SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LED's
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of Olympia
Electronics. A European manufacturer.
GENERAL
These luminaires are suitable for marine and
offshore applications where emergency light is
needed. Each luminaire must be permanently
connected to mains power supply. In normal
operation the led strip lights and the battery is
charging. In case of a mains power supply
failure
the
luminaire
automatically in emergency mode (powered by
its battery). When the mains power supply is
restored the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 4.
Battery Charging
The battery charging is completely controlled. In
this case, the best possible battery maintenance
is achieved, as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is connected.
By pressing the test button briefly an operation
test is initiated. During this test period all
indication LEDs are OFF.
Page 1 from 4
GR-316/15L/MAR
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, IEC 60092-306, IEC 60533
will
light the led strip
High Quality European based Manufacturers
220-240V AC/50-60Hz
3.5W / 7VA
3.6V/1.5Ah
From overcharge and full discharge
Charge, lamp fault, fault indication LED, TEST button
24h
180min
15 white LED's
105lm / 105lm
IP 40
5 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
350 x 134 x 45 mm (CRV 362 x 134 x 58 mm)
700gr.
3 years (1 year for the battery)
Automatic Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire`s back up operation.
This test is conducted automatically every six
months. In order to be performed, the main
power supply and the battery should be
connected (the battery should be charged). If the
battery is not charged, the test is postponed until
the battery is completely charged. If during the
Automatic Autonomous Test the luminaire's
duration is lower than the nominal, then the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the technical characteristics. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the Test button for 5 seconds, to extinguish
all the indicated LED errors. Then the luminaire
enters regular operation mode.
Indication LED status (with connected mains
power supply).
Charge
On: Good charge current.
Οff: No battery (No charging current
or disconnected battery).
Lamp Fault with L1 connected to L
GR-316/30L/MAR
5W / 8VA
3.6V/3Ah
30 white LED's
210lm / 210lm
o
770gr.
923316017_09_003

Advertisement

loading

Summary of Contents for olympia electronics GR-316/15L/MAR

  • Page 1 High Quality European based Manufacturers SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LED’s TECHNICAL CHARACTERISTICS GR-316/15L/MAR GR-316/30L/MAR OPERATION VOLTAGE 220-240V AC/50-60Hz MAXIMUM POWER CONSUMPTION 3.5W / 7VA 5W / 8VA BATTERIES (Ni-Cd) 3.6V/1.5Ah 3.6V/3Ah BATTERY PROTECTION From overcharge and full discharge...
  • Page 2 Οn (with LED strip off): Faulty LED strip (must 2. The device must be connected to the mains be replaced). power supply through a fuse dependent by the Οn (with LED strip on): Problem in the back up total amount of the line’s power load. circuit of the LED strip (must be checked by an In case of battery or lamp replacement, these authorized personel).
  • Page 3 Mounting methods All “Easy Light” can be mounted either surface or recess mounted in walls or suspended ceilings. For recess mounted installations, special accessories are required which can be found in the catalog and must be ordered separately. Suspended ceiling installation. On the bottom of the base plastic of the Easy light luminaire there are two H shaped cut outs.
  • Page 4 INSTALLATION INSTRUCTIONS Reflector Base plastic Diffusor Cable entry channels Luminaire mounting holes Base plastic 1 To install the luminaire you must dismantle it into 3 parts. 2 Place a flat blade screwdriver in the area Α to release the diffusor’s plastic hook.

This manual is also suitable for:

Gr-316/30l/mar