2.4 Control Unit Connections:

The following 4 connectors are placed at the top of the Control Unit:
FAULT (C) Fault Relay Common
FAULT (NC) Normally Closed Contact
FAULT (NO) Normally Open Contact
The faul t rel ay may be li nked to an analogue
input modu le to report any fault t o a third
equipment li ke a FACP ( Fire Alarm Control
Panel).
IN ALARM (+)
IN ALARM (-)
Alarm input to d isable, momen tarily, t he battery c harger and b e able to supp ly 300 -
600mA from ba ttery loa d to the ou tputs. Fo r th is, i t is necessa ry to l ink both IN
ALARM terminals by means of a jumper or short-circuit.
When this input is activated, the control unit will have an extra current of battery load
0.3 A or 0.6 A, depending on the DIP SW2 for outputs. Thus, if the power supply is in
Overload (Imax) sta te, the i ndication w ill d isappear by ac tivating this input, p rovided
that the excess current is the current which is supplying batteries.
PSO1 Output 1 (+)
PSO1 Output 1 (-)
PSO2 Output 2 (+)
PSO2 Output 2 (-)