Mitsubishi Heavy Industries FDT71VNPVF1 Data Book

Mitsubishi Heavy Industries FDT71VNPVF1 Data Book

Standard inverter packaged air conditioners split system air to air heat pump type
Table of Contents

Advertisement

DATA BOOK
DATA BOOK
STANDARD INVERTER PACKAGED
AIR-CONDITIONERS
(Split system, air to air heat pump type)
CEILING CASSETTE-4WAY TYPE
FDT71VNPVF1
FDT90VNPVF1
FDT90VNPVF2
DUCT CONNECTED-HIGH STATIC
PRESSURE TYPE
FDU71VNPVF1
FDU90VNPVF1
FDU90VNPVF2
FLOOR STANDING TYPE
FDF71VNPVD1
FDF90VNPVD1
FDF90VNPVD2
Service code
History of service code
Outdoor unit
FDC71VNP
1
L
FDC90VNP
1
L
Changes
1 → L: to comply with amended
safety standard for LVD
Manual No.'13•PAC-DB-194
updated June 30, 2017
CEILING SUSPENDED TYPE
FDEN71VNPVF1
FDEN90VNPVF1
DUCT CONNECTED-LOW/MIDDLE
STATIC PRESSURE TYPE
FDUM71VNPVF1
FDUM90VNPVF1
FDUM90VNPVF2
WALL MOUNTED TYPE
SRK71VNPZM

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Heavy Industries FDT71VNPVF1

  • Page 1 June 30, 2017 DATA BOOK DATA BOOK STANDARD INVERTER PACKAGED AIR-CONDITIONERS (Split system, air to air heat pump type) CEILING CASSETTE-4WAY TYPE CEILING SUSPENDED TYPE FDEN71VNPVF1 FDT71VNPVF1 FDEN90VNPVF1 FDT90VNPVF1 FDT90VNPVF2 DUCT CONNECTED-LOW/MIDDLE DUCT CONNECTED-HIGH STATIC STATIC PRESSURE TYPE PRESSURE TYPE FDUM71VNPVF1...
  • Page 2: Table Of Contents

    '13 • PAC-DB-194 CONTENTS 1. GENERAL INFORMATION ................2. SPECIFICATIONS ..................11 (1) Ceiling cassette-4way type (FDT) ............11 (2) Ceiling suspended type (FDEN) ............13 (3) Duct connected-High static pressure type (FDU) ......... 15 (4) Duct connected-Low / Middle static pressure type (FDUM) ....
  • Page 3 '13 • PAC-DB-194 (5) Floor standing type (FDF) ..............95 (6) Wall mounted type (SRK) ..............99 (7) Effective range of cool/hot wind (Reference) ........103 11.2 Electric wiring work installation ............104 (1) FDT, FDEN, FDUM series ..............104 (2) FDU series ..................
  • Page 4: General Information

    '13 • PAC-DB-194 1. GENERAL INFORMATION (1) New line-up 1) New Standard Inverter Outdoor unit FDC71VNP (3HP) ● FDC90VNP (3.5HP) New PAC series line up (40-140 class) 2) Add new indoor unit connection SRK71ZM- S can connect with FDC71VNP. Connectable indoor unit FDEN FDUM SRK-ZM...
  • Page 5 '13 • PAC-DB-194 (2) Specification comparison (2)-1 3HP Specification HYPER FDC71VNX SRC71ZM-S FDC71VNP FDT71VF1 SRK71ZM-S FDT71VF1 50Hz 220-240V 50Hz 220-240V Power supply 50Hz 220-240V 60Hz 220V 60Hz 220V Nominal Capacity Range 3.2 - 8.0 2.15 - 8.0 1.4 - 7.1 3.48 3.29 2.84...
  • Page 6 '13 • PAC-DB-194 (3) Difference from other series (3)-1 Nominal / Maximum capacity ● Ratio of cooling/heating ● Nominal capacity Maximum capacity ● Minimum capacity Lower than current model 1) 3HP 2) 3.5HP Cooling/Heating /Max Same Same Hyper Hyper/Micro (4HP) (3.5HP) (3)-2 Efficiency Nominal efficiency becomes lower,...
  • Page 7 '13 • PAC-DB-194 (3)-3 Unit size & weight Become smaller and lighter. 1) 3HP 2) 3.5HP 33% down 0.25 52% down 52% down FDC100VNX 0.15 FDC71VNX SRC71ZK-S FDC71VNP 0.05 FDC71VNX Unit size (m2) FDC100VN 25% down 45% down 45% down FDC71VNX SRC71ZK-S FDC71VNP...
  • Page 8 '13 • PAC-DB-194 Limited piping length Smaller piping diameter Liquid Reducer(attached in O/U) 1) 3HP D6.35 D9.52 D12.7 D15.88 D6.35 (Liquid side is not necessary in case of SRK) D12.7 2) 3.5HP D6.35 D9.52 D6.35 Pipe diameter adjustment is necessary near indoor unit D15.88 (3)-5 Piping system 1) 3HP...
  • Page 9 '13 • PAC-DB-194 2) 3.5HP Hyper Crank case heater (4) Other features (4)-1 Combination <Plural control> FDC71VNP Outdoor units do not have plural FDT40VF1 control. Plural combination is prohibited. Single only...
  • Page 10 '13 • PAC-DB-194 (4)-2 Cooling capacity characteristic When ambient temperature is higher… Cooling capacity become smaller to 85%. Cooling Maximum capacity of other series FDC71VNP FDC90VNP Ambient temperature [ deg.C ] (4)-3 Sound level Sound pressure level becomes higher. Silent mode is prepared. (note: capacity down to around 90%) 1) 3HP 2) 3.5HP FDC100VNX...
  • Page 11 '13 • PAC-DB-194 (4)-5 Maintenance Cable PCZ504A065A 8pin CNROM (1)Mente PC is possible for maintenance. (white) Relay cable is necessary. 4pin New RAM file is also needed. RAMDATA_eR25V.xls FD CONVERTER PCA006A075B (2)Inverter checker is possible for maintenance. Short-connector is necessary. (Short between Pin No.2 and No.3 of CNROM) CNROM...
  • Page 12: Specifications

    '13 • PAC-DB-194 2. SPECIFICATIONS (1) Ceiling cassette-4way type (FDT) Model FDT71VNPVF1 Model FDT71VNPVF1 Item Indoor unit FDT71VF1 Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 7.1 [ 1.4(Min.)~ 7.1(Max.)] Nominal heating capacity (range) 7.1 [ 1.0(Min.)~ 7.1(Max.)]...
  • Page 13 '13 • PAC-DB-194 Model FDT90VNPVF1 Model FDT90VNPVF1 Item Indoor unit FDT100VF1 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 9.0 [ 1.9(Min.)~ 9.0(Max.)] Nominal heating capacity (range) 9.0 [ 1.5(Min.)~ 9.0(Max.)] Power Cooling 2.67 consumption...
  • Page 14 '13 • PAC-DB-194 Model FDT90VNPVF2 Model FDT90VNPVF2 Item Indoor unit FDT100VF2 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz Nominal cooling capacity (range) 9.0 [ 1.9(Min.)~ 9.0(Max.)] Nominal heating capacity (range) 9.0 [ 1.5(Min.)~ 9.0(Max.)] Power Cooling 2.67 consumption...
  • Page 15: Ceiling Suspended Type (Fden)

    '13 • PAC-DB-194 (2) Ceiling suspended type (FDEN) Model FDEN71VNPVF1 Model FDEN71VNPVF1 Item Indoor unit FDEN71VF1 Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 7.1 [ 1.4(Min.) ~ 7.1(Max.)] Nominal cooling capacity (range) 7.1 [ 1.0(Min.) ~ 7.1(Max.)] Nominal heating capacity (range) Power Cooling...
  • Page 16 '13 • PAC-DB-194 Model FDEN90VNPVF1 Model FDEN90VNPVF1 Item Indoor unit FDEN100VF1 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.75...
  • Page 17: Duct Connected-High Static Pressure Type (Fdu)

