1. IO-SA0400Y is an analog input module which has 4ch voltage/current Input.
IO-SA0800Y is an analog input module which has 8ch voltage/current input.
IO-SA0004V is an analog output module which has 4ch voltage output (-10–10 V, 0–
10 V).
IO-SA0004C is an analog output module which has 4ch current output (4–20 mA).
IO-SA0202Y is an analog input and output mixed module which has 2ch
voltage/current input and 2ch voltage/current output.
2. DA conversion module converts digital value, 16-bit binary data (data: 14-bit) from
PLC CPU, into analog signal (voltage or current output). It converts digital value 0–
16000 (-8000–8000)/0–64000 (-32000–32000) to analog value 0–20 mA, 4–20 mA, -
10–10 V, 0–5 V, 0–10 V, 1–5 V.
3. AD conversion module converts input max. and min. value into 0–16000 (-8000–
8000).
If input value gets out of the range, it converts into -192–16191 (8192–8191). If value
gets out of this, -192–16191 (-8192–8191) is fixed.
4. There are two AD conversion methods:
A. Average processing
B. Sampling processing
5. Through "Hold Clear" function, DA module can output offset value (4 mA, -10 V) when
RUN mode changes to STOP mode or maintain output value being with RUN mode.
6. If the channel that is converting is prohibited, it will output the minimum value of each
output mode. (0 mA, 4 mA, -10 V, 0 V, 1 V)
7. Users can set up Offset/Gain value through the MAPLELOGIC Ladder Program.
8. Up to 11 analog modules can be added as an expansion module.
9. Normal status: LED On, Error status: LED blinking by 0.5 seconds interval.
Features of Analog Module
- 10 -