Checking The Firing Rate; High Altitude Installations - State Water Heaters 301 Series Instruction Manual

Hide thumbs Also See for 301 Series:
Table of Contents

Advertisement

CHECKING THE FIRING RATE

Follow these instructions to determine the actual firing rate of the
water heater:
Note: The heaters covered by this manual are capable of
modulating their firing rate. The firing rate should be
checked with the heater operating at it's full firing rate.
1. Ensure there are no other gas fired appliances connected to
the gas meter firing during this test.
2. Contact the gas supplier to determine the heating value, in Btu
per cubic foot, of the gas supply.
3. Connect a manometer to the supply gas pressure tap. Follow
the instructions for
Start Up
4. Start the water heater and ensure it is firing.
5. Check the supply gas pressure, refer to
correct pressure.
6. Locate the gas meter serving the water heater.
7. Time how long (in seconds) it takes for one cubic foot of gas
to be used while the water heater is firing with a stop watch.
8. Use the formula below to "clock" the gas meter and determine
the actual firing rate of the water heater based on the heating
value (Btu per cubic foot) of the gas supply:
3600
x H = Btu/hr
T
Example:
3600
x 1050 = 300,000 Btu/hr (87.9 kW)
12.6
3600 = seconds in one hour.
T = time, in seconds, to burn one cubic foot of gas.
H = heating value of gas in Btu per cubic foot.
Btu/hr = actual firing rate of the water heater.
Note: 1050 Btu per cubic foot is a standard value for natural
gas. Standard propane gas Btu content is 2500 Btu
per cubic foot. Btu values may change in certain
areas and at high elevations. Check with the local gas
utility company.
TO TURN OFF GAS SUPPLY
1. Change the Operating Set Point to the lowest temperature
setting, see
Operating Set Point and Differential Adjustment
48).
2. When the water heater has completed its shut down sequence
and enters the standby mode, turn the water heater's Enable/
Disable switch to the "Disable" position. When in the "Disable"
position the switch only removes electrical power from the gas
valve so that water heating is disabled. The display, CCB, and
other electrical components will still be energized and the display
will read "Water Heating Disabled".
3. Close Main Gas Shutoff Valve, see
(page 53).
(page 11) for
Table 4
(page
(page 40).
Figure 54

HIGH ALTITUDE INSTALLATIONS

Fire and Explosion Hazard
Under no circumstances should the
input exceed the rate shown on the
water heater's rating label.
Overfiring could result in fire or
explosion.
Gas and carbon monoxide detectors are
available.
Breathing Hazard - Carbon Monoxide Gas
Under no circumstances should
the input exceed the rate shown
on the water heater's rating label.
Overfiring could result in damage to
the water heater and sooting.
Gas and carbon monoxide detectors
are available.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
The water heaters covered by this manual are certified for use
without modification for altitudes up to 10,100 feet (3,078 m).
Most gas utility companies de-rate their gas for high altitudes,
making it unnecessary to install high altitude orifices.
Note: The actual firing rate of the water heater must not
exceed the input rating on the water heater's rating
label under any circumstances.
Note: Due to the input rating reduction at high altitudes,
the output rating of the water heater is also reduced
and should be compensated for in the sizing of the
equipment.
56

Advertisement

Table of Contents
loading

Table of Contents