    '13 • PAC-DB-194 (3) Duct connected-High static pressure type (FDU) Model FDU71VNPVF1 Model FDU71VNPVF1 Item Indoor unit FDU71VF1 Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 7.1 [ 1.4(Min.) ~ 7.1(Max.)] Nominal cooling capacity (range) 7.1 [ 1.0(Min.) ~ 7.1(Max.)] Nominal heating capacity (range) Power Cooling...
  • Page 18 '13 • PAC-DB-194 Model FDU90VNPVF1 Model FDU90VNPVF1 Item Indoor unit FDU100VF1 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.65...
  • Page 19 '13 • PAC-DB-194 Model FDU90VNPVF2 Model FDU90VNPVF2 Item Indoor unit FDU100VF2 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.65...
  • Page 20: Duct Connected-Low / Middle Static Pressure Type (Fdum)

    '13 • PAC-DB-194 (4) Duct connected-Low / Middle static pressure type (FDUM) Model FDUM71VNPVF1 Model FDUM71VNPVF1 Item Indoor unit FDUM71VF1 Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 7.1 [ 1.4(Min.) ~ 7.1(Max.)] Nominal cooling capacity (range) 7.1 [ 1.0(Min.) ~...
  • Page 21 '13 • PAC-DB-194 Model FDUM90VNPVF1 Model FDUM90VNPVF1 Item Indoor unit FDUM100VF1 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.65...
  • Page 22 '13 • PAC-DB-194 Model FDUM90VNPVF2 Model FDUM90VNPVF2 Item Indoor unit FDUM100VF2 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.65...
  • Page 23 '13 • PAC-DB-194 (5) Floor standing type (FDF) Model FDF71VNPVD1 Model FDF71VNPVD1 Item Indoor unit FDF71VD1 Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 7.1 [ 1.4(Min.) ~ 7.1(Max.)] Nominal cooling capacity (range) 7.1 [ 1.0(Min.) ~ 7.1(Max.)] Nominal heating capacity (range) Power Cooling...
  • Page 24 '13 • PAC-DB-194 Model FDF90VNPVD1 Model FDF90VNPVD1 Item Indoor unit FDF100VD1 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.79...
  • Page 25 '13 • PAC-DB-194 Model FDF90VNPVD2 Model FDF90VNPVD2 Item Indoor unit FDF100VD2 Outdoor unit FDC90VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 9.0 [ 1.9(Min.) ~ 9.0(Max.)] Nominal cooling capacity (range) 9.0 [ 1.5(Min.) ~ 9.0(Max.)] Nominal heating capacity (range) Power Cooling 2.79...
  • Page 26 '13 • PAC-DB-194 (6) Wall mounted type (SRK) Model SRK71VNPZM Model SRK71VNPZM Item Indoor unit SRK71ZM-S Outdoor unit FDC71VNP Power source Single phase 220-240V 50Hz / 220V 60Hz 7.1 [ 1.4(Min.) ~ 7.1(Max.)] Nominal cooling capacity (range) 7.1 [ 1.0(Min.) ~ 7.1(Max.)] Nominal heating capacity (range) Power Cooling...
  • Page 27 Decorative panel 860~910 □950 (Ceiling hole size) Symbol Content □630 (Suspension bolts pitch) Gas piping φ 15.88(5/8")(Flare) Liquid piping φ 9.52(3/8")(Flare) Drain piping VP25( I.D.25, O.D.32) Hole for wiring Suspension bolts (M10 or M8) Control Outside air opening (Knock out) for ducting Air outlet opening (Knock out)
  • Page 28 Decorative panel 860~910 □950 (Ceiling hole size) Symbol Content □630 (Suspension bolts pitch) Gas piping φ15.88(5/8")(Flare) Liquid piping φ9.52(3/8")(Flare) Drain piping VP25(I.D.25,O.D.32) Hole for wiring Suspension bolts (M10 or M8) Control Outside air opening (Knock out) for ducting Air outlet opening (Knock out) for ducting Space for installation and service...
  • Page 29 Note(1)The model name label is attached on the fan casing inside the air return grille. (Suspension bolts pitch) Note The slope of drain piping inside the 1272 (Suspension bolts pitch) unit must take decline of 10mm. 1240 1320 Air supply Drain hose piece (Accesory, 0.3m) (Installed on site)
  • Page 30 Note(1)The model name label is attached on the fan casing inside the air return grille. (Suspension bolts pitch) 1572 (Suspension bolts pitch) Note The slope of drain piping inside the unit must take decline of 10mm. 1540 1620 Air supply Drain hose piece (Accesory, 0.3m) Receiving part...
  • Page 31 '13 • PAC-DB-194 (c) Duct connected-High static pressure type (FDU) Model FDU71VF1 Symbol Content Gas piping φ15.88(5/8")(Flare) Liquid piping φ9.52(3/8")(Flare) VP25(I.D.25,O.D.32) Drain piping (Duct dimension) Drain piping VP20(I.D.20,O.D.26) (Gravity drainage) Hole for wiring Suspension bolts (M10) Outside air opening (Knock out) for ducting Air outlet opening (Knock out)...
  • Page 32 '13 • PAC-DB-194 Model FDU100VF1, 100VF2 Symbol Content Gas piping 1280 (Duct dimension) φ15.88(5/8")(Flare) Liquid piping φ9.52(3/8")(Flare) VP25(I.D.25,O.D.32) Drain piping Drain piping Drain hose piece VP20(I.D.20,O.D.26) (Gravity drainage) (Accessory) Hole for wiring (Installed on site) Suspension bolts (M10) Outside air opening (Knock out)...
  • Page 33 '13 • PAC-DB-194 (d) Duct connected-Low / Middle static pressure type (FDUM) Model FDUM71VF1 Symbol Content Gas piping φ15.88(5/8")(Flare) (Duct dimension) Liquid piping φ9.52(3/8")(Flare) 4×200=800 Drain piping VP25(I.D.25,O.D.32) Drain piping VP20(I.D.20,O.D.26) (Gravity drainage) Drain hose piece Hole for wiring (Accessory) Suspension bolts (M10) (Installed on site)
  • Page 34 '13 • PAC-DB-194 Model FDUM100VF1, 100VF2 Symbol Content Gas piping φ15.88(5/8")(Flare) Liquid piping φ9.52(3/8")(Flare) Drain piping VP25(I.D.25,O.D.32) 1280 (Duct dimension) Drain piping 4×280=1120 VP20(I.D.20,O.D.26) (Gravity drainage) Hole for wiring Suspension bolts (M10) Drain hose piece Outside air opening (Accessory) (φ150)(Knock out) for ducting (Installed on site) Air outlet opening...
  • Page 35 H can be installed left 25~50 (Range that can be adjusted) Air supply Remote control Air return grille 622.5 264(Liquid) 262(Gas) Terminal block (Power source) 238.5(Drain) Note(1) The model name label is attached on the (Center of left lower side panel inside the air return grille. terminal block) Space for installation and service Symbol...
  • Page 36 1090 Symbol Content 43.5 Gas piping φ15.88(5/8")(Flare) Liquid piping φ6.35(1/4")(Flare) Hole on wall for right rear piping (φ65) Hole on wall for left rear piping (φ65) Drain hose VP16 Outlet for wiring Outlet for piping(on both side) 1098 Wireless remote control Outlet for down piping (Refer to the above view)...
  • Page 37 Notes Symbol Content (1) It must not be surrounded by walls on the four sides. Service valve connection(gas side) (2) The unit must be fixed with anchor bolts. An anchor bolt must not φ12.7(1/2")(Flare) protrude more than 15mm. Service valve connection(liquid side) φ6.35(1/4")(Flare) (3)...
  • Page 38 Symbol Content Service valve connection(gas side) φ15.88(5/8")(Flare) Service valve connection(liquid side) φ6.35(1/4")(Flare) Pipe/cable draw-out hole Note Drain discharge hole φ20 x 3 places (1)It must not be surrounded by walls on four sides. Anchor bolt hole M10 x 4 places (2)The unit must be fixed with anchor bolts.
  • Page 39 '13 • PAC-DB-194 (3) Remote control (a) Wired remote control (Option parts) Model RC-E5 Interface kit (SC-BIKN-E) is required to use the wired remote control. (SRK series only) Wiring outlet Cut off the upper thin part of remote control lower case with a nipper or knife, and grind burrs with a file etc.
  • Page 40 '13 • PAC-DB-194 Model : RC-EX1A (Except SRK series) Installation space Exterior appearance Pearl White (Munsell color) (N8.5) near equivalent R/C cable:0.3mm × 2-core RoHS Adapted to directive PJZ000Z297...
  • Page 41 '13 • PAC-DB-194 (b) Wireless remote control RCN-E1R (Option parts) (Except SRK series) Unit: mm SRK series only (Standard accessory) Unit: mm...
  • Page 42 (Remote operation input: volt-free contact) CNB~Z Connector Remote control Drain motor Control PCB C F1~3 Fuse CNTA Fan motor t° t° ThI-R1 Float switch LED・2 LED・3 ※1 Reactor t° ThI-R2 YE/GN LED・2 CNWR2 CNW0 Power PCB Indication lamp Connecting line between (Green-Normal operation) indoor unit and outdoor unit F1(3.15A)
  • Page 43 CFI1,2 Capacitor for FMI ThI-R1 ThI-R2 ThI-R3 ThI-A Connector t° t° t° t° CNB~Z Fuse 220ー240V FMI1,2 Fan motor(with thermistor) LED・2 Indication lamp(Green-Normal operation) Connecting line between Prepare on site 1 2 3 4 5 CNW1 CNW2 indoor unit and outdoor unit CNJ WH LED・3 Indication lamp(Red-Inspection)
  • Page 44 CNB~Z Connector Drain motor F1,4 Fuse Fan motor Control PCB Float switch t° Reactor Remote control LED・2 Indication lamp(Green-Normal operation) t° LED・3 Indication lamp(Red-Inspection) t° Remote control communication address t° Plural units Master/Slave setting LED・2 LED・3 Model capacity setting Power PCB SW7-1 Operation check, Drain motor test run t°...
  • Page 45 CNB~Z Connector Drain motor F1,3,4 Fuse Fan motor(with thermostat) Float switch Remote control Control PCB Reactor t° LED・2 Indication lamp(Green-Normal operation) t° LED・3 Indication lamp(Red-Inspection) t° LED・2 LED・3 Remote control communication address Power PCB CNW0 t° Connecting line between Plural units Master/Slave setting YE/GN F1(6.3A)...
  • Page 46 CNB~Z Connector Drain motor F1,4 Fuse FMI2 Fan motor(with thermostat) Float switch Remote control Control PCB LED・2 Indication lamp(Green-Normal operation) ThI-R1 t° LED・3 Indication lamp(Red-Inspection) t° Remote control communication address ThI-R2 LED・2 LED・3 t° Plural units Master/Slave setting CNW0 Power PCB ThI-R3 t°...
  • Page 47 CNB~Z Connector Drain motor F1,3,4 Fuse FMI1,2 Fan motor(with thermostat) Float switch Remote control Control PCB Reactor ThI-R1 t° LED・2 Indication lamp(Green-Normal operation) t° LED・3 Indication lamp(Red-Inspection) ThI-R2 LED・2 LED・3 t° Remote control communication address CNW0 Power PCB ThI-R2 t° Plural units Master/Slave setting Connecting line between YE/GN...
  • Page 48 Color Marks Mark Color Mark Color Mark Color Connector Plural units Master/Slave setting CNB~Z Black GR Gray White F200~203 Fuse Model capacity setting Orange Fan motor Operation check,Drain motor test run Blue Yellow SW7- 1 Reactor Terminal block(Power source) BR Brown YE/GN Yellow/Green (□...
  • Page 49 Item Description CNE-CNX2 Connector Fan motor DISPLAY Flap motor WIRELESS RECEIVER CNX1 Louver motor BACK-UP SW Room temp. sensor PRINTED CIRCUIT Heat exch. sensor BOARD Humidity sensor Diode stack CNX2 Fuse Terminal block Varistor INTERFACE KIT SC-BIKN-E Color Marks Mark Color Y/G Black...
  • Page 50 POWER SOURCE ~ 220/230/240V 50Hz ~ 220V 60Hz PWB ASSY (MAIN) PWB ASSY (SUB) TERMINAL POWER BLOCK 1 TRANSISTOR FUSE (BK) (BK) (RD) 250V 20A (BK) ~ + 250V 20A ACTIVE 250V 20A (WH) (WH) FILTER (WH) (WH) 3~ UNIT ~...
  • Page 51 POWER SOURCE ~220/230/240V 50Hz PWB ASSY (MAIN) PWB ASSY (SUB) TERMINAL POWER BLOCK TRANSISTOR FUSE (BK) (BK) (RD) 250V 20A (BK) ACTIVE 250V 20A ~ + 250V 20A (WH) (WH) FILTER (WH) (WH) 3~ UNIT ~ - (BR) (BK) (YG) (WH)...
  • Page 52: Indoor Units

