c 60.0 (per speed setting,if applicable) Heating capacity Prated,h Contact details Mitsubishi heavy industries thermal systems,LTD Model(s) : FDUM50VH Item Symbol Value Unit Item Symbol Value Unit Cooling capacity (sensible)
  • Page 150: Ceiling Suspended Type (Fde)

    (100years) refrigerant Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 151 (100years) Contact details Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air-conditioners shall be 0,25. *** from 26 September 2018 Where information relates to multi-spilt air-conditioners,the test result and performance data be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
  • Page 152 Total electric power input 0.050 rated,c elec Sound power level Cooling capacity (latent) 60.0 rated,c (per speed setting,if applicable) Heating capacity rated,h Contact details Mitsubishi heavy industries thermal systems,LTD Model(s) : FDE50VH Item Symbol Value Unit Item Symbol Value Unit Cooling capacity (sensible) Total electric power input 0.050...
  • Page 153 Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. © Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.