York J10ZJ Instruction Manual page 30

Table of Contents

Advertisement

5167530-JIM-H-0218
J06 thru 12ZJ Physical Data (Continued)
Component
Nominal Tonnage
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
Type
Drive type
Quantity of motors
Motor HP each
No. speeds
RPM
Total CFM
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
Motor Sheave
Blower Sheave
Belt
Motor HP each
RPM
Frame size
FILTERS
Quantity - Size
1. Cooling Only Unit or Cooling Unit with Electric Heat
2. Cooling Unit with Gas Heat
st
3. 1
Stage 60% of Full Capacity.
4. J10ZJ, J12ZJ have crankcase heaters standard.
5. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
6. 2 In. Pleated, Optional, MERV 8.
7. 4 In. Pleated, Optional, MERV 13.
30
J06ZJ
J07ZJ
6.5
7.5
2
24
Prop
Prop
Direct
Direct
2
1/3
3/4
1
850
1110
7400
8000
1
15 x 15
15 x 15
Centrifugal
Centrifugal
1VL40
1VM50
1VL40
AK74
AK74
AK69
A53
A54
A52
1-1/2
2
1-1/2
1725
1725
1725
56
56
56
5,6
4 - (24 x 20 x 2)
4 - (24 x 20 x 2)
7
4 - (24 x 20 x 4)
4 - (24 x 20 x 4)
Models
J08ZJ
8.5
2
2
24
24
Prop
Direct
2
2
3/4
1
1
1110
9000
1
1
15 x 15
Centrifugal
1VM50
1VM50
1VM50
AK69
AK89
AK74
A54
A56
A54
3
2
3
1725
1725
1725
56
56
56
5,6
4 - (24 x 20 x 2)
7
4 - (24 x 20 x 4)
J10ZJ
10
2
24
Prop
Direct
2
3/4
1
1110
9400
1
15 x 15
Centrifugal
1VM50
1VM50
1VM50
AK84
AK74
AK74
A56
A54
A54
2
3
1725
1725
1725
56
56
5,6
5,6
4 - (24 x 20 x 2)
4 - (24 x 20 x 2)
7
7
4 - (24 x 20 x 4)
4 - (24 x 20 x 4)
Johnson Controls Unitary Products
J12ZJ
12.5
4
24
Prop
Direct
4
1/3
1
850
14000
1
15 x 15
Centrifugal
1VP56
BK77
BX56
3
5
1725
56
184T
5,6
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

J zj seriesJ12zj

Table of Contents