    '13 • PAC-DB-194 5. NOISE LEVEL Notes (1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27℃WB. Outdoor unit 35℃DB. (2) The data in the chart are measured in an anechoic room. (3) The noise levels measured in the field are usually higher than the data because of reflection. (1) Indoor units Ceiling cassette-4way type (FDT) Measured based on JIS B 8616...
  • Page 53 '13 • PAC-DB-194 (d) Duct connected-Low/Middle static pressure type (FDUM) Measured based on JIS B 8616 Model FDUM71VF1 Model FDUM100VF1, 100VF2 ●Mike position Noise level 38 dB (A) at P-HIGH Noise level 44 dB (A) at P-HIGH 33 dB (A) at HIGH 38 dB (A) at HIGH 29 dB (A) at MEDIUM 36 dB (A) at MEDIUM...
  • Page 54: Outdoor Units

    '13 • PAC-DB-194 (2) Outdoor units Measured based on ISO-T1, JIS B 8616 Measured based on ISO-T1, JIS B 8616 Mike position: at highest noise level in position as mentioned below (sound pressure level) Mike position: at highest noise level in position as mentioned below (sound pressure level) Distance from front side 1m Distance from front side 1m Height...
  • Page 55: Characteristics Of Fan

    '13 • PAC-DB-194 6. CHARACTERISTICS OF FAN (1) Duct connected-Higt static pressure type (FDU) ・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (SW8-4 OFF : 150Pa, SW8-4 ON : 200Pa), rated E.S.P., and minimum E.S.P. (SW8-4 OFF : 80Pa, SW8-4 ON : 10Pa) ・Characteristic FAN (2) shows air flow vs.
  • Page 56 '13 • PAC-DB-194 Model FDU100VF1, 100VF2 ■SW8-4 : OFF (Range of use limitation : Setting 80Pa-150Pa) Characteristic FAN (1) Characteristic FAN (2) Range of approvable air flow In case actual E.S.P. correspond setting of E.S.P. Setting 150Pa P-Hi P-Hi Setting 120Pa P-Hi Setting 80Pa Air flow (m...
  • Page 57: Duct Connected-Low / Middle Static Pressure Type (Fdum)

