Apollo XP95A Series - Smoke & Heat Detector Installation Manual

General

These instructions apply to Apollo detector base 45681-210, to variants of this base and to the associated ranges of UL listed XP95A and Discovery detectors which are listed overleaf.

Installation

These products must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of the detectors to report an alarm condition. Apollo Fire Detectors Limited is not responsible for detectors which are improperly installed, maintained and tested.

The FM approval for these initiating devices does not include or imply approval of the control unit to which it may be connected. In order to maintain an FM approved system, these initiating devices must be listed with an FM approved compatible control panel. For more information on RTI classification refer to FM class standard 3210.

Before installing these products check the continuity, polarity and insulation resistance of all wiring. Check that installation is in accordance with the fi re system drawings and conforms to all applicable local codes such as NFPA 72.

Use 3" octagonal box for direct connection to the base. 4" octagonal and 4" square boxes may be used with proper UL listed mounting brackets. When mounting on a wall, install 4" to 12" from the ceiling. Use 3M Weatherban 606 Non-Flammable sealing compound (or equivalent) to seal fi eld wiring conduit opening in the electrical box, this will reduce the stack effect. Secure the base to the electrical box with appropriate screws. Do not overtighten the screws. The raised mark on the side of the base indicates the direction of the detector LED when fitted. Connect the shield, if required, to the SHIELD terminal on the base. For information on how to set the address of each device correctly refer to the section 'Address Setting' overleaf.

Wiring


Do not use looped wire under wiring terminals. Break wire run to provide supervision of connections. Terminals L1 and L2 are polarity insensitive.

Wiring - Part 1
Fig. 1- Wiring diagram of XP95A/Discovery loop with single remote indicator

Wiring - Part 2
Fig. 2- Wiring diagram of XP95A/Discovery loop with common remote indicator

The above instructions cover the following base models:

45681-210 4" mounting base
45681-225 6" mounting base
45681-234 6" low profi le mounting base
45681-250 E-Z Fit 6" mounting base

Address Setting

Refer to the table below for the complete list of address settings. Select the desired address and remove the pips indicated in black. Remove pips with a small screwdriver.

Address Setting

Technical Data XP95A

Detector Model No. 55000-450 55000-550/555* 55000-650 55000-886
Detector Type Heat Ionization Photoelectric Multisensor
Working Voltage 17-28V dc 17-28V dc 17-28V dc 17-28V dc
Modulation Voltage (V peak to peak) 5-9V 5-9V 5-9V 5-9V
Maximum Alarm Current LED on 2.5mA 2.5mA 4.5mA 3.5mA
Surge Current 1.0mA 1.0mA 1.0mA 1.0mA
Supervisory Current 250μA 280μA 340μA 500μA
Heat Element Rating 131ºF (55ºC) N/A N/A N/A
Compatibility Identifi er 55000-450 55000-550/555* 55000-650 55000-886
Test Method
  • Hair dryer
  • Home safeguard
  • Gemini 501
  • Home safeguard
  • Gemini 501
  • Home safeguard
  • Gemini 501
Control Panel Refer to: www.apollo-fire.co.uk for compatible panels.

*Please note 55000-555 is ULC listed only.

Technical Data Discovery

Detector Model No. 58000-450 58000-550 58000-650 58000-750
Detector Type Heat Ionization Photoelectric Multisensor
Working Voltage 17-28V dc 17-28V dc 17-28V dc 17-28V dc
Modulation Voltage (V peak to peak) 5-9V dc 5-9V dc 5-9V dc 5-9V dc
Maximum Alarm Current LED on 3.5mA 3.5mA 3.5mA 3.5mA
Surge Current 1.0mA 1.0mA 1.0mA 1.0mA
Supervisory Current 500μA 400μA 500μA 500μA
Heat Element Rating 135ºF (57ºC)
-210ºF (99ºC)
N/A N/A 135ºF (57ºC)
(Mode 5)
Compatibility Identifi er 58000-450 58000-550 58000-650 58000-750
Test Method
  • Hair dryer
  • Home safeguard
  • Sensitivity test
  • No Climb
  • Gemini 501
  • Home safeguard
  • Sensitivity test
  • No Climb
  • Gemini 501
  • Home safeguard
  • Sensitivity test
  • No Climb
  • Gemini 501
  • Hair dryer (heat sensor only)
Control Panel Refer to: www.apollo-fire.co.uk for compatible panels.

©Apollo Fire Detectors Ltd 2017
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.com Website: www.apollo-fire.co.uk
In the USA: Apollo America Inc., 25 Corporate Drive, Auburn Hills, Michigan, 48326, USA Tel: (248) 332-3900 Fax: (248) 692-0888
Email: info.us@apollo-fire.com Website: www.apollo-fire.co.uk

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Apollo XP95A Series - Smoke & Heat Detector Installation Manual

Advertisement

Need Assistance?

Do you have a question about the XP95A Series that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents