EMERGENCY LUMINAIRES WITH 1 WHITE POWER LED
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
GENERAL
These devices are used indoors (ta 40 C) in
places where emergency luminaires are
needed. The luminaires GR-290 and GR-
292 are suitable for corridors lighting and
the GR-291 and GR-293 for open area
lighting. Each device must be permanently
connected to mains power supply. In
normal operation the battery is charging. In
case of a mains power supply failure the
device will light the illumination led
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 2.
Battery Charging
The
battery
charging
controlled. In this case, is achieved the
perfect battery maintenance , as well as
the elongation of its duration. When the
battery has completely charged, it charges
with a maintenance current.
Battery Cut-off
The device enters this mode when the
mains power supply fails and battery has
Page 1 from 5
NON MAINTAINED SELF TESTING SPOT LIGHT
GR-290
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
is
completely
(for LED MODULE specifications see page 4)
GR-291
220-240V AC / 50-60Hz
3.7W / 4.1 VA
4.8V/1.2Ah
Deep discharge and overcharge protection
Charge, lamp fault, battery fault, TEST button
24 hours
1.5 hour
1 white power LED
270lm
IP40
5 to 40 C
Up to 95%
ABS/PC, PC
Ø125 x 65 mm
435gr.
3 years (1 year for the battery)
lost its energy. During this operation the
device enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Test
This test can be done by pushing the test
button. The light source and the emergency
circuit of the device is monitored. The
manual test can be conducted only if the
main power supply and the battery is
connected. During this test period all
indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The
Automatic
conducted and measures the device's back
up operation and emergency duration. The
BATTERY FAULT LED blinks during
measurement, indicating this process to the
user. This test is conducted automatically
every six months. In order to be performed,
the mains power supply and the battery
should be connected and fully charged. If
GR-292
GR-293
3 hours
160lm
o
Autonomous
Test
923292000_09_016
is
the