    '13 • PAC-DB-194 (2) Duct connected-Low / Middle static pressure type (FDUM) ・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (100Pa) , rated E.S.P., and minimum E.S.P. (10Pa) ・Characteristic FAN (2) shows air flow vs. E.S.P curve when set fan tap is set P-Hi with each setting of E.S.P by remote control. ・External Static Pressure (E.S.P.) can be set by wired remote control.
  • Page 58: Temperature And Velocity Distribution

    '13 • PAC-DB-194 7. TEMPERATURE AND VELOCITY DISTRIBUTION Indoor temperature Cooling 27° CDB / 19° CWB Heating 20° CDB Note: These figures represent the typical main range of temperature and velocity distribution at the center of air outlet within the published conditions. In the actual installation, they may differ from the typical figures under the influence of air temperature conditions, ceiling height, operation conditions and obstacles.
  • Page 59 '13 • PAC-DB-194 Model FDT100VF1, 100VF2 Cooling Air flow : P-Hi ° 0.9 1.2 Heating Air flow : P-Hi ° ISD09406...
  • Page 60: Ceiling Suspended Type (Fden)

    '13 • PAC-DB-194 (2) Ceiling suspended type (FDEN) Model FDEN71VF1 Cooling Air flow : P-Hi ° Heating Air flow : P-Hi ° ISD09408...
  • Page 61 '13 • PAC-DB-194 Model FDEN100VF1 Cooling Air flow : P-Hi ° Heating Air flow : P-Hi ° ISD09408...
  • Page 62: Floor Standing Type (Fdf)

    '13 • PAC-DB-194 (3) Floor standing type (FDF) Models FDF71VD1, 100VD1, 100VD2 (a) Cooling Air flow:Hi (Louver position:Horizontal) Temperature distribution Less than 14℃ 16℃ 18℃ 24℃ 20℃ 22℃ 24℃ 26℃ (b) Heating Air flow:Hi (Louver position:Horizontal) Temperature distribution ℃ More than 42℃...
  • Page 63: Piping System

    '13 • PAC-DB-194 8. PIPING SYSTEM (1) FDT, FDEN, FDU, FDUM, FDF series Model 71 Indoor unit Outdoor unit Heating cycle Cooling cycle Service valve Outdoor air temp. sensor Gas pipe (Flare connecting) (φ12.7) Muffler (TH2) Discharge pipe Thermistor temp. sensor (Heat Reducer (TH3)
  • Page 64 '13 • PAC-DB-194 (2) SRK series Model 71 Indoor unit Outdoor unit Heating cycle Cooling cycle Service valve Outdoor air temp. sensor Gas pipe (Flare connecting) (φ12.7) Muffler (TH2) Discharge pipe temp. sensor Humidity Reducer (TH3) sensor Check joint (Th3) (Accessory) Heat exchanger...
  • Page 65: Range Of Usage & Limitations

    '13 • PAC-DB-194 9. RANGE OF USAGE & LIMITATIONS See next page. Operating temperature range When used below -5˚C, install a snow hood (prepared on site). Considering to get sufficient heating capacity, the area where the averaged lowest ambient Recommendable area to install air temperature in day time during winter is above 0˚C, and it has no accumulation of snow.
  • Page 66 '13 • PAC-DB-194 Operating temperature range ■ Cooling 46℃DB Usage range in cooling -15℃DB Indoor air temperature (℃WB) ■ Heating Usage range in heating Outdoor air temperature (℃WB) Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in places where natural wind can increase or decrease its design airflow rate.
  • Page 67 '13 • PAC-DB-194 Limitation on unit and piping installation Model for Marks appearing Descriptions Dimensional limitations outdoor unit in the drawing ≦ 30m (2) One-way pipe length FDC71VNP When the outdoor unit is positioned higher ≦ 20m FDC90VNP Elevation difference between indoor and outdoor unit When the outdoor unit is positioned lower ≦...
  • Page 68: Selection Chart

    Otherwise protection control by low pressure will be activated much more frequently and it will cause insufficient capacity or breakdown of the compressor in worst case. 10.1 Capacity tables (1) Ceiling cassette-4way type (FDT) FDT71VNPVF1 Model Indoor unit FDT71VF1 Outdoor unit...
  • Page 69 '13 • PAC-DB-194 (2) Ceiling suspended type (FDEN) FDEN71VNPVF1 Model Indoor unit FDEN71VF1 Outdoor unit FDC71VNP Cooling Mode Heating Mode : HC (kW) (kW) Indoor air temperature Indoor air temperature Outdoor Outdoor air temp. 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB...
  • Page 70 '13 • PAC-DB-194 (3) Duct connected-High static pressure type (FDU) FDU71VNPVF1 Model Indoor unit FDU71VF1 Outdoor unit FDC71VNP Cooling Mode Heating Mode : HC (kW) (kW) Indoor air temperature Outdoor Indoor air temperature Outdoor air temp. 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB...
  • Page 71 '13 • PAC-DB-194 (4) Duct connected-Low/Middle static pressure type (FDUM) FDUM71VNPVF1 Model Indoor unit FDUM71VF1 Outdoor unit FDC71VNP Cooling Mode Heating Mode : HC (kW) (kW) Indoor air temperature Outdoor Indoor air temperature Outdoor air temp. 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB...
  • Page 72 '13 • PAC-DB-194 (5) Floor standing type (FDF) FDF71VNPVD1 Model Indoor unit FDF71VD1 Outdoor unit FDC71VNP Cooling Mode Heating Mode : HC (kW) (kW) Indoor air temperature Outdoor Indoor air temperature Outdoor air temp. 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB...
  • Page 73 '13 • PAC-DB-194 (6) Wall mounted type (SRK) SRK71VNPZM Model Indoor unit SRK71ZM-S Outdoor unit FDC71VNP Cooling Mode Heating Mode : HC (kW) (kW) Indoor air temperature Indoor air temperature Outdoor Outdoor air temp. 18℃DB 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB...
  • Page 74 '13 • PAC-DB-194 [References data]   Capacity variation against outdoor and indoor temperature at the maximum compressor speed capacity compensation coefficient shows the ratio to nominal capacity. (Ⅰ) Model FDC71VNP ① Cooling Indoor air temperture 24℃WB Indoor air temperture 19℃WB Indoor air temperture 15℃WB Indoor air...
  • Page 75 '13 • PAC-DB-194 (Ⅱ) Model FDC90VNP ① Cooling Indoor air temperture 24℃WB Indoor air temperture 19℃WB Indoor air Indoor air temperture 15℃WB temperture 17℃WB Indoor air temperture 12℃WB Ambient air temperature (℃DB) ② Heating Ambient air Ambient air temperture 7℃WB temperture 18℃WB Ambient air Ambient air...
  • Page 76: Correction Of Cooling And Heating Capacity In Relation To Air Flow Rate Control (Fan Speed)

    '13 • PAC-DB-194 10.2 Correction of cooling and heating capacity in relation to air flow rate control (fan speed) Fan speed P-Hi or Hi Cooling 1.00 0.95 0.93 0.90 Coefficient Heating 1.00 0.97 0.96 0.94 Note (1) SRK series only. 10.3 Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor...
  • Page 77: Application Data

