Wiring the AMPS-24/E
2.7.3 Connecting to the AUX 24 Output
TB3 - This output supplies one non-resettable, power-limited (Class 2) (when set for less than 5A),
filtered 24VDC circuit available to power external devices. It may be used to power the DS-DB when
connected to TB24 on the DS-DB. This application requires that the AMPS-24 be monitored by an
FACP.
The output can be configured to provide 3A or 5A maximum current, or it can be disabled. Refer to
Section 3.2.6 on page 34.
2.7.4 Connecting to the SLC
TB2 - Supervised and power-limited (Class 2). With all power sources off, connect the power
supply from TB2 to the SLC interface.
NOTE: Do not connect the AMPS-24 to the SLC if the AMPS-24 is communicating via 485
trouble reporting. (Refer to "Trouble Reporting" on page 36.)
See
"SLC Addressing" on page 30
Refer to the SLC Wiring Manual for more information.
Optional 4-wire
Return Loop
Style 6 (Class A)
AMPS-24 Manual — P/N 51907:J2 02/26/2014
TB3
+24V
COM
AUX 24V
Figure 2.13 Connecting to the AUX 24V Output TB3
.
+
SLC A
TB2
A+
Figure 2.14 Connecting to the SLC Interface TB2
+24V
COM
SLC B
A-
B+
B-
SLC
Installation
+24V
COM
COM
+24V
+
To SLC
Interface