Controlling all Three Inputs with One Control Module
B.5 Controlling all Three Inputs with One Control Module
In this application, all three command inputs are being controlled by one multi-module, the SK-CONTROL-6 mounted inside the cabinet.
Output #1 is being used for 24 VDC aux power. Any output circuit may be configured to any input.
TB4
TB15
The following notes apply to Figure B.5.
•
An End-of-Line Resistor must be installed between terminals 1 and 4 for control module wiring supervision (the ELR value is
dependent on the module/FACP employed).
•
Either disable the unused addresses or install ELRs across unused outputs on the SK-CONTROL-6.
•
Refer to Section 3 for instructions on setting the DIP switches.
•
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
•
For a list of compatible devices, refer to the Silent Knight Device Compatibility Document #52612.
•
Refer to the SLC Wiring Manual for more information.
SK-PS Series Instruction Manual — P/N LS10227-002SK-E:C 2/2/2022
NO NC C
NO NC C
ZNAC-PS
Class A Converter
Option Module
Figure B.5 Controlling Three Inputs with One Module
24V Aux
Power
NAC1
AUX1
NAC2
AUX2
SK-CONTROL-6
Application Examples
SLC
47