    '13 • PAC-DB-194 11. APPLICATION DATA PJF012D016C INSTALLATION MANUAL FOR CEILING CASSETTE 11.1 Installation of indoor unit PJF012D016C -4WAY- TYPE (FDT) (1) Ceiling cassette-4way type (FDT) ①B This manual is for the installation of an indoor unit. This manual is for the installation of an indoor unit. ●Inst For electrical wiring work (Indoor), refer to page 104.
  • Page 78 '13 • PAC-DB-194 ①Before installation ③Preparation before installation ●Install correctly according to the installation manual. ●If suspension bolt becomes longer, do reinforcement of earthquake resistant. ●Confirm the following points:  ○For grid ceiling  ○Unit type/Power supply specification ○Pipes/Wires/Small parts ○Accessory items   When suspension bolt length is over 500mm, or the gap between the ceiling and roof is over 700mm, apply earthquake resistant brace to the bolt.
  • Page 79 '13 • PAC-DB-194 ⑤Refrigerant pipe (continued) ④Installation of indoor unit (continued) ⑥D 6. Make sure to install the indoor unit horizontally. Confirm the Caution: Strap (Accessory) Pipe cover (Accessory) levelness of the indoor unit with a level gauge or transpar- Refrigerating machine oil should not be applied to the threads of union or external surface of flare.
  • Page 80 '13 • PAC-DB-194 ⑦ ⑦ ⑥ ⑥ ● ● ● ● ● ● ● ● ⑧ ⑧ ● ● ● ● ● ● ● ● ① ① ② ② ⑨ ⑨ ● ● ② ② ① ① ○ ○ ⑩ ⑩...
  • Page 81 '13 • PAC-DB-194 PJF012D003C...
  • Page 82 '13 • PAC-DB-194 ⑧ Attaching a corner panel 1. To avoid unexpected falling of the corner panel, put the strap onto the corner panel’s pin with turning the strap up. 2. Then hang the strap of a corner panel onto the decorative panel’s pin. 3.
  • Page 83 '13 • PAC-DB-194 OUTDOOR AIR (OA) INTAKE FOR FDT If it is required to intake OA through FDT unit, make sure to check following points carefully in order to conform to the requirement of customer. If the OA intake volume through FDT unit is not satisfied with the required ventilation air volume, consider to install an indepemdent ventilation system.
  • Page 84: Ceiling Suspended Type (Fden)

    '13 • PAC-DB-194 PFA012D621B (2) Ceiling suspended type (FDEN) This manual is for the installation of an indoor unit. CAUTION For electrical wiring work (Indoor), refer to page 104. For remote control installation, refer to page 116. For wireless kit installation, refer to page 146. For electrical wiring ●...
  • Page 85 '12 • PAC-T-174 '13 • PAC-DB-194 ① Before installation ③ Preparation before installation (continued) Install correctly according to the installation manual. Pitch of suspension bolts and pipe position Location of pipe outlets Top cover Pitch of suspension bolts Drain line (left) Drain line (rear left)
  • Page 86 '13 • PAC-DB-194 ⑤ Installation of indoor unit ⑥ Refrigerant pipe (continued) Work procedure The pipe can be connected from three different directions. (back, reight, top) Paper pattern 1. Select the suspension bolt locations and the pipe hole location. When the pipe is routed through the back. (1) Use enclosed paper pattern as a reference, and If the bracket is removed, piping work will become easy.
  • Page 87 '13 • PAC-DB-194 ⑧ Wiring-out position and wiring connection ⑪ How to set the airflow direction Electrical installation work must be performed according to the installation It is possible to change the movable range of the louver on the air outlet from manual by an electrical installation service provider quali ed by a power the wired remote control.
  • Page 88: Duct Connected-High Static Pressure Type (Fdu)

    '13 • PAC-DB-194 PJG012D004 DUCT CONNECTED HIGH STATIC PRESSURE AIR (3) Duct connected-High static pressure type (FDU) PJG012D004 CONDITIONING UNIT INSTALLATION MANUAL (a) Indoor unit ○This model blow type a This manual is for the installation of an indoor unit. CAUTION For electrical wiring work (Indoor), refer to page 108.
  • Page 89 '13 • PAC-DB-194 2D004 ○This model is middle static ducted type air conditioning unit. Therefore, do not use this model for direct ③Preparation before installation blow type air conditioning unit. ●If suspension bolt becomes longer, do reinforcement of earthquake resistant. ①Before installation  ○For grid ceiling   When the suspension bolt length is over 500mm, or the gap between the ceiling and roof is...
  • Page 90 '13 • PAC-DB-194 ⑤ ⑦ ⑤ ① ① ● ● ○ ● ② ● ● ● ● ● ○ ● ● ● ② ● ○ ③ ● ● ● ○ ● ⑥ ●    ・  ・ ● ● ④   ●...
  • Page 91 '13 • PAC-DB-194 ⑦ ⑦ ● ● ● ● ● ● ● ● ● ● ※ ● ● ● ● ● ● ● ※ PJG012D004...
  • Page 92 '13 • PAC-DB-194 ⑧Wiring-out position and wiring connection ⑩Check list after installation ●Check the following items after all installation work completed. ● Electrical installation work must be performed according to the installation manual by an electrical installation service provider qualified by a power provider of the country, and be Check if Expected trouble Check...
  • Page 93 '13 • PAC-DB-194 (b) Replacement procedure of the fan unit Notes(1) The unit is a heavy item. It must be supported securely and handled with care not to drop when it is necessary to replace. (2) For the maintenance space, refer to page 84. (i) Model FDU71VF1 1) Remove the control box and the side panel, and remove 2) Take out the fan unit located at the near side in the arrow...
  • Page 94: Duct Connected-Low / Middle Static Pressure Type (Fdum)

    '13 • PAC-DB-194 (4) Duct connected-Low / Middle static pressure type (FDUM) (a) Indoor unit PJG012D008B  DUCT CONNECTED MIDDLE STATIC PRESSURE AIR CONDITIONING UNIT INSTALLATION MANUAL ○This mod blow type This manual is for the installation of an indoor unit. CAUTION For electrical wiring work (Indoor), refer to page 104.
  • Page 95 '13 • PAC-DB-194 008B  ○This model is middle static ducted type air conditioning unit. Therefore, do not use this model for direct ③Preparation before installation blow type air conditioning unit. ●If suspension bolt becomes longer, do reinforcement of earthquake resistant. ①Before installation  ○For grid ceiling   When the suspension bolt length is over 500mm, or the gap between the ceiling and roof is...
  • Page 96 '13 • PAC-DB-194 ⑤ ⑦ ⑤ ① ① ● ● ○ ● ② ● ● ● ● ○ ● ● ● ② ● ○ ③ ● ● ● ● ○ ● ⑥ ● ● ●    ・  ・ ●   ●...
  • Page 97 '13 • PAC-DB-194 ⑦ ⑦ ● ● ● ● ● ● ● ● ● ● ※ ● ● ● ● ● ● ● ※ PJG012D008B...
  • Page 98 '13 • PAC-DB-194 ⑧Wiring-out position and wiring connection ⑨External static pressure setting (continued) ● Electrical installation work must be performed according to the installation manual by an Indoor unit fan will run automatically and recognize E.S.P. by itself. electrical installation service provider qualified by a power provider of the country, and be The operation for automatic E.S.P.
  • Page 99 '13 • PAC-DB-194 (b) Replacement procedure of the fan unit Notes(1) The unit is a heavy item. It must be supported securely and handled with care not to drop when it is necessary to replace. (2) For the maintenance space, refer to page 90. (i) Model FDUM71VF1 3) Remove the screws marked in the circles (2 places) from the 1) Remove the control box and the side panel, and remove the...
  • Page 100: Floor Standing Type (Fdf)

