EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

8. USER LEVELS

Each user level type has access to specific menus according to the following table.
INFORMATION ONLY
H4 Present system status
H6 Display faults
H9 Interlocking outputs and inputs
H10 Change password
8.1.

USER LEVEL ACCORDING TO EN54-2

User level
User level type
EN54-2
-
1
2A
-
2B
Information only
2C
Building officer
3A
Service personnel
3B
-
4
-
1) Information only, i.e. the faults cannot be acknowledged.
2) Menu H9/C1 only.
8.1.1.

USER LEVEL 1

With the door closed, anybody has access to the push button "Alarms queued" to scroll / browse through the queued alarms.
BUILDING OFFICER
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calendar and clock
H4 Present system status
H6 Fault acknowledge
H7 Perform zone test
H9 Interlocking outputs and inputs
H10 Change password
Required action / equipment
No. (Hole in the Plexiglas.)
Fire brigade key. (To open the door.)
Like 2A + log on as "Information only"
Like 2A + log on as "Building officer"
Like 2A + log on as "Service personnel"
PC + EBLWin +
H/W key (EBLWin key)
PC + EBLWin + H/W key (EBLWin key) + a special password
SERVICE PERSONNEL
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calendar and clock
H4 Present system status
H5 Service
H6 FAULT Acknowledge
H7 Perform zone test
H8 Maintenance
H9 Interlocking outputs and inputs
H10 Change password
Access to
Alarms queued button.
Like 1 + Silence
buzzer, Silence alarm devices & Reset buttons.
Like 2A + keypad.
Menu H4, H6
H9
& H10
2
Like 2A + keypad. H1-H4, H6, H7, H9 & H10
Like 2A + keypad.
H1-H10
SSD & S/W download
SSD & S/W download + reset of alarm counter.
23
,
1