Safety function
12
I [mA]
A
B
C
A
HI-Alarm ≥21 mA
B
Error range ±2 %
C
LO-Alarm ≤3.6 mA
4.3.1
Dangerous undetected failures in this scenario
A dangerous, undetected failure is considered to be an incorrect output signal that deviates
from the real value by more than 2 %, wherein the output signal is still in the range of
4 to 20 mA or the relay contact remains closed.
Proserve NMS80
2
1
3
4
3
t
Endress+Hauser
A0025264
Need help?
Do you have a question about the Proserve NMS80 and is the answer not in the manual?
Questions and answers