    '13 • PAC-DB-194 PGA012D404 PGA012D404 (5) Floor standing type (FDF) ①Be CAUTION This manual is for the installation of an indoor unit. For electrical wiring work (Indoor), refer to page 112. For remote control installation, refer to page 116. ● Perform earth wiring surely. For wireless kit installation, refer to page 150.
  • Page 101 '13 • PAC-DB-194 2D404 ①Before installation ③Carrying-in and installation of the unit (Continued) ATTENTION: Model and power supply specification • Be sure to fix the unit with L-fittings and the fall-prevention fitting. ○ Install the unit properly ・Since the unit is tall, secure the unit no sooner than setting it in place. according to this Tapping screw instruction manual.
  • Page 102 '13 • PAC-DB-194 ④Refrigerant piping ④Refrigerant piping (Continued) ⑤Drain p ◆ Pipe and wire extracting position WARNI Caution ●Use the new refrigerant pipe.  When re-using the existing pipe system for R22 or R407C, pay attention to the following items. Gas pipe  ・Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare Liquid pipe parts.
  • Page 103 '13 • PAC-DB-194 ⑤Drain pipe ⑥Wire extracting position and wire connecton WARNING Control box position and power cable connection ●Electric work must be made by qualified electricians according to the “Engineering standards concerning electric equipment”, “Extension wiring regulations” and the electric wiring work manual.
  • Page 104: Wall Mounted Type (Srk)

    (6) Wall mounted type (SRK) WALL TYPE AIR CONDITIONER RKW012A411 R410A REFRIGERANT USED WARNING INSTALLATION MANUAL FOR INDOOR UNIT • Do not vent R410A into the atmosphere : R410A is a fluorinated • Do not perform any change of protective device itself or its setup greenhouse gas, covered by the Kyoto Protocol with Groval condition.
  • Page 105 seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
  • Page 106: Connection Of Refrigerant Pipings

    RKW012A411 Fixing of indoor unit Since this air conditioner has been designed to collect dew drops on the rear Gutter surface to the drain pan, do not attach the power cord above the gutter. Latch (2 locations) • How to remove the indoor unit from the installation board Installation Steps Wall Pass the pipe through...
  • Page 107 ○Installing shown in right illustration and pull it toward you. ①  Remove the air filter. ○ To install, insert the panel arm into the slot on the ②  Cover the unit with the front panel. Approx. 80 front panel from the position shown in right Front panel To remove / To install ③ ...
  • Page 108: Effective Range Of Cool/Hot Wind (Reference)

    '13 • PAC-DB-194 (7) Effective range of cool/hot wind (Reference) (a) FDT series Guideline for ceiling height Model Fan Speed Setting FDT71VF1 FDT100VF1, 100VF2 3.0m 3.2m 3.8m 4.3m Notes (1) If the ceiling height is over 3m, please consider to add circulators. This table shows reference values in case of four outlet.
  • Page 109: Electric Wiring Work Installation

    '13 • PAC-DB-194 11.2 Electric wiring work installation PSB012D999 (1) FDT, FDEN, FDUM, series PSBO12D999 ELECTRIC WIRING WORK INSTRUCTION Electrical Wiring Connection ②Remot Electrical wiring work must be performed by an electrician qualified by a local power provider according to ●...
  • Page 110 '13 • PAC-DB-194 D999 ②Remote Control, Wiring and functions ③ Operation and confirmation from remote control al power ● DO NOT install it on the following places Operation from RC-EX1A Operation from RC-E5 ollowing ①Places exposed to direct sunlight 1 Check the number of units connected in the remote control system. ②Places near heat devices It checks sub units of twin, triple or W-twin connection.
  • Page 111 '13 • PAC-DB-194 ⑥ Operation and setting from remote control ⑥ O A: Refer to the instruction manual for RC-EX series. B: Refer to the installation manual for RC-EX series. C: Loading a utility software vie Internet 11. A ○: Nearly same function setting and operations are possible. △: Similar function setting and operations are possible.
  • Page 112 '13 • PAC-DB-194 ⑥ Operation and setting from remote control (continued) RC-EX Setting & display item Description RC-E5 series A  11. Administrator settings [Administrator password] ・ Enable/Disable setting of operation can be set. [On/Off] [Change set temp.] [Change operation mode] [Change air flow direction] 1 Enable/Disable setting [Individual flap control setting][Fan speed] [High power operation] [Energy-saving operation] [Timer settings] [Weekly timer setting] A ...
  • Page 113 '13 • PAC-DB-194 PSB012D994 PSBO12D994 ELECTRIC WIRING WORK INSTRUCTION (2) FDU series Electrical Wiring Connection ②Remote Electrical wiring work must be performed by an electrician qualified by a local power provider according to ● Use three-core cable as wiring between indoor and outdoor unit. As for detail, refer to "INSTAL- ●...
  • Page 114: Checking Operation Data

    '13 • PAC-DB-194 2D994 ②Remote Control, Wiring and functions ③Trial operation "INSTAL- ● DO NOT install it on the following places The method of trial cooling operation ①Places exposed to direct sunlight ②Places near heat devices Operate the remote control unit as follows. ucting of 1.
  • Page 115 '13 • PAC-DB-194 ④Function Setting by Remote Control ⑤Co The functional setting Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically ● defined as following table. The initial function setting for typical using is performed automatically for a remote control unit and an indoor unit by the door unit connected, when Function No.
  • Page 116 '13 • PAC-DB-194 ⑤Control mode switching ected indoor and outdoor unit, and is automatically The control content of indoor units can be switched in following way. ( is the default setting) ● Switch No. Control Content Model RUN" mode selectable indoor unit. Indoor unit address (0-Fh) unit without "Auto-RUN"...
  • Page 117: Fdf Series

    '13 • PAC-DB-194 PGA012D405 PGAO12D405 (3) FDF series Electrical Wiring Connection ②Wi Electrical wiring work must be performed by an electrician qualified by a local power provider according to ● Use three-core cable as wiring between indoor and outdoor unit. As for detail, refer to "INSTALLATION MANUAL" of ①...
  • Page 118 '13 • PAC-DB-194 12D405 ②Wiring for the remote control (Continued) ③Function Setting by Remote Control (Continued) MANUAL" of ① Open the remote control cover and remove the screw without fail. Press (SET) button. ③ The current setting of selected function is indicated. (For example) "STANDARD"...
  • Page 119 '13 • PAC-DB-194 ③Function Setting by Remote Control (Continued) ④Trial ope Checking [Flow of function setting] It is possible to finish above setting on the way, and unfinished change of setting is unavailable. Start : While indoor unit do not operate, press “ ”...
  • Page 120 '13 • PAC-DB-194 ④Trial operation (Continued) ⑦Troubleshooting The operation data is saved when the situation of abnormal operation happen, and the data Checking operation data can be confirmed by remote control. Operation data can be checked with remote Number Data Item control unit operation.
  • Page 121: Installation Of Wired Remote Control (Option)

    '13 • PAC-DB-194 11.3 Installation of wired remote control (option) Installation manual for wired remote controller PJA012D730 Connect the remote control (1) Model RC-E5 terminal block. Connect the terminal of rem Read together with indoor unit's installation manual. with the terminal of indoor u WARNING (X and Y are no polarity) Wiring route is as shown in...
  • Page 122 '13 • PAC-DB-194 emote controller Connect the remote control cord to the Sheath Sheath The range of temperature setting Upper Upper terminal block. When shipped, the range of set tempe Connect the terminal of remote control (X,Y) Upper case Upper case Board Board Heating : 16 ~ 30˚C (55 ~ 86˚F)
  • Page 123 '13 • PAC-DB-194 PJ A0 12 D73 0 Sheath Sheath The range of temperature setting Upper When shipped, the range of set temperature differs depending on the operation mode as below. pper case Upper case Board Heating : 16 ~ 30˚C (55 ~ 86˚F) Except heating (cooling, fan, dry, automatic) : 18 ~ 30˚C (62 ~ 86˚F) Upper limit and lower limit of set temperature can be changed with remote control.
  • Page 124 '13 • PAC-DB-194 The functional setting The initial function setting for typical using is performed automatically by the indoor unit connected, when remote control and indoor unit are connected. As long as they are used in a typical manner, there wiil be no need to change the initial settings. If you would like to change the initial setting marked “...
  • Page 125 '13 • PAC-DB-194 Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table. Item Function No. Default Model "Auto-RUN" mode selectable indoor unit. Remote control function02 Indoor unit without "Auto-RUN" mode Indoor unit with two or three step of air flow setting Remote control function06...
  • Page 126 '13 • PAC-DB-194 PJA0 12 D73 0 nd is automatically defined as following table. Operation message How to set function Function description: ectable indoor unit. Function No. Stop air-conditioner and press (SET) (MODE) setting description: uto-RUN" mode buttons at the same time for over three seconds, and the three step of air flow setting "FUNCTION SET "...
  • Page 127: Installation Manual

    '13 • PAC-DB-194 (2) Model RC-EX1A PJZ012D077 eco touch REMOTE CONTROL RC-EX1A INSTALLATION MANUAL...
  • Page 128 '13 • PAC-DB-194 1 . Safety Precautions This installation manual describes the installation methods and precautions related to the remote control. Use this manual together with the user’s manuals for the indoor unit, outdoor unit and other optional equipment. Please read this manual carefully before starting the installation work to install the unit properly.
  • Page 129 '13 • PAC-DB-194 When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress electric noises. It could cause malfunction or break-down due to hazardous effects on the inverter, private power generator, high frequency medical equipment, radio communication equipment, etc. The influences transmitted from the remote control to medical or communication equipment could disrupt medical activities, video broadcasting or cause noise interference.
  • Page 130 '13 • PAC-DB-194 2 . Accessories & Prepare on site R/C main unit, wood screw (ø3.5 x 16) 2 pcs Accessories User’s Manual, Installation Manual Parts procured at site When the cable length is longer than Item name Q’ty Remark 100 m, the max size for wires used Switch box in the R/C case is 0.5 mm...
  • Page 131 '13 • PAC-DB-194 Request Be sure not to install R/C at a place where temperatures around the installation surface of R/C may differ largely from actual room temperature. Difference between detected temperature and actual room temperature could cause troubles. The correction for detected temperature by the R/C cannot offset such temperature difference because it corrects the detected temperatures itself.
  • Page 132 '13 • PAC-DB-194 ④   W hen wires are passed through the bottom case, fix the bottom case at 2 places on the switch box. Upper side Upper side Switch box Switch box for 1 pc for 2 pcs Cut out the thin wall part at the screw mounting Bottom case...
  • Page 133 '13 • PAC-DB-194 If the hole is cut too large, moisture, dust or insects may enter. Seal gaps with putty or the like. ④     Fix the bottom R/C case on a flat surface with wood screws. ⑤   I n case of the upper center, p a s s t h e w i r i n g b e h i n d 120mm...
  • Page 134 '13 • PAC-DB-194 Note: Connection to personal computer It can be set from a personal computer via the USB port (mini-B). Connect after removing the cover for USB port of upper case. Replace the cover after use. If dust, insect, etc. enters, it could cause electric shocks or breakdown.
  • Page 135: Installation Of Outdoor Unit

    11.4 Installation of outdoor unit Model FDC71VNP page 72. ● ● ● 〇 〇 〇 〇 〇 〇 〇 〇 〇 〇 〇 〇 〇...
  • Page 136 ● ●    ●   ● ● (e.g. organic fertilizer). Locations with calcium chloride (e.g. snow melting agent).   ● ● ● ● ● ● ●...
  • Page 137 ● ● ● 〇 ● ● 〇 ● 〇 〇 〇 ● 〇 ● 〇 ● 〇 〇 〇 (mm) Ⅰ Ⅱ Ⅲ Ⅳ 〇 〇 〇 Do not install the unit in places which exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g. snow melting agent), exposed to ammonia substance (e.g.
  • Page 138 ●  ●    ●   ● ●   ● < > ● ●   ● [Except SRK]      ● ● [SRK]      ●   ●   ●   ● ●   ● A ー . ●   ● ....
  • Page 139 〜 〜   ●   ● ° 〜 〜 〜 〜 〜 〜 〜 〜 ○ ① ○ ℃ ○ ② ○ < > ○ 〜 ○ 〜 〜 ● ● ● ※ ● ● ● ● ℃ ●...
  • Page 140 ● ● ● ● ●     ●   ●   ●   ●   ●   ●   ●   ●   ●   ●   ● ● ● ● ● ○ ○ ○ ● ● ○ ●...
  • Page 141 ● ○ ● ◎: ○: △: ◎ ○ △ △ ◎ ○ △ △ ● ● ※ × ※ ※ ● ●...
  • Page 142: Installation Manual For Outdoor Unit

    PCA012D058A Check before installation work • Model name and power source INSTALLATION MANUAL FOR OUTDOOR UNIT • Refrigerant piping length Model FDC90VNP R410A REFRIGERANT USED • Piping, wiring and miscellaneous small parts Slee • Indoor unit installation manual Incl Accessories for outdoor unit Q’ty •...
  • Page 143 • Ensure that no air enters in the refrigerant circuit when the unit is  • Do not bundling, winding or processing for the power cord. Or, do not  • Do not perform any change of protective device itself or its setup condition.  4) Caution about selection of installa installed and removed.  deforming the power plug due to tread it.    The forced operation by short-circuiting protective device of pressure switch and    If air enters in the refrigerant circuit, the pressure in the refrigerant circuit    This may cause fire or heating.  temperature controller or the use of non specified component can cause fire or burst.  (1) If the unit is installed in the area where the snow w becomes too high, which can cause burst and personal injury.  • Do not run the unit with removed panels or protections.  The bottom plate of unit and intake, outlet may be •...
  • Page 144: Haulage And Installation

    Inclination plate Accessories for outdoor unit Q’ty Tape measure Charge hose (Designed specifically for R410A) Putty ts, power Hammer Flaring tool set (Designed specifically for R410A) Grommet (Heat pump type only) Drain hose (extension hose) Gas leak detector (Designed specifically for R410A) Spanner wrench Drain elbow (Heat pump type only) Piping cover...
  • Page 145 7) To run the unit for a cooling operation, [Refer to Drain piping work.] when the outdoor temperature is –5°C or lower. ●  Attached heater on a base plate on site, if there is possibility to freeze drain water. In case that the product has a corrective drainage system, the drainage paths should have suitable ● ...
  • Page 146   ● ° 〜 〜 〜 〜 〜 〜 〜 〜 ○ ① ○ ℃ ○ ② ○ < > ○ 〜 ○ 〜 〜 ● ● ● ※ ● ● ● ● ℃ ● ● ●...
  • Page 147 ● ● ● ● ●     ●   ●   ●   ●   ●   ●   ●   ●   ●   ●   ● ● ● ● ● ○ ○ ○ ● ● ○ ●...
  • Page 148 ● ○ ● ◎: ○: △: ◎ △ △ ◎ △ △ ● ● ※ × ※ ※ ● ●...
  • Page 149: Option Parts

    '13 • PAC-DB-194 12. OPTION PARTS 12.1 Wireless kit (1) FDT series (RCN-T-36W-E) PJF012D010 Notes : WIRELESS KIT INSTALLATION MANUAL Following functions of FDT Type-F indoor unit series are not able to be set with this wireless remote control (RCN-TC-36W-E). 1.
  • Page 150: How To Insert Batteries

    '13 • PAC-DB-194 Remote control Wireless remote control's operable area ① Standard reachable area of the signal Installation of the control holder [condition] Illuminance at the receiver: 300lux (when no lighting is installed within 1m of the receiver in an ordinary office.) Caution Ceiling surface DO NOT install it on the following places...
  • Page 151: Fden Series (Rcn-E1R)

    '13 • PAC-DB-194 PFA012D620 (2) FDEN series (RCN-E1R) WIRELESS REMOTE CONTROLLER INSTALLATION MANUAL PFA012D620 Notes : Following functions of FDEN Type-F indoor unit series are not able to be set with this wireless remote control (RCN-E1R). 1. Flap control system WIRELESS REMOTE CONTROLLER INSTALLATION MANUAL 2.
  • Page 152 '13 • PAC-DB-194 ③   FDEN Setting on site To change setting PCB on the receiver has the following 1. Remove the front panel. switches to set the function. 2. Remove four screws located on the back of the receiver and Default setting is shown with mark.
  • Page 153 '13 • PAC-DB-194 ③   FDEN (continued) Wireless remote control operation distance ① Standard signal receiving range ② Points for attention in connecting a plural [Condition] number of indoor units [Condition] Illuminance at the receiver area: 360 lux. (When no lighting xture is located within 1m of Illuminance at the receiver area: 360 lux.
  • Page 154 '13 • PAC-DB-194 ③   FDEN (continued) How to read the two-digit display A two-digit indicator (7-segment indicator) is provided on the receiver section. (1) An indication will be displayed for one hour after power on. (2) An indication appears for 3.5 seconds when a “Stop” command is sent from the wireless remote control while the air conditioner is not running.
  • Page 155: Fdu, Fdum, Fdf Series (Rcn-Kit3-E)

    '13 • PAC-DB-194 3.1 WIRELESS KIT (RCN-KIT3-E) (3) FDU, FDUM, FDF series (RCN-KIT3-E) Notes: ③ How to install the receiver Following functions of FDU indoor unit series are not able to be set with this wireless remote control (RCN-KIT3-E). 1. 4-fan speed setting (PHi/Hi/Me/Lo) 3-fan speed setting (Hi/Me/Lo) The following two methods can be used to install the receiver onto a ceiling or a wall.
  • Page 156 '13 • PAC-DB-194 ④ Remote control (B) Control plural indoor units with one remote control Up to 16 indoor units can be connected. Installation of the control holder ①Connect the XY terminal with 2-core wire. Restrictions on the thickness and length of wire As for the size, refer to the following note.
  • Page 157: Simple Wired Remote Control (Rch-E3)

    '13 • PAC-DB-194 12.2 Simple wired remote control (RCH-E3) Notes: Following functions of FDU indoor unit series are not able to be set with this simple wired remote control (RCH-E3).  1. 4-fan speed setting (PHi/Hi/Me/Lo) 3-fan speed setting (Hi/Me/Lo) Names and functions of sections Remote control sensor ON/OFF button Operation/Inspection lamp...
  • Page 158: Wiring Specifications

    '13 • PAC-DB-194 MITSUBISHI HEAVY INDUSTRIES,LTD. AIR-CONDITIONING & REFRIGERATION SYSTEMS HEADQUARTERS In case of embedding wiring Remote control installation dimensions Wall surface Wiring Wiring outlet Electrical box (In case of embedding wiring) (Prepare on site) 12×7 Slot hole Installation hole 9×4.5 Slot hole (2 places)...
  • Page 159 '13 • PAC-DB-194 In case of exposing cord Simple Remote Control Installation Manual PJZ012D069 ⑴   M ake certain to remove a screw on the bottom surface of the remote control. Read together with indoor unit's installation manual. WARNING ⑴ ●   F asten the wiring to the terminal securely and hold the cable securely so as not to apply Screw ⑵ Remove the upper case of the remote control.
  • Page 160 '13 • PAC-DB-194 3. Master/ slave setting when more than one remote control are used ⑴   U p to two remote controls can be connected to one unit (or one group) of indoor unit. Switch Setting Function detail Slave remote control indoor unit SW1-1 Master remote control...
  • Page 161 connecting section. Be careful about contact failure. unit. (No polarity of X and Y) 100 - 200m・・・・・・・・・・・・・・・・・0.5mm × 2 cores Under 300m・・・・・・・・・・・・・・・・・0.75mm × 2 cores ⑹   M ount the upper case for restoring to its former state so as not to crimp the remote control cord, Under 400m・・・・・・・・・・・・・・・・・1.25mm ×...
  • Page 162 ct failure. “88” blinks on the temperature setting indicator. (blinking for approximately 2 to 10 seconds while × 2 cores data is read) Then, the return air temperature is displayed. When AIR CON NO. is pressed, return × 2 cores to the indoor unit selection display (example, “U 000”).
  • Page 163: Filter Kit (Fdum Series)

    PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 PJZ012D076 Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating Installation Points and Operating...
  • Page 164 '13 • PAC-DB-194 3. Installation Points (1) Stick the insulation on both inner sides of the duct, leaving no space up and down. (Unit inside) BOTTOM Insulation Sticking standard position for insulation Duct (Unit outside) Insulation Duct Insu lation (*) After unpacking, bottom side of the unit is located at the upper side. (2) Install the rail on both inner sides of the duct with the screw.
  • Page 165: Interface Kit (Sc-Bikn-E)

    '13 • PAC-DB-194 12.4 Interface kit (SC-BIKN-E) RKZ012A088B Accessories included in package Safety precautions Before use, please read these Safety Precautions thoroughly before installation. Be sure to check all the accessories included in package. ●All the cautionary items mentioned below are important safety related items to be taken into consideration, so be sure to observe them at all times.
  • Page 166 '13 • PAC-DB-194 Installation of the interface ・Install the interface within the range of the connection cable length (approximately 1.3m) from the indoor unit. Wiring inlet ・Be sure not to extend the connection cable on site. If the connection cable is extended, malfunction may occur. ・Fix the interface on the wall, pillar or the like.
  • Page 167 '13 • PAC-DB-194 Functions of CNT connector It is available to operate the air conditioning unit and to monitor the operation status with the external control unit (remote display) by sending the input/output signal through CNT connector on the indoor control PCB. 0.75mm Note (1) 0.3mm ×2m...
  • Page 168 '13 • PAC-DB-194 Connection of wired remote control Regarding the connection of wired remote control, refer to the instruction manual of wired remote control. ①Switch ON the DIP switch SW2-2 (Factory setting : ON) on the interface PCB. DIP suitch Caution:Wireless remote control attached to the indoor unit can be used in parallel, after connecting the wired remote control.
  • Page 169: Super Link E Board (Sc-Adna-E)

    '13 • PAC-DB-194 12.5 Super link E board (SC-ADNA-E)
  • Page 170 '13 • PAC-DB-194...
  • Page 171: Technical Information

    2160 variable Rated air flow(outdoor) Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJF000Z314...
  • Page 172 Rated air flow(outdoor) 3780 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJF000Z314...
  • Page 173 Rated air flow(outdoor) 3780 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJF000Z314 167-1...
  • Page 174: Ceiling Suspended Type (Fden)

    Rated air flow(outdoor) 2160 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PFA003Z973...
  • Page 175 Rated air flow(outdoor) 3780 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PFA003Z973...
  • Page 176: Duct Connected-High Static Pressure Type (Fdu)

    Rated air flow(outdoor) 2160 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z160...
  • Page 177 Rated air flow(outdoor) 3780 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z160...
  • Page 178 Rated air flow(outdoor) 3780 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z160 171-1...
  • Page 179 Rated air flow(outdoor) 2160 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z159...
  • Page 180 3780 variable Rated air flow(outdoor) Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z159...
  • Page 181 Rated air flow(outdoor) Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PJG000Z159 173-1...
  • Page 182: Floor Standing Type (Fdf)

    Rated air flow(outdoor) 2168 Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PGA000Z812...
  • Page 183 3780 variable Rated air flow(outdoor) Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PGA000Z812...
  • Page 184 Rated air flow(outdoor) Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX. United Kingdom PGA000Z812 175-1...
  • Page 185: Wall Mounted Type (Srk)

    Rated air flow(outdoor) 2160 m3/h Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom PCA001Z722...
  • Page 186 Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.

Table of Contents